ECOTRONIC tech
Cod. 3540V010 - 07/2010 (Rev. 00)
108
EN
H19
No. litres solar circuit (litres)
Only with Flowmeter connected and activated
between 0 and 9999 litres
H20
Average circulating pump speed (%)
Cumulative calculation performed only if the circulating pump is working
0-100%
BIL
Thermal Quantity Balance (kWh)
Cumulative calculation performed only if the circulating pump is working
between 0 and 9999 kWh
Press the Up/Down buttons to scroll the list of faults. To display the value press the Enter button in relation to
the parameter.
Press the Enter button to return to the list of faults.
Press the Info button to return to the Service Menu. Press the Info button for 10 seconds to exit the card Service
Menu or exiting is automatic after 15 minutes.
"rE" - History Reset
Press the ON/OFF button for 3 seconds to delete all the information stored in the History Menu: the card will
automatically exit the Service Menu, in order to con
fi
rm the operation.
Press the Info button for 10 seconds to exit the card Service Menu or exiting is automatic after 15 minutes.
Thermal quantity balance (Calculation)
The Regulator performs the accumulated energy calculation only if the Solar Circulating Pump is working: the
value is then displayed through the parameter BIL in the History menu; see the Service Menu section.
ATTENTION: This function depends on the value of parameter P15 Thermal Quantity Balance (Installer para-
meter, default equal to 0=Off) which must be set to 1.
Non-modulating circulating pump (without fl owmeter)
The value of the following parameters must be correctly set:
-
P16
Solar circuit max.
fl
ow rate (l/min)
-
P18
Antifreeze liquid protection rating (%)
-
P23
Solar circulating pump operation (0=On/Off).
Accumulated energy (kWh) =
Value P16 * 60 x (deltaT: S3 – S4) x 1.163 x ((100-Value P18)/100) / 1000
Modulating circulating pump (with fl owmeter)
The value of the following parameters must be correctly set:
-
P18
Antifreeze liquid protection rating (%)
-
P23
Solar Circulating Pump operation (1 = Modulating)
-
P25
Flowmeter type selection.
Accumulated energy (kWh) =
Value measured by
fl
owmeter *60 x (delta T:S3-S4) x 1.163 x ((100-valueP18)/100)/1000
Note
The regulator performs the instantaneous calculation every second and updates the value of parameter BIL every
time the accumulated energy increases by 1kW.
In case of a power failure, the Regulator does not lose the accumulated energy calculation: the data is saved
every 10 minutes, therefore when the power is restored and the Solar Circulating Pump restarts, the calculation
can begin again without loss of data.
Содержание ECOTRONIC tech
Страница 6: ...ECOTRONIC tech IT Cod 3540V010 07 2010 Rev 00 6 Dimensioni ...
Страница 43: ...ECOTRONIC tech 43 Cod 3540V010 07 2010 Rev 00 ES Medidas ...
Страница 81: ...ECOTRONIC tech 81 Cod 3540V010 07 2010 Rev 00 EN Dimensions ...
Страница 118: ...ECOTRONIC tech Cod 3540V010 07 2010 Rev 00 118 Dimensions FR ...
Страница 155: ...ECOTRONIC tech 155 Cod 3540V010 07 2010 Rev 00 NL Afmetingen ...
Страница 192: ......