English (GB)
17
8. Setting the pump
For the setting of the pump, use
•
control panel
•
R100 remote control
•
bus communication (not described in detail in
these instructions. Contact Grundfos).
The table below shows the application of the
individual operating units and in which section the
function has been described.
"-" = not available with this operating unit.
8.1 Factory settings
8.2 Control panel
The control panel (fig. 14) incorporates
•
buttons for setting, and .
•
light fields, yellow, for indication of control mode
and pump head.
•
indicator lights, green and red, for operating and
fault indication. See section
.
Fig. 14
Control panel
8.2.1 Control mode setting
Description of function, see section
When and are pressed simultaneously, the light
fields will indicate the selected control mode:
If the buttons are pressed for more than 5 sec., the
control mode will change over to constant pressure
and proportional pressure respectively. This means
that constant-curve duty is deactivated if selected
with the R100.
Function
Co
nt
ro
l pa
n
e
l
R
100
Proportional-pressure
control
Constant-pressure control
Setting of pump head
Max. curve duty
Min. curve duty
Constant-curve duty
-
Temperature influence
-
Resetting of fault
indications
Activation/deactivation of
pump buttons
-
Allocation of pump number
-
Reading of various data
-
Start/stop
UPE(D)
80-120 FZ
UPE
100-120 FZ
Control mode
Proportional
pressure
Proportional
pressure
Head
6 m at max.
flow.
See fig. 14.
6 m at max.
flow.
See fig. 14.
Control of twin-
head pump
Alternating
operation
-
Warning
At high liquid temperatures, the pump
may be so hot that only the buttons
should be touched to avoid burns.
TM
04
46
93
18
09
Light fields
Control mode
Top + bottom light
fields flashing
Proportional pressure
Middle light fields
flashing
Constant pressure
None of the light
fields are on
Constant curve
Buttons
Indicator lights
Light fields
Содержание UPE 100-120 F
Страница 2: ......