10. Fault finding

11. Disposal

This product or parts of it must be disposed of in an 
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company 

or service workshop.

Subject to alterations.

DANGER

Electric shock

Death or serious personal injury
- Before starting any work at the pump, switch off 

the power supply. Make sure that the power supply 
cannot be switched on accidentally.

- Be aware that capacitors will be live up to 30 

seconds after the power supply has been switched 
off.

Before dismantling the circulator, drain the system, 
or close the isolating valves on either side of the 
circulator.

CAUTION

Hot liquid

Minor or moderate personal injury
- The pumped liquid may be scalding hot.

CAUTION

Pressurised system

Minor or moderate personal injury
- The pumped liquid may be under high pressure.

Fault

Power supply

Cause

Remedy

1. The pump does not run.

No power supply.

a) The system is switched off.

Check the system controller.

b) One fuse in the installation is 

blown.

Replace the fuse.

c) The current-operated or 

voltage-operated circuit 
breaker has tripped.

Cut in the circuit breaker.

d) Power supply failure.

Check that the power supply falls within 
the specified range.

Normal power supply.

a) The controller has switched off. Check the controller and its settings.
b) The pump is blocked by 

impurities.

Remove the impurities.

c) The pump is defective.

Replace the pump.

2. The pump cannot be 

controlled and only runs at 
maximum speed.

Normal power supply.

a) No signal through the signal 

cable.

Check if the cable is connected to the 
controller. If yes, replace the cable.

3. Noise in the system.

Normal power supply.

a) Air in the system.

Vent the system.

b) The outlet pressure is too high. Reduce the setting of the controller or 

the valve.

4. Noise in the pump.

Normal power supply.

a) Air in the pump.

Let the pump run. The pump vents itself 
over time.

b) The inlet pressure is too low.

Increase the inlet pressure or check the 
air volume in the expansion tank, if 
installed.

5. Insufficient flow.

Normal power supply.

a) The pump performance is too 

low.

Check the controller and its settings.

b) The hydraulic system is closed 

or the system pressure is 
insufficient.

Check the check valve and filter. 
Increase the system pressure.

UPMM_UPML_UPMXL_US.book  Page 15  Tuesday, February 26, 2019  10:18 PM

Содержание UPML

Страница 1: ...GRUNDFOS INSTRUCTIONS UPML UPMXL Installation and operating instructions UPMM_UPML_UPMXL_US book Page 1 Tuesday February 26 2019 10 18 PM...

Страница 2: ...2 UPMM_UPML_UPMXL_US book Page 2 Tuesday February 26 2019 10 18 PM...

Страница 3: ...nt for more than thirty 30 days and canceling any balance still owing on the equipment or c in the case of service at the seller s option redoing the service or refunding the purchase order amount of...

Страница 4: ...or circulating liquids in heating and air conditioning systems They are suitable for cold water applications and can be integrated in geothermal heating pumps DANGER Indicates a hazardous situation wh...

Страница 5: ...zard Death or serious personal injury In domestic hot water systems the temperature of the pumped liquid must always be above 122 F 50 C due to the risk of legionella WARNING Biological hazard Death o...

Страница 6: ...MXL Nominal diameter DN of inlet and outlet ports mm Maximum head dm _ N F Cast iron pump housing Stainless steel pump housing 2 bolt flanges Port to port length mm AUTO PWM VDC Internally controlled...

Страница 7: ...th or serious personal injury Before dismantling the pump drain the system or close the isolating valve on either side of the pump before the screws are removed The pumped liquid may be scalding hot a...

Страница 8: ...iquid may be scalding hot and under high pressure CAUTION Hot surface Minor or moderate personal injury Position the pump so that persons cannot accidentally come into contact with hot surfaces Do not...

Страница 9: ...of filter damage Ground fault circuit interrupter GFCI If the pump is connected to an electrical installation where a ground fault circuit interrupter GFCI is used for additional protection this Groun...

Страница 10: ...e has two or three leads The signal cable must be connected to the control box by a dubox housing with an FCI terminal block and terminals Fig 10 VDC signal cable connection The ground symbol identifi...

Страница 11: ...s feedback signal The PWM frequency of the feedback signal is fixed at 75 Hz in the pump Duty cycle d 100 x t T Fig 11 PWM signal Fig 12 PWM input profile A heating PWM feedback signal Power consumpti...

Страница 12: ...ted input voltage low level UIL 1 V High level input current IIH 10 mA Input duty cycle PWM 0 100 PWM frequency output open collector f 75 Hz 5 Accuracy of output signal regarding power consumption 2...

Страница 13: ...mA Input duty cycle PWM 0 100 PWM frequency output open collector f 75 Hz 5 Accuracy of output signal regarding power consumption 2 of PWM signal Output duty cycle PWM 0 100 Collector emitter breakdo...

Страница 14: ...rial curve setting For first start up Start at factory pre setting If a setting has already been selected Start at the actual setting Press the button for two seconds The pump enters setting mode and...

Страница 15: ...The current operated or voltage operated circuit breaker has tripped Cut in the circuit breaker d Power supply failure Check that the power supply falls within the specified range Normal power supply...

Страница 16: ...16 UPMM_UPML_UPMXL_US book Page 16 Tuesday February 26 2019 10 18 PM...

Страница 17: ...17 UPMM_UPML_UPMXL_US book Page 17 Tuesday February 26 2019 10 18 PM...

Страница 18: ...18 UPMM_UPML_UPMXL_US book Page 18 Tuesday February 26 2019 10 18 PM...

Страница 19: ...2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS M xico Boulevard TLC No 15 Parque Industrial Stiva Aeropuerto C P 66600 Apodaca...

Страница 20: ...e Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S www grundfos com UPMM...

Отзывы: