background image

English (GB)

5

7. Electrical connection

The electrical connection must be carried out by an authorised 
electrician in accordance with local regulations. 

The required voltage quality measured at the module terminals is 
- 10 %/+ 6 % of the rated voltage during continuous operation 
(including variation in the supply voltage and losses in cables). 
Check that there is voltage symmetry in the power supply lines, 
i.e. approximately same difference of voltage between the 
individual phases. See also section 

15. Checking of motor and 

cable

, point 1.

In order that the modules meet the EC EMC Directive (2004/108/
EC), a 0.47 

μ

F capacitor (in accordance with IEC 384-14) must 

always be connected over the two phases to which the 
temperature transmitter is connected. See fig. 

11

.

Fig. 11

Electrical connection

The electrical connections must be made close to the flange (fig. 

12

), either by means of a terminal box (figures 

13

 and 

14

) or 

cable termination kit.

Fig. 12

BM/BMhp with terminal box

Fig. 13

Wiring diagram, DOL connection

Fig. 14

Wiring diagram, star-delta connection

7.1 Frequency converter operation

Grundfos motors

Three-phase Grundfos MS and MMS motors can be connected to 
a frequency converter.
If a frequency converter is to be used for booster modules 
connected in series, it must be connected to the last module in 
the flow direction.
We recommend Grundfos CUE. The CUE is a series of frequency 
converters designed for speed control of a wide range of 
Grundfos products, for example BM and BMhp.

During frequency converter operation, it is not advisable to run 
the motor at a frequency higher than the rated frequency (50 or 
60 Hz). In connection with pump operation, it is important never to 
reduce the frequency, and consequently the speed, to such a 
level that the necessary flow of cooling liquid past the motor is no 
longer ensured.
The permissible frequency ranges are 30-50 Hz and 30-60 Hz, 
respectively.
During start, the maximum acceleration time from 0 to 30 Hz is 3 
seconds.
During stop, the maximum deceleration time from 30 to 0 Hz is 3 
seconds.
Depending on the frequency converter type, it may expose the 
motor to detrimental voltage peaks.
The above disturbance can be abated by installing an RC filter 
between the frequency converter and the motor.
Possible increased acoustic noise from the motor can be abated 
by installing an LC filter which will also eliminate voltage peaks 
from the frequency converter.
For further details, please contact your frequency converter 
supplier or Grundfos.

Warning
Connect the pump to an external mains switch 
placed close to the pump and to a motor-protective 
circuit breaker.
It must be possible to lock the mains switch in OFF 
position, isolated. Type and requirements as 
specified in EN 60204-1, 5.3.2.

Warning 
Before making any electrical connections, make sure 
that the power supply has been switched off and that 
it cannot be accidentally switched on. 
The pump must be earthed. 

TM

0

2

 5

255

 2

402

T

M

02

 52

56

 24

10

BM 4", BM/BMhp 6", BM/BMhp 8"

Direct-on-line

TM

00

 4

035

 16

94

RD

BM/BMB

YE
BK

0,47 µF

0.47 

μ

F

RD = Red
YE = Yellow
BK = Black

BM/BMB

M

S
U
P
P

L
Y

L3

L2

L1

Yellow:W

Red   :V

Black  :U

Black

Red

Yellow

BK = Black
RD = Red
YE = Yellow

BM/BMhp 6", BM/BMhp 8"

Star-delta starting 

TM

00

 40

34 

31

97

Caution

If a Grundfos MS motor with a temperature 
transmitter is connected to a frequency converter, a 
fuse incorporated in the transmitter will melt and the 
transmitter will be inactive. The transmitter cannot be 
reactivated. This means that the motor will operate 
like a motor without a temperature transmitter.

W2

V2

U2

W1

V1

B2

R2

Y2

R1

Y1

R

O

F

Y

L

P

P

U

S

B=Black, R=Red, Y=Yellow

U1

M

B1

BK = Black
RD = Red
YE = Yellow

Содержание BM 125

Страница 1: ...BM BMhp Installation and operating instructions GRUNDFOS INSTRUCTIONS ...

Страница 2: ...s to be stored it must be stored on a frost free location or it must be ensured that the motor liquid is frost proof 1 Symbols used in this document 2 2 General description 2 2 1 Pumped liquids 2 2 2 Sound pressure level 2 3 Delivery transportation and storage 2 3 1 Frost protection 2 4 Preparation 3 5 Installation 3 5 1 Booster modules connected in series and in parallel 4 6 Pipe connection 4 7 E...

Страница 3: ...allation Grundfos booster modules are as standard supplied without a built in non return valve However a non return valve can be built in on request See fig 7 In systems involving the risk of water hammer in connection with start stop the necessary measures must be taken to minimise this risk The booster modules are suitable for both vertical and horizontal installation however the discharge port ...

Страница 4: ...pass mounted above each other 6 Pipe connection The booster modules are fitted with clamp liners for Victaulic PJE clamp couplings on the suction and discharge sides See fig 10 Fig 10 Pipe connection using clamp couplings TM00 3760 1902 TM00 3761 1902 Air escape valve Closing valve Non return valve Pressure switch Flow switch Motor operated valve Diaphragm tank Pressure gauge Air escape valve Isol...

Страница 5: ...y the speed to such a level that the necessary flow of cooling liquid past the motor is no longer ensured The permissible frequency ranges are 30 50 Hz and 30 60 Hz respectively During start the maximum acceleration time from 0 to 30 Hz is 3 seconds During stop the maximum deceleration time from 30 to 0 Hz is 3 seconds Depending on the frequency converter type it may expose the motor to detrimenta...

Страница 6: ... 1 2 3 4 until all modules are running When module 2 is checked module 1 must be running When module 3 is checked modules 1 and 2 must be running etc If modules in series are also connected in parallel fig 8 the direction of rotation of each section connected in series should be checked After having checked the direction of rotation stop the modules in the order 4 3 2 1 The booster system is now r...

Страница 7: ...nce with the estimated inlet pressure At a pressure lower than 0 5 bar for BM 4 and BM BMhp 6 and 1 bar for BM BMhp 8 an alarm is given and the module must be stopped without delay All discharge connections to the system should be fitted with a flow switch which will stop the system at the set minimum flows The above monitoring devices ensure a correct inlet pressure and a minimum flow of cooling ...

Страница 8: ...rt circuited not cutting in Replace the coil Check the coil voltage d The control circuit has cut out or is defective Check the control circuit and the contacts in the monitoring devices pressure switch flow switch etc e The motor supply cable is defective Check motor and cable See also section 15 Checking of motor and cable 3 The booster system runs but gives no water or develops no pressure a No...

Страница 9: ...ue and multiply by 100 The result is the current unbalance in For three phase motors the current unbalance must not exceed 5 If so or if the current exceeds the maximum operating current there are the following possible faults The contacts of the motor protective circuit breaker are burnt Replace the contacts Poor connection in leads possibly in terminal box Too high or too low supply voltage See ...

Страница 10: ...endix 1 LOG BOOK for BM BMhp booster modules Product No Installation date Company your ref Country Type Start of operation City VFD Softstart Brand Date Amb temp Liquid temp Flow pressure Current A Voltage V Comments ...

Страница 11: ...Appendix 11 System sketch ...

Страница 12: ... tanács alábbi előírásainak IT Dichiarazione di conformità CE Grundfos dichiara sotto la sua esclusiva responsabilità che i prodotti BM e BMhp ai quali si riferisce questa dichiarazione sono conformi alle seguenti direttive del Consiglio riguardanti il riavvicinamento delle legislazioni degli Stati membri CE LT EB atitikties deklaracija Mes Grundfos su visa atsakomybe pareiškiame kad gaminiai BM i...

Страница 13: ...nly to water pumps marked with the minimum efficiency index MEI See pump nameplate This EC declaration of conformity is only valid when published as part of the Grundfos installation and operating instructions publication number 150095 1116 Bjerringbro 9th November 2016 Carsten Høybye Pedersen Senior Manager Grundfos Holding A S Poul Due Jensens Vej 7 8850 Bjerringbro Denmark Person authorised to ...

Страница 14: ...ɩɥɭɚɬɚɰɢɢ ˀ ˋ 1 ˀ ˋ 2 ʿ ˀ ʧ ʿ ˋ 3 ˁ ʻ BM BMh ˀ ˁ 004 2011 ʽ ˀ ˁ 010 2011 ʽ ˀ ˁ 020 2011 ˑ KAZ BM BMh ɉɚɣɞɚɥɚɧɭ ɛɨɣɵɧɲɚ ɧԝɫԕɚɭɥɵԕ ʤ ಢ ಱ ದ ದ ದಱ ಱ 1 ʿ ಱ ದ ದ 2 ʧ ಪ ದ ದಱ ౢಱ ಱ ದ ದ ౢಱ ಪ ದ ಪ 3 ಪ ದ ದ ದ ಢ ಢ ದ ˁ ದ BM BMh ಢ ದ ಪ ದ ˀ ˁ 004 2011 ʺ ದ ದ ˀ ˁ 010 2011 ದ ಪ ˀ ˁ 020 2011 ʶ ʽ ಢ ಪ ದ ಪ ...

Страница 15: ...ʇɸɺʏʗʅʋɸʍ ʈɼʓʍɸʗʆ ʖɼʉɸɻʗʕɸʅ Ɍʗʏʙʍɻʝʏʔ Ɋʍʘɼʛ ʚɸʔʖɸʀʉʀʂ ʕɼʗʒʏʙʋ ʍʎʕɸʅ ʇʉʏʙʋʏʕ ɝɸʔ 3 ʖɼʉɼʆʏʙʀʌʏʙʍ ɸʗʖɸɻʗʋɸʍ ɸʋʔɸʀʕʂ ʕɼʗɸɹɼʗʌɸʃɵ ʍʎʕɸʅ ʔɸʗʛɸʕʏʗʋɸʍ ʑʂʖɸʆʂ ʕʗɸ ɨɼʉɼʆʏʙʀʌʏʙʍʍɼʗ ʇɸʕɸʔʖɸɺʗʋɸʍ ʋɸʔʂʍɵ BM BMh ʖʂʑʂ ʑʏʋʑɼʗɿ ʔɼʗʖʂʝʂʆɸʘʕɸʅ ɼʍ ʇɸʋɸʈɸʌʍ ɝɸʛʔɸʌʂʍ ɝʂʏʙʀʌɸʍ ʖɼʄʍʂʆɸʆɸʍ ʆɸʍʏʍɸʆɸʗɺʂ ʑɸʇɸʍʒʍɼʗʂɵ ǺǸ Ǻǹ 004 2011 ɪɸʅʗɸʕʏʃʖ ʔɸʗʛɸʕʏʗʏʙʋʍɼʗʂ ʕɼʗɸɹɼʗʌɸʃ ǺǸ Ǻǹ 010 2011 ɝɼʛɼʍɸʍɼʗʂ ʞ ʔɸʗʛɸʕʏʗʏʙʋʍɼʗʂ ɸʍʕʖɸʍɺʏʙʀʌɸʍ ʕ...

Страница 16: ...16 ...

Страница 17: ...ea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd 7 Jalan Peguam U1 25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone 60 3 55...

Страница 18: ...7085 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S www grundfos com ...

Отзывы: