background image

6

CONTENTS

Page

1.

General description

6

2.

Installation

6

2.1

Motor cooling

6

2.2

Outdoor installation

6

2.3

Electrical connection

7

2.3.1

Mains switch

7

2.3.2

Protection against electric shock - indirect contact 

7

2.3.3

Additional protection 

7

2.3.4

Motor protection

7

2.3.5

Protection against mains voltage transients

7

2.3.6

Supply voltage

7

2.3.7

Start/stop of pump

7

2.4

Other connections

8

2.5

Signal cables 

8

2.6

Bus connection cable

8

2.6.1

New installations

8

2.6.2

Replacing an existing pump

8

3.

Setting the pump 

9

3.1

Factory setting

9

4.

Setting by means of control panel

9

4.1

Setpoint setting

9

4.2

Pump in controlled-operation mode 
(differential pressure control)

9

4.3

Pump in uncontrolled-operation mode

9

4.4

Setting to max. curve duty

10

4.5

Setting to min. curve duty

10

4.6

Start/stop of pump 

10

5.

Setting by means of R100 

11

5.1

Menu OPERATION 

12

5.1.1

Setpoint setting

12

5.1.2

Setting of operating mode

12

5.1.3

Fault indications

12

5.1.4

Alarm log

12

5.2

Menu STATUS 

12

5.2.1

Display of actual setpoint

12

5.2.2

Display of operating mode

12

5.2.3

Display of actual value

12

5.2.4

Display of actual speed

13

5.2.5

Display of input power and power consumption

13

5.2.6

Display of operating hours

13

5.3

Menu INSTALLATION 

13

5.3.1

Selection of control mode

13

5.3.2

Setting of controller

13

5.3.3

Selection of external setpoint signal

14

5.3.4

Selection of fault, operating or ready signal relay

14

5.3.5

Blocking of the buttons on the pump

14

5.3.6

Allocation of pump number

14

5.3.7

Selection of function for digital input

14

5.3.8

Setting of sensor

14

5.3.9

Setting of min. and max. curves

14

6.

External forced-control signals 

15

6.1

Start/stop input 

15

6.2

Digital input 

15

7.

External setpoint signal

15

8.

Bus signal 

15

9.

Priority of settings 

16

10.

Indicator lights and signal relay 

17

11.

Megging 17

12.

Technical data 

18

12.1

Supply voltage 

18

12.2

Leakage current

18

12.3

Inputs/output 18

12.4

Other technical data 

18

13.

Re-lubrication of motor motor bearings 

18

14.

Disposal

18

Before beginning installation procedures, these in-
stallation and operating instructions should be stud-
ied carefully. 

Furthermore, the enclosed installa-

tion and operating instructions for the standard 
pump should be studied carefully. 

The installation 

and operation should also be in accordance with lo-
cal regulations and accepted codes of good practice.

1. General description

Grundfos E-pumps are pumps fitted with frequency-controlled 
standard motors for three-phase mains connection.

The pumps have a built-in PI controller and can be connected to 
an external sensor enabling control of for instance pressure, dif-
ferential pressure, temperature, differential temperature or flow in 
the system in which the pumps are installed. The pumps can be 
set to uncontrolled operation, i.e. the pump performance can be 
set according to the demand. 

The pumps are typically used as circulator pumps in large heating 
or cooling water systems with variable demands.

The desired value (setpoint), e.g. the desired differential pressure 
if a differential pressure sensor has been installed, can be set di-
rectly on the pump control panel, via an input for external setpoint 
signal or by means of the Grundfos wireless remote control R100. 

All other settings are made by means of the R100. 
Important parameters such as actual value of control parameter, 
power consumption, etc. can be read via the R100. 

The pump incorporates 

inputs for external potential-free contacts for start/stop and 
digital function. 
The digital function enables external setting of max. curve or 
min. curve. 

an output for a potential-free fault, operating or ready signal.

an input for bus communication. 
Via the bus communication input, the pump can be controlled 
and monitored by a building management system or another 
external control system.

2. Installation

2.1 Motor cooling

To ensure sufficient cooling of motor and electronics, the follow-
ing must be observed: 

Place the pump in such a way that sufficient cooling is en-
sured. 

The temperature of the cooling air must not exceed 40

°

C. 

Cooling fins and fan blades must be kept clean.

2.2 Outdoor installation

When installed outdoors, the pump must be provided with a suit-
able cover to avoid condensation on the electronic components, 
fig. 1. 

Fig. 1

Examples of covers

For further installation, see installation and operating instructions 
for the standard pump.

TM

02

 22

56

 39

01

Содержание NBE

Страница 1: ...TPE D NBE NKE 11 22 kW GRUNDFOS INSTRUCTIONS Installation and operating instructions...

Страница 2: ...quais esta declara o se refere est o em conformidade com as Directivas Comunit rias com aproxima o das leis dos estados membros da CE para M quinas 98 37 CE Norma usada EN ISO 12100 Compatibilidades...

Страница 3: ...73 23 EEZ 95 Primenjeni standardi EN 60 335 1 i EN 60 335 2 51 Prohl en o shod My firma Grundfos prohla ujeme na svou odpov dnost e v robky TPE D NBE a NKE na n se toto prohl en vztahuje jsou v soula...

Страница 4: ...4...

Страница 5: ...iones de instalaci n y funcionamiento 60 Instru es de instala o e funcionamento 73 86 Installatie en bedieningsinstructies 99 Monterings och driftsinstruktion 112 Asennus ja k ytt ohjeet 125 Montering...

Страница 6: ...structions should be stud ied carefully Furthermore the enclosed installa tion and operating instructions for the standard pump should be studied carefully The installation and operation should also b...

Страница 7: ...ting DC and smooth DC fault currents occur For these pumps an earth leakage circuit breaker type B must be used This circuit breaker must be marked with the following symbols Note When an earth leakag...

Страница 8: ...cross sectional area of min 0 5 mm and max 1 5 mm for external on off switch digital in put setpoint and sensor signals The screens of the cables must be connected to frame at both ends with good fram...

Страница 9: ...ion The setpoint value corresponds to 100 of the maximum pump performance see data sheet for the pump Other pump settings are marked with bold faced type under each individual display in sections 5 1...

Страница 10: ...s continuously to change to the min curve of the pump bottom light field flashes When the bottom light field is on must be pressed for 3 seconds before the light field starts flash ing To return to un...

Страница 11: ...R100 offers additional possibilities of setting and status dis plays for the pump The displays are divided into four parallel menus fig 16 0 GENERAL see operating instructions for the R100 1 OPERATION...

Страница 12: ...signal range Setpoint signal outside signal range Other fault A fault indication can be reset in this display if the cause of the fault has disappeared 5 1 4 Alarm log If faults have been indicated t...

Страница 13: ...time Ti is set within the range from 0 1 to 3600 s If 3600 s is selected the controller will function as a P controller Furthermore it is possible to set the controller to inverse control if the setpo...

Страница 14: ...input of the pump terminal 1 fig 4 can be set to dif ferent functions Select one of the following functions Min min curve Max max curve The selected function is activated by closing the contact betwe...

Страница 15: ...ternal setpoint Hlower 20 0 x 80 0 16 m In uncontrolled operation mode the setpoint can be set exter nally within the range from the min curve to the setpoint set on the pump or by means of the R100 f...

Страница 16: ...p erate according to the max curve the pump control panel and the R100 can only set the pump to stop Example If via the digital input the pump has been forced to op erate according to the max curve th...

Страница 17: ...an installation incorporating E pumps is not al lowed as the built in electronics may be damaged TM00 7600 0304 Green Red Indicator lights Signal relay activated during Description Fault red Opera ti...

Страница 18: ...5 mm Maximum cable length 500 m 12 4 Other technical data EMC electromagnetic compatibility EN 61 800 3 Immunity to electromagnetic disturbance second environment industrial areas Contact Grundfos for...

Страница 19: ...u City Shizuoka pref 431 21 Phone 81 53 428 4760 Telefax 81 53 484 1014 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Tele...

Страница 20: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96480952 1104 139 Repl 96480952 1102...

Отзывы: