8. Control functions

8.1 Elements on the control panel

Fig. 9

Control panel

8.2 Display

The display (1) is on when you have switched on 
the power supply.
The display shows the actual pump power 
consumption in watt (integer) or the actual flow 
during operation.
If a fault is indicated, correct the fault and reset 
the pump by switching the power supply off and 
on.
If the pump impeller is rotated, for example 
when filling the pump with water, sufficient 
energy can be generated to light up the display 
even if the power supply has been switched off.

Light field indicating high and low flow

The light field blinks for low flow

– If the flow is lower than 1 gpm, the light 

field alternately flashes between "0" and 
"1" randomly.

The light field shows HI for high flow

– If the flow is higher than 12 gpm, the light 

field shows "HI" on user interface. 

8.2.1 Light fields indicating the pump setting

The pump has optional performance settings 
which you can select with the push-button. See 
fig. 

9

.

The pump setting is indicated by light fields in 
the display. See fig. 

10

.

Fig. 10

Light fields

For more information about the function of the 
settings, see section 

9. Fault finding the product

.

8.3 Setting the pump

You can change the pump setting by pressing 
the push-button.

8.3.1 Factory default setting

The pump's factory default setting is the 
AUTO

ADAPT

 setting.

8.3.2 Changing from recommended to 

alternative pump setting

Heating systems are "slow" systems that cannot 
be set to the optimum operation within minutes 
or hours.
However, if the recommended pump setting in 
some applications does not give the desired 
distribution of heat in the rooms of the house, 
you can change to an alternative pump setting.

8.4 Selection of control mode by 

application

See also sections 

8. Control functions

 and 

8.6 Pump performance and operating mode 
selection

.

TM0

4

 342

1 3

5

11

Pos. Description

1

Display showing the power 
consumption in watt or the flow.

Light field indicating high and low flow

2

Production code:

• 1st and 2nd figures: year

• 3rd and 4th figures: week

3

Light field indicating fixed speed

4

Light field indicating constant pressure

5

Light field indicating AUTO

ADAPT

6

Push-button for selection of pump 
setting

TM

06 

751

351

6

Application

Control mode

Floor heating

Constant pressure

Two-pipe system

AUTO

ADAPT

Ventilation

Speed 1, 2 or 3

Boiler-shunt

Speed 1, 2 or 3

One-pipe system

Speed 1, 2 or 3 or 
constant pressure

Domestic hot water

Speed 1, 2 or 3

Содержание ALPHA2 15-55F CI 115V

Страница 1: ...GRUNDFOS INSTRUCTIONS ALPHA2 Variable speed circulators with AutoADAPT Installation and operating instructions 3191277 Listed Conforms to ANSI UL Std 778 Certified to CAN CSA Std C22 2 No 108 ...

Страница 2: ...t was purchased together with proof of purchase and installation date failure date and supporting installation data Unless otherwise provided the distributor or dealer will contact Grundfos or an authorized service station for instructions Any defective product to be returned to Grundfos or a service station must 1 Limited warranty 2 2 General information 3 2 1 Symbols used in this document 3 3 Re...

Страница 3: ...al warranty period set forth by the original purchase date 2 General information 2 1 Symbols used in this document The text accompanying the three hazard symbols DANGER WARNING and CAUTION will be structured in the following way Example DANGER Indicates a hazardous situation which if not avoided will result in death or serious personal injury WARNING Indicates a hazardous situation which if not av...

Страница 4: ...ing instructions one check valve one Check Valve Installed sticker 4 Installing the product WARNING Pressurized system Death or serious personal injury Before dismantling the pump drain the system or close the isolating valve on either side of the pump before the screws are removed The pumped liquid may be scalding hot and under high pressure DANGER Electric shock Death or serious personal injury ...

Страница 5: ...ping No permanent damage will occur In fact Grundfos encourages testing the various hydraulic modes with your hydronic system to ensure maximum energy savings and comfort level 6 With zone panel control applications when there is a call for heat and power has been sent to the pump the pump will remember and restart from the last duty point and hydraulic mode 4 2 Mechanical installation When making...

Страница 6: ...d position CAUTION Hot surface Minor or moderate personal injury Position the pump so that persons cannot accidentally come into contact with hot surfaces DANGER Electric shock Death or serious personal injury Switch off the power supply before starting any work on the product Make sure that the power supply cannot be accidentally switched on WARNING Pressurized system Death or serious personal in...

Страница 7: ...pply a silicon sealant to the internal contours of the shell in order to eliminate any air gaps and prevent condensation between the insulating shell and pump housing Alternatively you can insulate the pump manually in accordance with standard insulating requirements for heating and cooling systems The fitting of insulating shells will increase the pump dimensions Fig 6 Fitting insulating shells t...

Страница 8: ...trician in accordance with the latest edition of the National Electric Code and state local codes and regulations DANGER Electric shock Death or serious personal injury Switch off the power supply before starting any work on the product Make sure that the power supply cannot accidentally switched on DANGER Electric shock Death or serious personal injury This pump has not been investigated for use ...

Страница 9: ...e sure to connect the ground cable conductor green of the pump to the ground cable conductor of the power supply Step Action Illustration 3a Strip the ends of the cable conductors as illustrated TM06 8250 4816 3b Align the end of each of the pump s cable conductors including any frayed strands with the end of the corresponding cable conductor from the power supply Green conductor ground Black cond...

Страница 10: ...ation and start up The pump is easy to install Thanks to the AUTOADAPT function factory setting you can start the pump in most cases without making any settings High degree of comfort Minimum noise from valves etc Low energy consumption Low energy consumption compared to conventional circulator pumps 6 2 Applications The ALPHA2 circulator pump is designed for the circulation of water in heating sy...

Страница 11: ...hnical data 6 3 1 Glycol The pump is designed for pumping clean water or up to 50 50 mixtures by weight of glycol and water For glycol usage as well as additional liquid information see section 10 Technical data To prevent the glycol mixture from degrading avoid temperatures exceeding the rated liquid temperature and minimize the operating time at high temperatures It is important to clean and flu...

Страница 12: ...a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment to an ou...

Страница 13: ...ction of the settings see section 9 Fault finding the product 8 3 Setting the pump You can change the pump setting by pressing the push button 8 3 1 Factory default setting The pump s factory default setting is the AUTOADAPT setting 8 3 2 Changing from recommended to alternative pump setting Heating systems are slow systems that cannot be set to the optimum operation within minutes or hours Howeve...

Страница 14: ...ditions You can quickly vent the pump by setting the pump to speed III for a short period In speed II the pump is set on the medium curve under all operating conditions In speed I the pump is set on the minimum curve under all operating conditions Manual summer mode In manual summer mode the pump is stopped to save energy and only the electronics are running To avoid lime deposit that could block ...

Страница 15: ...all operating conditions Constant pressure I The duty point of the pump will move left and right along the lowest constant pressure curve depending on the water demand in the system The head is kept constant irrespective of the water demand Constant pressure II The duty point of the pump will move left and right along the middle constant pressure curve depending on the water demand in the system T...

Страница 16: ...age is too high Check that the power supply falls within the specified range b The rotor is blocked by impurities Remove the impurities ___ ___ a Supply voltage is too low Switch the power off and on Check for air locked rotor and or voltage Correct the power supply 2 Noise in the system Light field is on a There is air in the system Install an air eliminator b The flow is too high Reduce the pump...

Страница 17: ...vent over time Install an air eliminator If necessary rework the piping d The valves are sticking Make sure all valves are in good working order i e remove lime deposits e Wrong direction of flow See the direction of flow arrow marked on the pump Reinstall the pump to correct the direction of flow f The boiler is not working properly Check the water temperature from the boiler and check the boiler...

Страница 18: ...lel pumping applications Curve conditions Test liquid Airless water Curves apply to a density of 983 2 kg m3 and a liquid temperature of 140 F 60 C All curves show average values and should not be used as guarantee curves If a specific minimum performance is required individual measurements must be made Curves apply to a kinematic viscosity of 0 474 cSt Approximate power usage Liquid temperature M...

Страница 19: ...f the product This product or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundfos company or service workshop ...

Страница 20: ...20 ...

Страница 21: ...00 www grundfos us GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS México Boulevard TLC No 15 Parque Industrial Stiva Aeropuerto C P 66600 Apodaca N L México Phone 011 52 81 8144 4000 Fax 011 52 81 8144 4010 www grundfos mx ...

Страница 22: ... com Trademarks displayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2020 Grundfos Holding A S all rights reserved ...

Отзывы: