28 | Installation, Operating, and Maintenance Manual
Rev. 05JUL2016
Appendix F2: Non-Pressurized Variable Speed Flow Center Submittals
.
Submittal Data
non-pressurized flow center, variable speed pump
Project Name:
Contractor:
Engineer:
Order Number:
Additional Information:
Technical Data
Electrical and Power Data
Approved Antifreeze
Mounting
Pump Performance Curves
Circulator:
Cabinet:
Tank:
Insulation:
Valves:
Grundfos Magna GEO 32-140 (variable speed--requires controller)
Powder coated galvanized steel
Polyvinyl chloride (PVC)
CFC-free polyurethane foam
1”, 3-way, 4-position flushing and isolation/service valve, composite
valve body and spool, NBR seals, stainless steel retaining ring
Max. fluid temp.: 140°F [60°C]
Min. fluid temp.: 14°F [-10°C]
Max. operating press.: 13 psig [89.6 kPa]
Max. ambient air temp.: 104°F [40°C]
Max. ambient relative humidity: 80%
Propylene Glycol
Methanol
Ethanol
Curves are manufacturer’s reported averages using water at 68°F [20°C].
Flow center is
designed for indoor
installation only.
Flow center must
be installed in an
upright position as
shown to the right.
The pump terminal
box should be
located in one of the
following orienta-
tions:
Motor: 208-230V, 50/60 Hz, single phase, 2-pole, ETL
C/US
approved (meets UL and CSA
requirements), electronically protected, insulation class F, 0.09 to 1.7 Amps (at 230V)
GEO-FLO PRODUCTS CORPORATION
905 Williams Park Drive
Bedford, IN 47421 U.S.A.
PH: 812-275-8513; FAX: 812-275-8523
www.geo-flo.com
SD 1275 rev. 02JAN2013
Flow (U.S. GPM) [l/s]
Grundfos Magna GEO 32-140 Performance Curves (Single Pump)
Head (F
ee
t) [kP
a]
[0.32 0.63 0.95 1.26 1.58 1.89 2.21 2.52 2.84 3.15]
Pump operates in
between these curves
to maintain flow rate
or temperature diff.
0
5
10
15
20
25
30
35
40
45
50
[134.3]
[14.9]
[29.8]
[44.8]
[59.7]
[74.6]
[89.5]
[104.5]
[119.4]
[149.2]
0 5 10 15 20 25 30 35 40 45 50
0 10 20 30 40
Flow (U.S. GPM) [l/s]
Grundfos Magna GEO 32-140 Power
0
50
100
150
200
250
Po
w
er (W
atts)
[0.63 1.26 1.89 2.52]
NOTES: The Magna GEO
(variable speed) pump
adjusts speed (when used
with controller) to maintain
flow rate or temperature
difference. For Watts based
upon a specific flow rate and
pressure drop, go to
www.geo-flo.com, and use
the pump sizing calculator.
NP
1
NP
2
NP
V
NP
V2
NP
Series