background image

English (GB)

21

10. Electrical connection

10.1 Controller on base frame

The electrical connection must be carried out according to the 
wiring diagram in the control cabinet.

Connection of power supply

• The connection to the power supply must be fitted with a fuse 

of the correct size in accordance with local regulations and 
connected to terminals L1-L2 and L3 on the isolating switch. 
The electronic board is phase-sensitive, and the power 
conductors must therefore be connected in the correct order of 
phases. The wiring must typically be sized for minimum 125 % 
of the full-load current of the pump.

Connection of external sensor signals

• If a pressure switch is installed in the suction pipe, connect it 

to terminal bar TB12 (fig. 5 or 6, pos. 9). Use one of terminals 
AL No 1 to 4.

• If a pressure switch is installed in the discharge pipe, connect 

it to terminal bar TB12 (fig. 5 or 6, pos. 9). Use one of 
terminals AL No 1 to 4.

• If a pump room thermostat is installed, connect it to terminal bar 

TB12 (fig. 5 or 6, pos. 9). Use one of terminals AL No 1 to 4.

• If the water reservoir level is to be monitored, connect the float 

switches for low and for high level to terminal bar TB12 (fig. 5 
or 6, pos. 9). Use one of terminals AL No 1 to 4.

• If a vibration sensor is installed in the fire pump set, connect it 

to terminal bar TB12 (fig. 5 or 6, pos. 9). Use one of terminals 
AL No 1 to 4.

• If the motor temperature is to be monitored, connect the 

temperature sensor to terminals 89-90.

• If the status of the flowmeter (option A4) is to be indicated, 

connect the signal cable of the flowmeter to terminal bar TB12 
(fig. 5 or 6, pos. 9). Use one of terminals AL No 1 to 4.

Connection of external control signals

• If the pump is to be started by a remote signal, connect the 

signal cable to terminal "Remote St NC" (fig. 5 or 6, pos. 9).

• If the pump is to be started by a signal from a deluge valve, 

connect the valve contact to terminal "Deluge NC" (fig. 5 or 6, 
pos. 9). Remove jumper J1 to enable the function.

• If the pump is to be started by a signal from a flow switch (NO), 

connect the signal cable to terminal "Flow switch" (fig. 5 or 6, 
pos. 9).

• If the fire pump set is to be locked by external equipment 

(option A6), terminals 3-110 can be used to connect a NO 
contact when the interlocked equipment is in the same pump 
room and wiring is mechanically protected. Otherwise, 
terminal 104-106 must be used when connecting a remote 
control voltage from the other equipment. Make sure that the 
control voltage from other equipment and that from control 
relay CR10 are compatible. For electrical connection, see also 
the label in the control cabinet.

• If the fire pump sets are divided into zones (options A9 to 

A11), see the label in the control cabinet.

Connection of external equipment

• If the controller is to lock other equipment (option A7), see the 

label in the control cabinet.

• If a motor heater is to be connected, see the label in the 

control cabinet. 

All other external sensors must be connected to the terminals 
shown on the wiring diagram in the control cabinet.

10.2 Wall- and floor-mounted controller

In the case of wall- or floor-mounted controllers, the connections 
to the motor must also be made besides the connections 
described in section 

10.1 Controller on base frame

.

Type GPA

The motor must be connected to terminals T1, T2 and T3 on the 
main contactor (1M). The wiring must typically be sized for 
minimum 125 % of the full-load current of the pump.

Type GPY

The motor must connected to terminals T1-T2-T3 on contactor 
1M and T4-T5-T6 on contactor 2M. The wiring must typically be 
sized for minimum 125 % of the full-load current of the pump.

10.3 Connection to standard alarm relays

If operating and alarm messages are to be transferred for 
instance to a building management system, conductors can be 
connected to the standard alarm relays (fig. 5 an6, pos. 9). 
The alarm relays has one NO and one NC contact.
The table below gives an overview of standard alarm relays.

Warning

Check that the supply voltage specified on the 
nameplate of the control cabinet corresponds to 
the local conditions.

The electrical connection should be carried out 
by qualified personnel in accordance with local 
regulations.

