English (GB)
13
7.3.1 Setting in connection with pump replacement
If an uncontrolled pump is to be replaced with a
UPE(D) FZ pump, settings can be made according to
the tables below.
Read the tables as follows:
•
If the maximum head of the existing pump is
6 metres and the pump is running at maximum
speed under normal operating conditions, it is
recommended to set the pump to 3 metres and to
select proportional pressure.
•
If, however, the existing pump is running at a
reduced speed, it is recommended to set the
pump to 2 metres and to select constant
pressure.
7.4 Max. or min. curve duty
To be set on the control panel, with the R100 or a
building management system via bus. It is not
possible to set max. curve duty via the external
input.
The pump can be set to operate according to the
max. or min. curve, like an uncontrolled pump.
See fig. 10.
Fig. 10
Max. and min. curves
The
max. curve
mode can be selected if an
uncontrolled pump is required. See section
. In this operating mode, the pump
will operate independently of an external controller,
if installed.
The
min. curve
mode can be used in periods in
which a minimum flow is required. This operating
mode is for instance suitable for night-time duty.
7.5 Constant-curve duty
To be set with the R100.
The pump can be set to operate according to a
constant curve, like an uncontrolled pump.
Select one of the curves between the max. and
min. curves. See fig. 11.
Fig. 11
Constant-curve duty
Existing pump at maximum speed
Existing pump at reduced speed
Existing
pump
UPE(D) FZ
Existing
pump
UPE(D) FZ
Maximum
head
[m]
Setting of
head
[m]
Setting of control
mode
Maximum
head
[m]
Setting of
head
[m]
Setting of control
mode
3
2
Constant pressure
3
1.5
Constant pressure
4
2
Constant pressure
4
1.5
Constant pressure
5
2.5
Proportional pressure
5
2
Constant pressure
6
3
Proportional pressure
6
2
Constant pressure
7
3.5
Proportional pressure
7
2.5
Proportional pressure
8
4
Proportional pressure
8
3
Proportional pressure
9
4.5
Proportional pressure
9
3.5
Proportional pressure
10
5
Proportional pressure
10
3.5
Proportional pressure
11
5.5
Proportional pressure
11
4
Proportional pressure
12
6
Proportional pressure
12
4
Proportional pressure
TM
00
5
547
45
96
Q
H
Max.
Min.
TM
00 554
8 459
6
Q
H
Max.
Min.
Содержание UPE 100-120 F