![gs yuasa SLR-1000 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/gs-yuasa/slr-1000/slr-1000_instruction-manual_2274811011.webp)
8
5. HANDLING and OPERATION
WARNING
Risk of fire, explosion or burns. Do not disassemble, heat above 50
℃
or
incinerate.
When handling the batteries, avoid causing a short circuit between the positive
(+) and negative (-) terminals. A short circuit may cause leakage, heat generation,
ignition, explosion, fire, and/or smoke.
Place the insulation covers over the terminals and connectors properly. Not doing
so may cause an electric shock or short circuit, and may result in breakage, burn,
ignition and explosion.
CAUTION
The batteries should be handled by professionals such as certified technicians.
Mishandling may occur if they are handled by less qualified personnel.
When handling and using the batteries, observe the precautions listed below to avoid
leakage, heat generation, ignition, explosion, and/or smoke. Please take these
precautions to ensure safety:
a) Do not heat or throw the batteries into fire.
b) Do not disassemble or modify the batteries.
c) Do not charge or use the batteries with a reversed connection [between the
batteries] in which the positive (+) terminal is connected to the negative terminal
(-).
d) Do not mix and use different types and brands of batteries together.
e) Do not cause a strong physical shock or drop the batteries.
f) Avoid partially replacing batteries and use new and old batteries together.
This battery has regulating valves inside. Do not touch the valves. Touching them may
cause performance deterioration, shorter life, and rupture of the batteries.
Store the battery in an air-conditioned facility and keep the temperature between 5
℃
and 30
℃
. If the ambient temperature becomes lower than -15
℃
, discharging is not
only working but also electrolyte may freeze, which cause the batteries to break. In an
environment where the ambient temperature is constantly above 45
℃
, the batteries
deteriorate more rapidly, which may cause the batteries to break.
Maintain ambient temperature variation within ±5
℃
. Cells within a string should be
maintained within 5°C of other cells in that string. Temperature differences may result
in decreased battery life.
Содержание SLR-1000
Страница 22: ... 17 9 3 System Drawing 9 3 1 System Name RE SLR48VSYS 02 48kWh 48V system with SLR1000 ...
Страница 23: ... 17 9 3 2 System Name RE SLRC50048 01 24kWh 48V system with SLR500 ...
Страница 24: ... 17 9 3 3 System Name RE SLR24VSYS 01 24kWh 24V system with SLR1000 ...
Страница 25: ... 17 9 3 4 System Name RE SLRC50024 01 12kWh 24V system with SLR500 ...