Caution

The dimensional drawings show the area suitable 
for power and motor connections. No other 
location must be used. Only watertight hub 
fittings must be used when entering the cabinet 
to preserve the NEMA rating of the cabinet.

Relay

Function

RUN

Indicates that the pump is running.

Pow. Av.

Indicates that power supply is okay. 
If deactivated, there is a phase or power failure.

Ph. Rev.

Indicates phase reversal.

Room Al.

Indicates one of the following conditions:
- Overvoltage
- Undervoltage
- Phase unbalance.

Motor Tr.

Indicates one of the following conditions:
- Overcurrent
- Undercurrent
- Fail to start
- Earth fault.

EPSR ready

Indicates that the pressure board (EPSR) is 
ready and functioning.

Содержание Fire DNF

Страница 1: ...Fire DNF Fire HSEF electric Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...EC Member States Machinery Directive 2006 42 EC Standards used EN 12100 1 2003 EN 12100 2 2003 EN 809 1998 Low Voltage Directive 2006 95 EC Standards used EN 60204 1 2006 EN 60439 1 1999 EMC Directiv...

Страница 3: ...4 Levelling 17 9 5 Pipework 18 9 6 Bypass 18 9 7 Connection to the pressure sensor 18 9 8 Priming tank and test pipe 18 9 9 Alignment 19 9 10 Separate control cabinet 20 10 Electrical connection 21 1...

Страница 4: ...o reduce the risk of fire or electric shock the manufacturer s instructions for selection of overload and short circuit protection must be followed Lifting points for the entire fire pump set Hazadous...

Страница 5: ...impeller diameter may therefore deviate from the standard diameters stated in catalogues data sheets etc The actual impeller diameter is stated on the pump nameplate 4 2 1 Split case pump The Grundfo...

Страница 6: ...and allows for setting of pressure values See section 5 2 Settings via display Fig 4 Control panel She controller has two DIP switches for settings See section 5 1 Settings via DIP switches The intern...

Страница 7: ...ia display Cut in B3 fig 4 This button is used to set the pressure limit for starting the pump It is enabled with a DIP switch See section 5 1 Settings via DIP switches It is also used when setting th...

Страница 8: ...an be displayed in PSI P or bar B The display also gives access to the setting menus of the controller See section 5 2 Settings via display 4 4 6 Indicator lights on control panel Four indicator light...

Страница 9: ...Pressing these buttons simulates a pressure drop in the system Start delay In systems with several pumps it may be necessary to set a start delay to prevent all motors from starting at the same time...

Страница 10: ...scribed below Setting of upper DIP switch Phase reversal reference switch No 6 If indicator light Phase Reversal is on change the DIP switch setting ABC CBA to another setting using a pencil Setting o...

Страница 11: ...the previous log To exit the menu do not press any button for more than 30 seconds or press Cut in button B3 for more than 10 seconds Menu 12 event log In this menu the user can view the event log The...

Страница 12: ...er placed on the common base frame Example DNF Fire DN F 80 25 260 E A X A A B B Example HSEF Fire HSE F 8 15 323 E B X D A B C Fire Fire system Pump type DN End suction pump HSE Horizontal split case...

Страница 13: ...60 60 Hz Example S N E A S Packing type stuffing box N Uncooled stuffing box E With internal barrier fluid F With external barrier fluid A PTFE impregnated fibre packing rings and EPDM O ring in pump...

Страница 14: ...AGES MAXIMUM BRAKE HORSEPOWER REQUIRED AT RATED SPEED AT ANY CAPACITY CONDITION 1 3 5 7 9 11 4 6 8 10 12 13 2 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2...

Страница 15: ...eplate for the fire pump set See fig 11 8 7 Maximum operating pressure 10 16 or 25 bar The maximum operating pressure is stated on the pump nameplate 8 8 Ambient temperature Minimum ambient temperatur...

Страница 16: ...d are one part cement to three parts sand and four parts medium aggregate The concrete foundation must have an absolutely level and even surface Provide the foundation with anchor bolts to fasten to f...

Страница 17: ...e borne noise in the pipework only rubber bellows expansion joints Fit the expansion joints both on the suction and the discharge sides The distance from the pump should be at least 1 to 1 1 2 x DN di...

