2
2. UNPACKING, TRANSPORTING, AND STORING
2.1. Unpacking and Transporting
1)
The batteries are filled with electrolyte and charged before shipping.
2)
Please unpack close to the area for installation.
3)
After unpacking, count the number of batteries and accessories to check if any items are missing and
also inspect for any visible damage.
CAUTION
Take the necessary precautions to avoid physical shocks to the batteries when
unpacking, as they may cause the batteries to break.
If a crack in the case, leakage or any other abnormalities are found at the time of
unpacking, do not use the batteries and please contact GS Yuasa. If used, the battery
may short circuit, cause a fire, or break.
Do not hold the terminals when carrying the batteries. Doing so may cause the
batteries to break. Please always follow the methods specified by GS Yuasa.
When temporarily suspending or lifting the batteries, please follow the standard
procedure described in
Table 1
below.
When carrying the batteries, avoid strong physical shocks such as banging and dropping,
as such shocks may cause the batteries to break.
Please take precautions when transporting the batteries to avoid injury and back pain.
Table 1 Standard Procedure for Transporting and Temporarily Suspending or Lifting Batteries
Battery Type
Suspending and Lifting Temporarily
Transporting
SLR-1000
SLR-500
Use Jig to lift up battery supporting lid
Use hand truck, cart or
something to move smoothly
2.2. Battery storage
The batteries gradually lose their capacity, even if they are not used, due to self-discharge. Please charge
the batteries according to the instructions shown in
Section 4.1.
The charging requirements may vary
depending on the temperature of the storage area. Please refer to
Table 2
below as a guideline. If possible,
the batteries should be stored in a dry place and at a low temperature.
Table 2 Guideline for Charging Intervals
Storage Temperature
25
℃
or less
30
℃
or less
35
℃
or less
40
℃
or less
Fresh Charge Interval
Within 6 months
Within 4 months
Within 3 months
Within 2 months
WARNING
Please ventilate the battery storage area. The batteries emit hydrogen gas even at rest, which
may cause fire or explosion if not ventilated.
CAUTION
When storing, disconnect the batteries from the load and the charger and store in the conditions specified in
the Installation Environment section. Charge the batteries to compensate for self-discharge. Failure to do so
may result in the breakage or deterioration of the batteries.
Содержание SLR-1000
Страница 22: ... 17 9 3 System Drawing 9 3 1 System Name RE SLR48VSYS 02 48kWh 48V system with SLR1000 ...
Страница 23: ... 17 9 3 2 System Name RE SLRC50048 01 24kWh 48V system with SLR500 ...
Страница 24: ... 17 9 3 3 System Name RE SLR24VSYS 01 24kWh 24V system with SLR1000 ...
Страница 25: ... 17 9 3 4 System Name RE SLRC50024 01 12kWh 24V system with SLR500 ...