GEO-FLO UNIVERSAL PUMP CONTROLLER: UPC-GEO |  5

Wiring the Controller (Single Heat Pump -- Magna Geo Pump) 

WARNING: OPEN THE POWER SUPPLY DISCONNECT SWITCH AND SECURE IT IN AN OPEN 
POSITION PRIOR TO PERFORMING ELECTRICAL WORK. VERIFY THAT POWER HAS BEEN 
DISCONNECTED PRIOR TO WIRING THE CONTROLLER. FAILING TO SECURE THE ELECTRI-
CAL SUPPLY COULD RESULT IN SERIOUS INJURY OR DEATH. THIS EQUIPMENT SHOULD BE 
INSTALLED AND SERVICED BY QUALIFIED PERSONNEL ONLY.

NOTE: The Magna GEO 32-140 motor requires no external protection. Wiring the Magna GEO directly to mains 

power is recommended. See Appendix C for more information.

NOTE: Low voltage wiring will vary depending on the installation and sensors used.

1. 

Turn off power at the heating/cooling system or fuse/circuit breaker panel.

2. 

Decide on where wires will enter the controller housing and remove the appropriate knock-outs.

3. 

Figures 2a through 2d provide controller terminal descriptions and wiring for a single unit; Figure 3 shows 

wiring for two heat pumps. Complete wiring using appropriately sized wire and replace controller’s cover.

NOTES:

A. 

HP IN1: Left terminal receives 24VAC input from heat pump accessory output (labeled “ACC” or “A” by 

some heat pump manufacturers). IMPORTANT: Some heat pump accessory relay contacts are not isolated 
from the 24 VAC heat pump transformer, and may create a “dirty” power signal, especially heat pumps 
with thermostat-controlled ECM fan motors (symptom includes variable speed pump not shutting off). An 
additional relay will be required for these heat pumps (see Figure 2b). If an accessory terminal is not avail-
able, Figures 2c and 2d illustrate connections. Alternatively, ∆T mode may be used, which will only require 
one relay (coil connected to Accessory and C; contacts connected to HP and IN1).

 

 

 

 

   

 

 

 

24

 VAC

 Input

 to

 P

owe

r
 

Cont

roll

er

 (N

ote

 3

24VAC

 Input

 Signal

  

(N

ote

 2)

 

24VAC

 Input

 Signal

 

 (N

ote

 1)

  

Ma

gna

 GEO

 P

um

Input

/Output

Grundfos

 D

irec

Se

nsor

 Inpu

ts

 

1-

10

 VD

Input

 

(not

us

ed

)

Ea

rt

Ground

 

Thermistor

 

Inputs

 

Y2

Brown

 

Bl

ac

Bl

ue

 

Entering

 W

at

er

 Therm

 (f

rom

 loop

Leaving

  W

at

er

 T

he

rm

 (to

 loop

Thermistors

 Common

 

4-

pi

conn

ector

 from

 

Grundfos

 Flo

w

 S

en

so

on

 e

ith

er

 Entering

 O

Leaving

 W

at

er

  s

id

 

R C

 

  

  

 

LWT

EWT

OUT IN REF

PWM

HP IN1 HP IN2

LWT

EWT

C

THERMS

+

-

1-10 DCIN

24VAC INGND

AUXILIARY

L1

L2

N1 N2

OUT

OUT IN

IN

BRN BLK BLU

ACC

(Note A)

C

208-230 VAC Input/Output

Power to UPS26-99 (2nd pump)

for two pump flow centers. Do

not connect Magna GEO single

pump flow center to this

terminal block.

Line V

oltage W

iring 

(115V or 230V

)

UPS26-99 (2nd pump)

Do not connect to 

Magna GEO pump.

115V

or 230V

pump

(Note B)

(Note C)

Figure 2a: Wiring Diagram: 

Single heat pump (isolated 

accessory relay for Y2)

IMPORTANT:

Controller must

be grounded.

Содержание Geo-Flo Universal Pump Controller

Страница 1: ...cts Corporation 905 Williams Park Drive Bedford Indiana 47421 U S A Main Number 812 275 8513 Toll Free 800 784 8069 Fax 888 477 8829 Document 3704 Rev 05JUL2016 Installation Operating and Maintenance...