Страница 18: ...ssure sensor 1 4 NPTF is on the right side of the controller fig 3 pos 6 Run a hose from the discharge pipe to the pressure sensor Water pipes must be flushed clean before connecting the pressure sens...

Страница 19: ...long coupling life This is particularly important with increased motor speed Follow the installation instructions of the coupling manufacturer TM03 2999 5005 Outside diameter of coupling mm Clearance...

Страница 20: ...recommended to avoid water accumulation at the controller s feet 7 TM01 8886 0800 Place the foil where needed 8 TM01 8887 0800 Retighten the screws 9 TM01 8888 0800 Check the alignment carefully once...

Страница 21: ...erminal 104 106 must be used when connecting a remote control voltage from the other equipment Make sure that the control voltage from other equipment and that from control relay CR10 are compatible F...

Страница 22: ...uttons START and STOP 10 Simulate a power failure by turning the circuit breaker to OFF and check if the circuit connected to terminals PowAv is reacting properly 11 Simulate phase reversal by pressin...

Страница 23: ...ndle back to OFF and press STOP button A3 fig 3 pos 3 12 3 Test run To start a test run open the isolating valve to the test pipe and press buttons Cut in B3 and Cut out B2 fig 4 The pump runs for ten...

Страница 24: ...hermal paper and be correctly oriented The following operations must be followed to replace the paper 1 Unscrew the axle and remove the empty roll 2 On the printer open the top cover to get access to...

Страница 25: ...e desired results To set the leakage rate of the stuffing box remove the protecting guards of the shaft on both sides This gives access to the setting screw See service instructions Bearing lubricatio...

Страница 26: ...pipe has been installed according to section 9 5 Pipework c Impeller out of balance Clean the impeller d Inner pump parts worn Replace defective parts e Pump stressed by the pipework Install the pump...

Страница 27: ...ce technician can prepare and provide the appropriate spare parts Please obtain the technical data for the system from the nameplate 17 Warranty The warranty is governed by the framework of our genera...

Страница 28: ...75 2220 x 701 x 1320 1050 525 MMG 280M E 90 2271 x 701 x 1320 1096 590 HSEF 5 8 MMG 200LA E 30 2010 x 701 x 1320 669 6 5 283 283 143 248 MMG 200LB E 37 2010 x 701 x 1320 692 270 HSEF 5 11 MMG 225M E 4...

Страница 29: ...5 525 MMG 280M E 90 1728 x 701 x 842 891 590 HSEF 5 12 MMG 280M E 90 1733 x 701 x 891 999 6 5 302 390 257 590 MMG 315S E 110 1943 x 853 x 976 1479 1050 MMG 315M E 132 2023 x 853 x 976 1591 1150 HSEF 6...

Страница 30: ...0M E 55 2280 x 701 x 1320 1195 447 MMG 280S E 75 2355 x 701 x 1472 1344 554 HSEF 8 17 MMG 280S E 75 2399 x 701 x 1472 1400 10 8 353 302 458 554 MMG 280M E 90 2449 x 701 x 1472 1447 600 MMG 315S E 110...

Страница 31: ...E 55 1775 x 701 x 915 1037 447 MMG 280S E 75 1805 x 701 x 942 1138 554 HSEF 8 17 MMG 280S E 75 1844 x 701 x 994 1194 10 8 353 302 458 554 MMG 280M E 90 1894 x 701 x 994 1241 600 MMG 315S E 110 2028 x...

Страница 32: ...80M E 90 2980 154 89 7 2 HSEF 5 12 MMG 280M E 90 3 x 380 415 660 690 Y 2980 154 89 7 2 MMG 315S E 110 2980 188 108 7 2 MMG 315M E 132 2980 222 128 7 5 HSEF 6 10 MMG 280S E 75 3 x 380 415 660 690 Y 297...

Страница 33: ...74 7 4 HSEF 8 15 MMG 225M E 45 3 x 380 415 660 690 Y 1480 78 45 7 5 MMG 250M E 55 1480 95 55 7 5 MMG 280S E 75 1480 128 74 7 4 HSEF 8 17 MMG 280S E 75 3 x 380 415 660 690 Y 1480 128 74 7 4 MMG 280M E...

Страница 34: ...34...

Страница 35: ...22 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 L...

Страница 36: ...1739 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: