32
15.720023-V3.0
DMX model 227
8.4
Exchanging the Diaphragm
!
WARNING
Wear protective gloves and glasses when carrying out
work on the dosing head, connections or lines!
●
Loosen the 6 screws (2) on the dosing head (3).
●
Remove the dosing head (3).
●
Unscrew the diaphragm (1) to the left.
●
Refit the retaining ring (4), shim ring (5), lip seal (7) and supporting ring (6),
replacing if necessary.
●
Screw in the new diaphragm (1).
●
Remove the ventilation hood of the motor, and rotate the fan blades until
the diaphragm reaches the rear dead point.
●
Attach the dosing head (3), and tighten the screws (2) diagonally.
Max. torque 70-80 Nm.
●
Vent the pump, and restart.
CAUTION
After initial start-up and after each diaphragm
exchange, tighten the fixing screws of the dosing head:
After approx. 6 to 10 working hours or two days, tighten
the dosing head screws crosswise using a torque
wrench, torque 70-80 Nm.
2
3
6
1
4
5
7