6.5.16 Mains connection, enclosures D1h and D2h
Enclosure
Torque Nm [ft-lb]
Mains
Motor
Protective earth
Relay
D1h
19-40
19-40
3 (2.2)
0.6 (0.4)
D2h
19-40
19-40
3 (2.2)
0.6 (0.4)
1. Connect the earth conductor to terminal 95 (PE).
2. Connect the mains conductors to terminals 91 (L1), 92
(L2) and 93 (L3).
3. Fix the mains cable with a cable clamp.
6.5.17 Motor connection, enclosures D1h, D2h, D5h and D7h
Take the following terminal positions into consideration when you
design the cable connection.
1. Connect the earth conductor to terminal 99 (PE). See the figures
below.
2. Connect the motor conductors to terminals 96 (U), 97 (V) and 98
(W).
3. Fix the screened cable with a cable clamp.