8. Technical data
Caution
Observe the permissible temperature range of the sensors!
Note
Observe the accuracy of the sensor!
Electronics
16-bit microprocessor technology
Display
Backlit plain-text display
Display languages
German, English, French, Spanish, Russian and Polish
Indication mode
In ppm for measured values of both sensors
Permissible temperatures
Conex
®
DIA-G and sensor interface (without sensor):
• operation: 0 to +40 °C
• storage: 0 to +65 °C
Permissible relative air
humidity
Maximum 90 % at 40 °C (no condensation)
Power supply
• 110-240 V - 10 %/+ 10 % (50/60 Hz)
• 24 VDC
Power consumption
Approximately 30 VA
Material (enclosure)
ABS, resistant to chemicals
Enclosure class
IP65 for Conex
®
DIA-G wall-mounting enclosure and sensor interface
Weight Approximately
1.5
kg
Connections
Screw terminals for cables up to maximum 2.5 mm
2
Safety functions
• Permanent sensor monitoring or automatic sensor test, interval between
tests adjustable from 0.5 to 30 days
• Wire breakage monitoring of all current outputs
• Optional backup battery with backup indication on the display, allowing
Conex
®
DIA-G to work for at least one hour after power failure
• Automatic adjustment of data specific to the sensor (for example
calibration data)
• Display of the sensor exchange intervals with a plain-text message
Backup battery
All devices can be equipped with an external backup battery as an option.
The backup battery supplies the gas warning controller, including the
electrically isolated relays, but no external devices (for example signal
lamp, aeration, sprinkler system, etc.). The battery lasts for about one hour
after power supply failure.