Страница 2: ...iring Single Unit Magna GEO Pump 5 Wiring One Flow Center Two Heat Pumps 8 Wiring 0 10 VDC output 10 Setup 11 Quick Start Procedure 11 General Navigation 11 Main Page 11 System Status 12 Setup Menu 12...

Страница 3: ...ion rejection in KBTU H Two lockout modes allow the installer to choose whether to lock the system parameters so they cannot be inadvertently changed or to lock the screen so the feedback temperatures...

Страница 4: ...GEO attempts to satisfy the T requirement by first using the more efficient Magna GEO 32 140 pump If the Magna GEO reaches its maximum performance level before satisfying the T set point requirement...

Страница 5: ...Approvals Certified to CSA C22 2 No 24 Conforms to UL Standard 873 Dimensional Data A B C D E F G H I J Weight Inches 5 1 8 6 11 16 1 7 8 3 3 8 5 5 8 3 3 8 1 11 16 1 4 3 16 1 2 standard conduit knock...

Страница 6: ...ll bit Hammer Small Philips or flathead screwdriver Wire cutters strippers Electrical Tape Legend of Abbreviations EWT Entering Water Temperature from loop to heat pump LWT Leaving Water Temperature t...

Страница 7: ...accessory relay contacts are not isolated from the 24 VAC heat pump transformer and may create a dirty power signal especially heat pumps with thermostat controlled ECM fan motors symptom includes var...

Страница 8: ...ave an accessory terminal sometimes labeled A or ACC One of the purposes for the accessory terminal is for control of a solenoid valve for open loop systems However it also affects the operation of th...

Страница 9: ...T THE MAGNA GEO VARIABLE SPEED PUMP HIGH VOLTAGE TERMINALS TO THE T SIDE OF THE HEAT PUMP COMPRESSOR CONTACTOR THE HIGH IN RUSH CURRENT MAY CAUSE PREMATURE CONTACTOR FAILURE ALWAYS CONNECT THE PUMP DI...

Страница 10: ...minimum and nominal full load flow rate of the larger unit Set stage two flow between minimum and nominal flow for both units on full load For example 4 ton and 3 ton heat pump Minimum full load flow...

Страница 11: ...same connections as unit 2 1 2 of Flo Link x 1 1 4 PE fusion set 1 1 4 or 2 HDPE NOTE If 2 a 1 1 4 to 2 coupling is required 1 2 of Flo Link x 1 hose barb set with fitting for PT Port 1 1 4 fusion x 1...

Страница 12: ...NGND AUXILIARY L1 L2 N1 N2 OUT OUT IN IN BRN BLK BLU C Note B Note C Signal IN Note A Magna3 not used NOTES A 0 10 VDC Output labeled PWM Connect 0 10 VDC output from the OUT BRN and REF BLU terminals...

Страница 13: ...two Main pages or increases or decreases a particular param eter Pressing and holding the OK button for one second while on either Main page changes the display to the Setup Menu screen unless the co...

Страница 14: ...TAGE 2 will be applied when the controller receives a 24 VAC signal at the left HP IN2 terminal or when a dry contact is made across the two HP IN2 terminals Press the OK button to select Item 1 STAGE...

Страница 15: ...3 Press the OK button to select the MIN menu the triangle cursor will turn solid and use the buttons to set the value Once set press the OK button again to lock in the value Sensor Configuration NOTE...

Страница 16: ...ay of flow rate entering and leaving fluid temperatures and HE HR depending on which sensors are installed Meter mode does not provide an output to control the pump s and only displays the Main 2 page...

Страница 17: ...he 0 10 VDC setting is used for Grundfos Magna3 or other pumps that require a 0 10 VDC input signal The mode is selected by moving the cursor to Item 6 SIGNAL in the Setup Menu and pressing the OK but...

Страница 18: ...circuit board Display NO PUMP Controller does not detect a Magna GEO var spd pump attached Could also indicate no power to pump 1 PWM Cable not attached to pump or controller Check PWM cable at pump a...

Страница 19: ...report No Pump in Status area Check PWM cable connection at pump and at controller Or may require isolation relay Control displays 2 PUMPS RUN NING but UPS26 99 will not run No 230V input power at L2...

Страница 20: ...rty or defective Check direction of ow arrow on sensor tube body and re plumb if necessary Re plumb to remove disturbance Flush loop Remove sensor and clear debris Replace sensor if necessary Controll...

Страница 21: ...sensor cable and seals 2 Brass adapters 1 Hose Barb X 10 200 Flow Tube 2 G1 1 4 Union nuts for Flow Tube Adapters 4 Hose clamps stainless steel 2 10k Thermistors 1 4 MPT brass connection 2 SPDT Isolat...

Страница 22: ...ire fitting pipe thermistor to prevent conductive heat transfer from affecting the thermistor reading Adding additional wire to the thermistor leads is accept able since the resistance of the thermist...

Страница 23: ...926 35 0 1 7 30 024 77 0 25 0 10 000 119 0 48 4 3 836 36 0 2 2 29 203 78 0 25 6 9 762 120 0 48 9 3 756 37 0 2 8 28 406 79 0 26 1 9 531 38 0 3 4 27 565 80 0 26 7 9 305 10k resistor is 10k 39 0 3 9 26 8...

Страница 24: ...ly limited by the sum of resistance in the NTC resistor and the resistance in the coil in the mains filter If the power is turned on when the supply voltage is at its highest point the in rush current...

Страница 25: ...HOLE LOCATIONS SUGGESTED MOUNTING HOLE LOCATIONS This document must be printed full scale to properly mark the mounting hole locations The Page Scaling in the Print dialog box in Adobe Acrobat must b...

Страница 26: ...should be located in one of the following orientations Grundfos Magna GEO 32 140 variable speed High Impact Polystyrene plastic CFC free polyurethane foam 1 Full port 3 Way 4 Position flushing and iso...

Страница 27: ...H G F E D C B Inches CM LBS KG 3 8 DRIVE SOCKET 2 12 1 2 4 3 4 9 7 16 8 1 2 10 3 16 33 6 5 0 31 7 12 0 24 0 21 6 25 9 12 7 E A D F B H G C I 12 26 Fluid connections are Flo Link double O ring style Tr...

Страница 28: ...pact Polystyrene plastic CFC free polyurethane foam 1 Full port 3 Way 4 Position flushing and isolation service valve Brass body and spool NBR seals stainless steel retaining ring UPS26 99 motor 208 2...

Страница 29: ...t pump connections Flow center may be field modified to a one pump flow center by replacing the constant speed pump with a blank plate kit SD 1299 rev 24SEP2013 Flow U S GPM l s Grundfos UPS26 99 Powe...

Страница 30: ...w center must be installed in an upright position as shown to the right The pump terminal box should be located in one of the following orienta tions Motor 208 230V 50 60 Hz single phase 2 pole ETLC U...

Страница 31: ...X 812 275 8523 www geo flo com SD 1275 rev 02JAN2013 Dimensional Data Requires two Flo Link double O ring transition fittings Typically PE fusion or PVC glue fittings are used for the ground loop a ho...

Страница 32: ...e pump terminal box should be located in one of the following orienta tions UPS26 99 motor 230V 60 Hz single phase 2 pole UL and CSA approved internal thermal over load protection insulation class F t...

Страница 33: ...ump with a blank plate Flow U S GPM l s Grundfos UPS26 99 Power Curves Power Watts 0 13 0 25 0 38 0 50 0 63 0 76 0 88 1 00 1 14 1 26 1 39 1 51 1 64 1 77 1 89 2 02 2 15 2 27 0 10 20 30 40 Flow U S GPM...

Страница 34: ...r where T temperature difference between EWT and LWT Fluid factor adjustment for antifreeze It is possible that the calculation shown on the controller screen is different than a hand calculation The...

Страница 35: ...ded wiring piping diagrams for one flow center two heat pumps 8 Added wiring diagrams for 0 10 VDC output 10 Updated figures setup menu descriptions and operation for new 3 0 software 11 15 Added form...

Страница 36: ...ntinually working to improve its products As a result the design and specifications of products in this catalog may change without notice and may not be as described herein For the most up to date inf...

Отзывы: