background image

English (GB)

8

Additionally, indicator I8 shows that the pump is running.

M: Manual reset with [Alarm Reset] button B1.
A: Automatic reset.

Status mode

The display can be switched to status mode by pressing [Alarm 
Reset] button B1 (fig. 4) for 5 seconds.
The first three lines shows the status of inputs and outputs. 
The fourth line shows the maximum voltage (OV) applied to the 
controller and the earth fault limit (GND). The earth fault detection 
is optional (option B13). The display switches back to normal 
mode after 10 minutes, or when the [Alarm Reset] button is 
pressed.

Fig. 8

Display 1 in status mode

The table below gives an overview of inputs and outputs.

Simulation mode

The display mode can be switched to phase-reversal simulation 
by pressing [Alarm Reset] button B1 (fig. 4) for more than 
10 seconds. See fig. 8. 
During this simulation, indicator light "Phase Reversal" (fig. 4, 
pos. 2) is on, and alarm relay "Ph. Rev." is activated.

Fig. 9

Display 1 in simulation mode

4.4.5 Display D2 (pressure status)

The display shows the pressure status of the system.

Fig. 10

Display 2

The display is divided into two lines. The first line shows day and 
time, or status messages. The day and time are always shown. 
If a message must be shown, the display will be scrolling 
successively at intervals of ± 1 second.
The last digit indicates whether the weekly test is enabled (E) or 
disabled (D). If a timer count-down (on timer and off timer) is 
activated, the remaining time will be shown to the right instead of 
E or D.

If manual stop is required (automatic stop function is not 
enabled), the word "MANU" will be shown to the right.

The second line shows the pressure status. The first group of 
digits shows the cut-out pressure, the second group shows the 
cut-in pressure, and the third group shows the actual system 
pressure. The pressure can be displayed in PSI (P) or bar (B).
The display also gives access to the setting menus of the 
controller. See section 

5.2 Settings via display

.

4.4.6 Indicator lights on control panel

Four indicator lights show the status of the controller and pump. 
The indicator lights and their indication are described in the table 
below.

Pos.

Indication

Description

Reset

I1

Overcurrent

I > 130 % of I

N

 for 

more than 20 
seconds.

M

I2

Undercurrent

I < 30 % of I

N

 for more 

than 20 seconds.

M

I3

Overvoltage

U > 110 % of U

N

 for 

more than 1 second.

M

I4

Undervoltage

U < 85 % of U

N

 for 

more than 1 second.

M

I5

Phase Unbalance

Over 3 % for more 
than 1 second.

M

I6

Phase Loss

Power missing for 
more than 1 second.

A

I7

Fail to Start

I < 5 % for more than 
20 seconds.

M

I8

Motor Run

Mains contactor is 
closed.

A

TM

04 51

45 270

9

Pos.

Input

Output

1

Alarm 1

Power Available

2

Alarm 2

Phase Reversal

3

Alarm 3

Pump Room Relay

4

Alarm 4

Motor Alarm Relay

5

Motor run

Lock Rotor (shunt trip)

6

Alarm 5

Alarm A

7

DIP ABC-CBA

Alarm B

8

Reset PB

Alarm C

TM

04

 51

46

 27

09

Input:    00001000
Output: 10000000

12345678

Phase Reversal

Simulation

T

M

04

 51

47

 27

09

TM

04

 51

48

 27

09

T

M

04

 51

49

 27

09

Pos.

Indicator 
light

Indication

1

Power 
Available

This indicator light indicates that the 
power is acceptable on all three 
phases, and the phase sequence is 
correct. The power is acceptable if the 
voltage is more than 85 % of rated 
voltage.

2

Phase 
Reversal

This indicator light indicates phase 
reversal of the power source.

3

Pump 
Demand

This indicator light indicates an 
automatic start condition. It is activated 
when the system pressure falls below 
the cut-in pressure. It is deactivated 
when the run time has expired (if the 
function is enabled), or when [STOP] 
button A3 (fig. 3, pos. 3) is pressed.

4

Weekly Test

This indicator light indicates that the 
system is in operation due to a weekly 
test. The weekly test is programmable.
The weekly light is also on during 
manual test.

We 23:23:32

E

245    252    262

P

We 23:23:32

22

246    252    262

P

We 23:23:32 MANU

245    252    262

P

Содержание Fire DNF

Страница 1: ...Fire DNF Fire HSEF electric Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...EC Member States Machinery Directive 2006 42 EC Standards used EN 12100 1 2003 EN 12100 2 2003 EN 809 1998 Low Voltage Directive 2006 95 EC Standards used EN 60204 1 2006 EN 60439 1 1999 EMC Directiv...

Страница 3: ...4 Levelling 17 9 5 Pipework 18 9 6 Bypass 18 9 7 Connection to the pressure sensor 18 9 8 Priming tank and test pipe 18 9 9 Alignment 19 9 10 Separate control cabinet 20 10 Electrical connection 21 1...

Страница 4: ...o reduce the risk of fire or electric shock the manufacturer s instructions for selection of overload and short circuit protection must be followed Lifting points for the entire fire pump set Hazadous...

Страница 5: ...impeller diameter may therefore deviate from the standard diameters stated in catalogues data sheets etc The actual impeller diameter is stated on the pump nameplate 4 2 1 Split case pump The Grundfo...

Страница 6: ...and allows for setting of pressure values See section 5 2 Settings via display Fig 4 Control panel She controller has two DIP switches for settings See section 5 1 Settings via DIP switches The intern...

Страница 7: ...ia display Cut in B3 fig 4 This button is used to set the pressure limit for starting the pump It is enabled with a DIP switch See section 5 1 Settings via DIP switches It is also used when setting th...

Страница 8: ...an be displayed in PSI P or bar B The display also gives access to the setting menus of the controller See section 5 2 Settings via display 4 4 6 Indicator lights on control panel Four indicator light...

Страница 9: ...Pressing these buttons simulates a pressure drop in the system Start delay In systems with several pumps it may be necessary to set a start delay to prevent all motors from starting at the same time...

Страница 10: ...scribed below Setting of upper DIP switch Phase reversal reference switch No 6 If indicator light Phase Reversal is on change the DIP switch setting ABC CBA to another setting using a pencil Setting o...

Страница 11: ...the previous log To exit the menu do not press any button for more than 30 seconds or press Cut in button B3 for more than 10 seconds Menu 12 event log In this menu the user can view the event log The...

Страница 12: ...er placed on the common base frame Example DNF Fire DN F 80 25 260 E A X A A B B Example HSEF Fire HSE F 8 15 323 E B X D A B C Fire Fire system Pump type DN End suction pump HSE Horizontal split case...

Страница 13: ...60 60 Hz Example S N E A S Packing type stuffing box N Uncooled stuffing box E With internal barrier fluid F With external barrier fluid A PTFE impregnated fibre packing rings and EPDM O ring in pump...

Страница 14: ...AGES MAXIMUM BRAKE HORSEPOWER REQUIRED AT RATED SPEED AT ANY CAPACITY CONDITION 1 3 5 7 9 11 4 6 8 10 12 13 2 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2...

Страница 15: ...eplate for the fire pump set See fig 11 8 7 Maximum operating pressure 10 16 or 25 bar The maximum operating pressure is stated on the pump nameplate 8 8 Ambient temperature Minimum ambient temperatur...

Страница 16: ...d are one part cement to three parts sand and four parts medium aggregate The concrete foundation must have an absolutely level and even surface Provide the foundation with anchor bolts to fasten to f...

Страница 17: ...e borne noise in the pipework only rubber bellows expansion joints Fit the expansion joints both on the suction and the discharge sides The distance from the pump should be at least 1 to 1 1 2 x DN di...

Страница 18: ...ssure sensor 1 4 NPTF is on the right side of the controller fig 3 pos 6 Run a hose from the discharge pipe to the pressure sensor Water pipes must be flushed clean before connecting the pressure sens...

Страница 19: ...long coupling life This is particularly important with increased motor speed Follow the installation instructions of the coupling manufacturer TM03 2999 5005 Outside diameter of coupling mm Clearance...

Страница 20: ...recommended to avoid water accumulation at the controller s feet 7 TM01 8886 0800 Place the foil where needed 8 TM01 8887 0800 Retighten the screws 9 TM01 8888 0800 Check the alignment carefully once...

Страница 21: ...erminal 104 106 must be used when connecting a remote control voltage from the other equipment Make sure that the control voltage from other equipment and that from control relay CR10 are compatible F...

Страница 22: ...uttons START and STOP 10 Simulate a power failure by turning the circuit breaker to OFF and check if the circuit connected to terminals PowAv is reacting properly 11 Simulate phase reversal by pressin...

Страница 23: ...ndle back to OFF and press STOP button A3 fig 3 pos 3 12 3 Test run To start a test run open the isolating valve to the test pipe and press buttons Cut in B3 and Cut out B2 fig 4 The pump runs for ten...

Страница 24: ...hermal paper and be correctly oriented The following operations must be followed to replace the paper 1 Unscrew the axle and remove the empty roll 2 On the printer open the top cover to get access to...

Страница 25: ...e desired results To set the leakage rate of the stuffing box remove the protecting guards of the shaft on both sides This gives access to the setting screw See service instructions Bearing lubricatio...

Страница 26: ...pipe has been installed according to section 9 5 Pipework c Impeller out of balance Clean the impeller d Inner pump parts worn Replace defective parts e Pump stressed by the pipework Install the pump...

Страница 27: ...ce technician can prepare and provide the appropriate spare parts Please obtain the technical data for the system from the nameplate 17 Warranty The warranty is governed by the framework of our genera...

Страница 28: ...75 2220 x 701 x 1320 1050 525 MMG 280M E 90 2271 x 701 x 1320 1096 590 HSEF 5 8 MMG 200LA E 30 2010 x 701 x 1320 669 6 5 283 283 143 248 MMG 200LB E 37 2010 x 701 x 1320 692 270 HSEF 5 11 MMG 225M E 4...

Страница 29: ...5 525 MMG 280M E 90 1728 x 701 x 842 891 590 HSEF 5 12 MMG 280M E 90 1733 x 701 x 891 999 6 5 302 390 257 590 MMG 315S E 110 1943 x 853 x 976 1479 1050 MMG 315M E 132 2023 x 853 x 976 1591 1150 HSEF 6...

Страница 30: ...0M E 55 2280 x 701 x 1320 1195 447 MMG 280S E 75 2355 x 701 x 1472 1344 554 HSEF 8 17 MMG 280S E 75 2399 x 701 x 1472 1400 10 8 353 302 458 554 MMG 280M E 90 2449 x 701 x 1472 1447 600 MMG 315S E 110...

Страница 31: ...E 55 1775 x 701 x 915 1037 447 MMG 280S E 75 1805 x 701 x 942 1138 554 HSEF 8 17 MMG 280S E 75 1844 x 701 x 994 1194 10 8 353 302 458 554 MMG 280M E 90 1894 x 701 x 994 1241 600 MMG 315S E 110 2028 x...

Страница 32: ...80M E 90 2980 154 89 7 2 HSEF 5 12 MMG 280M E 90 3 x 380 415 660 690 Y 2980 154 89 7 2 MMG 315S E 110 2980 188 108 7 2 MMG 315M E 132 2980 222 128 7 5 HSEF 6 10 MMG 280S E 75 3 x 380 415 660 690 Y 297...

Страница 33: ...74 7 4 HSEF 8 15 MMG 225M E 45 3 x 380 415 660 690 Y 1480 78 45 7 5 MMG 250M E 55 1480 95 55 7 5 MMG 280S E 75 1480 128 74 7 4 HSEF 8 17 MMG 280S E 75 3 x 380 415 660 690 Y 1480 128 74 7 4 MMG 280M E...

Страница 34: ...34...

Страница 35: ...22 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 L...

Страница 36: ...1739 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: