background image

14

English (US)

5. Electrical installation

The proper operating voltage and other 
electrical information can be found on the 
nameplate attached to the top of the motor.
Depending on pump model, the motor has either 
built-in, automatic, resetting of thermal 
protection or is impedance protected and in 
either case does not require additional external 
protection. The temperature of the windings will 
never exceed allowable limits, even if the rotor is 
locked.
Wire sizes should be based on the ampacity 
(current-carrying properties of a conductor) as 
required by the latest edition of the National 
Electrical Code or local regulations.
Both the power and grounding wires must be 
suitable for at least 194 °F (90 °C).
If rigid conduit is to be used, the hub must be 
connected to the conduit system before it is 
connected to the terminal box of the pump.

5.1 For all 115 V and 230 V models

5.1.1 Single-speed pump wiring

1. Connect the white/white electrical leads from 

the circulator pump to the incoming power 
leads with wire nuts or other approved 
connectors.

2. Attach incoming grounding wire to either of 

the green grounding screws.

Fig. 3

Wiring diagram for all 115 V and 
230 V single-speed pumps.

5.1.2 Multi-speed pump wiring

1. Insert black conductor into terminal "L" 

position.

2. Insert white conductor into terminal "N" 

position.

3. Insert grounding conductor into terminal 

"

" position.

Fig. 4

Wiring diagram for 115 V and 230 V 
multi-speed pumps*

*

UP(S) 15 capacitor wire position 4 & 8;
UP(S) 26/43/50 capacitor wire position 2 & 4.

WARNING

All electrical work should be 
performed by a qualified electrician in 
accordance with the latest edition of 
the National Electrical Code and local 
codes or regulations.

WARNING

The safe operation of this pump 
requires that it be grounded in 
accordance with the National 
Electrical Code and local codes or 
regulations.

WARNING

The ground conductor should be a 
copper conductor of at least the size 
of the circuit conductor supplying 
power to the pump. Minimum ground 
conductor size is 14 AWG. Connect 
the ground conductor to the 
grounding point in the terminal box 
and then to an acceptable ground.

WARNING

Do not ground to a gas supply line.

WARNING

For fig. 

3

, some pump models may 

come with two access wiring ports 
(cable entries) to the terminal box. To 
ensure safe operation of your 
installation, the enclosed terminal box 
cap (blanking) plug MUST be inserted 
into the unused wiring access port 
(cable entry).

T

M

05

 55

65

 38

12

T

M

05

 55

66

 38

12

Capacitor

Green 
grounding 
screws

Ground

White 
line 
leads

1 2 3 4 5 6 7 8

Cap

a

ci

tor

Green 
ground 
Neutral 
Line

Содержание UP 15-100F

Страница 1: ...GRUNDFOS INSTRUCTIONS UP Series circulators Installation and operating instructions UP15 and UP26 Stainless and Bronze ...

Страница 2: ...instructions To obtain service under this warranty the defective product must be returned to the distributor or dealer of GRUNDFOS products from which it was purchased together with proof of purchase and installation date failure date and supporting installation data Unless otherwise provided the distributor or dealer will contact the GRUNDFOS factory or authorized service station for instructions...

Страница 3: ... by volume solution of ethylene or propylene glycol and water can be used however a decrease in pump performance may result due to an increase in the viscosity of the solution Check with manufacturer for information regarding suitability of pumping other liquids Closed systems Model UP S 15 26 43 and 50 series pumps with cast iron pump housings are designed to pump water compatible with their cast...

Страница 4: ...tank pool etc Table A Maximum water temperature Ambient temperature 104 F 40 C 120 F 48 C 140 F 60 C 160 F 71 C 175 F 79 C Water temperature All UP 230 F 110 C 220 F 104 C 210 F 98 C 190 F 87 C 175 F 79 C Exceptions below UPS 15 35 165 F 73 C 140 F 60 C UP 15 100F 205 F 96 C 195 F 90 C 185 F 85 C 175 F 79 C UP 26 120U 205 F 96 C 195 F 90 C 185 F 85 C 175 F 79 C UP 26 116 150 F 65 C 140 F 60 C Tabl...

Страница 5: ...es be installed on each side of the pump If possible do not install elbows branch tees and similar fittings just before or after the pump Provide support to the pump or adjacent plumbing to reduce thermal and mechanical stress on the pump 4 3 Installation requirements 1 Thoroughly clean and flush the system prior to pump installation 2 Do not install the pump at the lowest point of the system wher...

Страница 6: ... pumps 5 1 2 Multi speed pump wiring 1 Insert black conductor into terminal L position 2 Insert white conductor into terminal N position 3 Insert grounding conductor into terminal position Fig 4 Wiring diagram for 115 V and 230 V multi speed pumps UP S 15 capacitor wire position 4 8 UP S 26 43 50 capacitor wire position 2 4 WARNING All electrical work should be performed by a qualified electrician...

Страница 7: ...e end of the shaft and gently turn until the shaft moves freely Replace and tighten the plug Open the isolating valves and wait 2 to 3 minutes for the system pressure to equalize before starting the pump 9 Disposal This product or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundf...

Страница 8: ... O Box 16768 Jebel Ali Free Zone Dubai Phone 971 4 8815 166 Fax 971 4 8815 136 www grundfos uae GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS México Boulevard TLC No 15 Parque Industrial Stiva Aeropuerto C P 66600 Apodaca N L México Phone 011 52 81 8144 4000 Fax 011 52 81 8144 4010 www grundfos mx ...

Страница 9: ...ECM 1202189 www grundfos com The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S ...

Отзывы: