Manage Sensor / Sensor / Sensor configuration

• Configure
The submenu Configure is only available for analog and digital 
inputs. Three different kinds of types (4-20mA, State, Count) can 
be defined.

If an analog input is chosen, Configure can configure the input as 
0-20mA or 4-20mA input.

If a digital input is chosen, two settings can be configured:
Type: State or Count

State: Result for this input will be 1 or 0 depending on the 
polarization of the digital input.
Invert pol. With this setting, the polarization of the digital input 
can be changed.
Count: Counts the digital pulses within the interval
Interval [s]: Defines the interval 

• Add parameters 

With Add parameters… new parameters of the selected device 
can be added to the parameter screen and therefore can be used 
as input for one of the controllers. 
To add a parameter to the Parameter screen select a parameter 
(e.g. Add pH) with [Up]- and [Down] buttons and confirm with 
[OK] button. 
• Remove sensor
To remove the selected sensor or input select Remove with [Up]- 
and [Down] buttons and confirm with [OK] button. This will 
remove the sensor and also the parameters which were provided 
by this sensor. If an input of a controller is linked to this sensor/
parameter the controller will be deactivated.

Add sensor

To add an analog sensor select Add 0/4-20mA… with [Up]- and 
[Down] buttons and confirm with [OK] button. 
To add a digital sensor select Add digital in… with [Up]- and 
[Down] buttons and confirm with [OK] button. 
To add an MODBUS sensor select Add MODBUS sensor… with 
[Up]- and [Down] buttons and confirm with [OK] button. 
This function will automatically search the MODBUS port for a 
new sensor and will automatically add the new sensor to the 
sensor list. No further interaction is required.

After adding a sensor, a parameter has to be added. See section 

• Add parameters

9.2.2 Manage parameters

This submenu allows to change the sequence of the parameters 
in the parameter screen.
To change the position of a parameter select the parameter you 
want to shift with [Up]- [Down] buttons and [OK] button. With [Up]- 
and [Down] buttons the position can be changed and [OK] button 
confirms the new position.

9.2.3 Cleaning device

In the Cleaning menu a connected cleaning device can be 
configured. 
Cleaning is only needed if one of the connected sensors is 
submersed and a automatic cleaning device is installed.
Interval [s] is the time between two cleaning actions. To change 
the interval of the cleaning procedure, select Interval [s] with [Up]- 
and [Down] buttons and by pressing [OK] button the interval can 
be changed with [Up]- and [Down] buttons. Pressing [OK] button 
confirms the new interval.
Duration [s] defines the time for one cleaning action (i.e. time the 
cleaning device is activated / powered on). To change the 
duration of the cleaning procedure, select Duration [s] with [Up]- 
and [Down] buttons and by pressing [OK] button the duration can 
be changed with [Up]- and [Down] buttons. Pressing [OK] button 
confirms the new duration.
Wait [s] is the delay for starting a new measurement after a 
cleaning action has finished. To change the delay select Wait [s] 
with [Up]- and [Down] buttons and by pressing [OK] button the 
delay can be changed with [Up]- and [Down] buttons. Pressing 
[OK] button confirms the new duration.

9.2.4 Measurement settings

Interval [s] defines the time between two measurements. To 
change the interval of the measurement, select Interval [s] with 
[Up]- and [Down] buttons and by pressing [OK] button the interval 
can be changed with [Up]- and [Down] buttons. Pressing [OK] 
button confirms the new interval.
This will also change the sampling interval of the analog and 
digital inputs. Range is 1 s to 99 s.

9.2.5 Date/Time

Year defines the year of date. To change the year, select Year 
with [Up]- and [Down] buttons and by pressing [OK] button the 
year can be changed with [Up]- and [Down] buttons. Pressing 
[OK] button confirms the new year.
Month defines the month of date. To change the month, select 
Month with [Up]- and [Down] buttons and by pressing [OK] 
button the month can be changed with [Up]- and [Down] 
buttons. Pressing [OK] button confirms the new month.

Sensor configuration

Configure...
Add parameters...
Remove

Configure

Type:

4-20 mA

Configure

Type:

State

Invert pol.:

No

Configure

Type:

Count

Interval [s]:

60

Add para

Add pH
Add pH-mV
Add Temp.

Add new sensor

Add 0/4-20mA...
Add digital in...
Add MODBUS sensor...

Manage parameters

pH
Temp.
FCL
TCL

Cleaning 1...

Interval [s]:

120

Duration [s]:

2

Wait [s]:

0

Meas. settings

Interval [s]:

5

Date/Time

Year:

2016

Month:

Jan

Day:

8

Hour:

6

Minute:

43

Содержание DID

Страница 1: ...DID Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...vent of product failure 3 1 5 Working with chemicals 3 2 Safety instructions 3 3 Receiving the product 3 3 1 Transporting the product 3 3 2 Scope of delivery 3 3 3 Product updates other 3 4 Installing...

Страница 3: ...nsor installation fitting control unit etc No external interferences i e no electric and electro magnetic interferences by leakage current earth fault of pumps electric motors high voltage currents et...

Страница 4: ...ll them out by temporary increase of the discharge 5 Starting up the product 5 1 Initial startup Once the mounting and installation have been completed and checked the initial start up of the DID will...

Страница 5: ...the selection of the language see section 9 2 8 Select language Subsequently reading and information display will be shown The most recent information obtained by the CU 382 will be displayed even wh...

Страница 6: ...cludes a PID Proportional Integral Derivative controller which is capable of dosing disinfectants to the monitored water drinking bathing waste water The hydraulic part of the station manages the comp...

Страница 7: ...ers temperature 100 240 VAC 50 60 Hz Installation variant BF1 Bypass flow cell 1 sensor BF3 Bypass flow cell 3 sensors TI1 Tank immersion clean water 1 sensor TI2 Tank immersion clean water 2 sensors...

Страница 8: ...Free chlorine dosing control with validation via ORP Free Chlorine 0 2 ppm ORP 2000 2000 mV DID 3 BF3 FCL2 ORP 98915663 Free chlorine dosing control with wide pH variation and validation via ORP Free...

Страница 9: ...cknowledges alarms in the alarm screen Right button Moves right in views or values Down button Moves one line downward the selected line has a triangle as first character Decreases values OK 1 2 3 4 5...

Страница 10: ...tons and pressing OK button will open up the Quick calibration menu Before taking a sample to perform a calibration rinse the sampling point of the flow cell at least 3 times to remove all residuals f...

Страница 11: ...e first row shows date and time the alarm has occurred the first time In the rows two to four the alarm text is displayed With OK button every alarm can be acknowledged If the reason for the occurrenc...

Страница 12: ...position 9 2 3 Cleaning device In the Cleaning menu a connected cleaning device can be configured Cleaning is only needed if one of the connected sensors is submersed and a automatic cleaning device...

Страница 13: ...he Parameter settings menu a parameter can be calibrated monitored linked to an alarm linked to an output and removed Also an overview of all settings of a parameter can be displayed 9 3 1 Calibrate e...

Страница 14: ...and Value will show the current calibrated value Offset and Slope will show the calibration coefficients which are stored onto the sensor Performing a Span calibration This type of calibration is an...

Страница 15: ...digital outputs see section 9 3 6 Output settings 9 3 6 Output settings In the Output settings menu a parameter can be allocated to an analog or digital output If an analog output is chosen 4 mA defi...

Страница 16: ...ght button Pressing OK button will confirm the maximum of pulses min 9 3 7 Parameter info The Parameter info screen shows a summary of all important settings and information for one parameter 9 3 8 pH...

Страница 17: ...with Up and Down buttons and by pressing OK button the integral part can be changed with Up Down Left and Right button Pressing OK button will confirm the new value for Ti To disable the integral part...

Страница 18: ...OK button will confirm the type None as a type will deactivate the controller Hysteresis defines the hysteresis for the 2 P controller The switching points for the controller are Setpoint Hysteresis...

Страница 19: ...available Due to the fact that the controller output range is from 0 to 100 mapping isn t necessary The only parameter which can be changed is the maximum of pulses min for 100 output To change the m...

Страница 20: ...data will be copied to the USB stick Delete logs will delete all system llogfiles To delete all logfiles select Delete logs with Up and Down buttons and by pressing OK button the logfiles will be dele...

Страница 21: ...artup Routine functional check Suspicion of DID malfunction Modification of DID e g integration of additional sensor or device Change of measuring location Depending on the application water compositi...

Страница 22: ...and flow cell can be destroyed if too much force is used Flow detector shows no flow Inlet valve is closed Inlet strainer is blocked Open inlet valve Clean inlet strainer Water is not visible within t...

Страница 23: ...mm 4 Data Units TI1 TI2 General data Number of connectable S CAN sensors 1 2 Min liquid temperature C 0 1 Max liquid temperature C 45 Min ambient temperature C 0 1 Max ambient temperature C 45 Hydraul...

Страница 24: ...r external mechanical relay switch Digital input for external mechanical relay switch Galvanic isolation kV none none Maximum input frequency Hz 100 100 Low input voltage V 7 7 High input voltage V 8...

Страница 25: ...al display 70 x 40 viewing area trans reflective white background Data transfer USB host mode support for data transfer with USB stick Supports FAT FAT32 USB host mode support for data transfer with U...

Страница 26: ...hout packaging With packaging Product number kg kg DID 1 BF1 FCL2 4 26 8 095 98915656 DID 1 BF1 CDI2 4 26 8 095 98915657 DID 1 BF1 PA2 4 26 8 095 98915658 DID 1 BF1 HP2 4 26 8 095 98915659 DID 3 BF3 F...

Страница 27: ...6 6025 0416 TM06 6039 0216 Fig 12 Dimension of control unit CU 382 for wall mounting back mm Fig 13 Dimension of sensor with holder mm pipe with external diameter 50 mm not included 198 137 5 3 30 185...

Страница 28: ...Avoid direct sunlight for proper operation Before installation and operation DID the instruction manual must be read Avoid drying up the sensors The sensors must always be submerged in water Avoid suc...

Страница 29: ...Documents as listed Type of product Measurement Process Control Name of product DID Model number D 320 GF1 230 D 320 GF3 230 Low Voltage Directive 2014 35 EU Standard used EN 61010 1 2010 RoHS2 2011 6...

Страница 30: ...30...

Страница 31: ...Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava iel 60 LV 1035 R ga T lr 3...

Страница 32: ...5263 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: