5

English (US)

4.2.1 Installation requirements

1. Thoroughly clean and flush the system 

before installing the pump.

2. Do not install the pump at the lowest point of 

the system where dirt and sediment collect. 
If there are suspended particles in the water, 
we recommend installing a strainer and/or a 
filter. Be sure to clean these regularly.

3. Install a vent at the high point(s) of the 

system to remove air trapped in the system.

4. Ensure that water does not enter the 

terminal box during the installation process.

5. Open system: Install the pump in the supply 

line; the inlet side of the pump should be 
flooded with water. Ensure that the static 
head requirement from section 

9.1.2 Inlet 

pressure

 is fulfilled.

Closed system: Install a safety relief valve to 
protect against temperature and pressure 
build-up.

4.2.2 Positioning the terminal box

Position the terminal box to one side of the 
pump or the other, with the conduit entry 
pointing down. See fig. 

2

.

Fig. 2

Recommended terminal box 
orientation

4.2.3 Changing the terminal box position

If you must change the terminal box position, we 
recommend to do so before installing the pump. 

If you change the terminal box position after the 
pump is installed, switch off the power supply 
and ensure that the power cable is unplugged. 
Close the isolating valves before removing the 
hex socket head screws on the pump.

1. While supporting the stator (motor), use a 4 

mm or 5 mm wrench to remove the four (4) 
hex socket head screws from the pump 
housing and stator.

2. Carefully separate the stator from the pump 

housing and rotate it to the correct terminal 
box orientation and refit it.

3. Replace the hex socket head screws and 

tighten diagonally and evenly (7 ft.-lb. 
torque).

4. Check that the motor shaft turns freely. To do 

so, first remove the large screw in the middle 
of the nameplate, then insert a small flat 
blade screwdriver into the end of the shaft, 
and turn it gently. See fig. 

2

.

If the shaft does not turn easily, repeat the 
disassembly/reassembly process.

4.3 Electrical installation

4.3.1 Electrical requirements

The operating voltage and other electrical data 
are marked on the nameplate. Make sure that 
the motor is suitable for the electrical supply on 
which it will be used.

4.3.2 Electrical connection

Without the optional timer

Insert the 115 V plug of the power cable from the 
pump into a properly grounded 115 V electrical 
outlet.

With the optional timer

If you use the optional timer, plug the timer into 
a 115 V electrical outlet. Plug the power cable of 
the pump into the timer outlet. Be sure to route 
the power cable, so that it does not touch the 
exhaust vent pipe of a gas- or oil-fired water 
heater.

T

M

05

 55

63

 38

12

UPS 15-42 does not require manual 
turning of shaft.

Содержание UP 15 series

Страница 1: ...GRUNDFOS INSTRUCTIONS UP S 15 circulators With power cable and optional digital timer Installation and operating instructions ANSI NSF372...

Страница 2: ...be returned to the distributor or dealer of Grundfos products from which it was purchased together with proof of purchase and installation date failure date and supporting installation data Unless oth...

Страница 3: ...Ensure that the voltage and frequency of the product match the voltage and frequency of the installation site See section 7 1 Nameplate for information on the nameplate Examine the product to make sur...

Страница 4: ...ress on the pump Fig 1 Acceptable pump mounting positions WARNING Electric shock Death or serious personal injury Switch off the power supply before starting any work on the product Make sure that the...

Страница 5: ...is unplugged Close the isolating valves before removing the hex socket head screws on the pump 1 While supporting the stator motor use a 4 mm or 5 mm wrench to remove the four 4 hex socket head screw...

Страница 6: ...easier setting TM07 1682 2018 When setting the timer if you pause for more than 30 seconds the timer will automatically return to normal time of day display 1 Press TIME A flashing 4 digit year appear...

Страница 7: ...n at sunrise or sunset proceed to step 7 7 Press or to scroll to one of the 2 screens with moon and sun icons flashing and AM or PM flashing The AM plus icons screen means this event will happen at su...

Страница 8: ...undfos UP S 15 pump is designed for domestic hot water recirculation Grundfos UP S Series 15 pumps are designed for indoor use only Grundfos UP S 15 series pumps with stainless steel or bronze volutes...

Страница 9: ...of the pump 3 Remove the large screw in the middle of the nameplate 4 Insert a small flat blade screwdriver into the end of the shaft and gently turn it until the shaft moves freely See fig 2 5 Repla...

Страница 10: ...is table In a pressurized system the required inlet pressure is the minimum allowable system pressure In an open system the required inlet pressure is the minimum distance at which the pump must be lo...

Страница 11: ...3500 www grundfos us GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS M xico Boulevard TLC No 15 Parque Industri...

Страница 12: ...1229 www grundfos com The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright...

Отзывы: