background image

English (GB)

30

12. Accessories

12.1 Unions and valve kits

* When ordering for UK versions, use product numbers for 25-xx (G 1 1/2).

Available on request.

G-threads have a cylindrical form in accordance with the EN-ISO 
228-1 standard. R-threads have a conical form in accordance 
with the ISO 7-1 standard. In the case of a thread of size 1 1/2", 
the threads are specified as G 1 1/2 or R 1 1/2. You can only 
screw male G-threads (cylindrical) into female G-threads. You 
can screw male R-threads (conical) into female G- or R-threads. 
See fig. 

42

.

Fig. 42

G-threads and R-threads

12.2 Insulating shells

The pump is supplied with two insulating shells. Type A pumps 
with air-separating chamber are not supplied with insulating 
shells. However, you can order insulating shells as an accessory. 
See table below.
The insulation thickness of the insulating shells corresponds to 
the nominal diameter of the pump. 
The insulating shells, which are tailored to the individual pump 
type, enclose the entire pump housing. The insulating shells are 
easy to fit around the pump. See fig. 

43

.

Fig. 43

Insulating shells

Product numbers, unions

ALPHAx

Con

n

e

c

tion

3/4

1

1 1/4

1

1 1/4

3/4

1

1 1/4

22

28

15

18

22

28

42

15-xx*

G 1

15-xx N*

25-xx

G 1 1/2

529921 529922 529821 529925 529924

25-xx N

529971 529972 

519805 519806 505539 519808 519809

529977 529978 529979

32-xx

G 2

509921 509922

32-xx N

509971

529995

Rp

R

Rp

mm

mm

TM0

6

 586

7 021

6

R

Rp

Rc

G

Pump type

Product number

Available

ALPHAx XX-XX 130

98091786

spare part

ALPHAx XX-XX 180

98091787

spare part

ALPHAx XX-XX A

505822

accessory

TM

0

6

 5

822

 0

216

Содержание ALPHA SOLAR 15-75 130

Страница 1: ...ALPHA2 ALPHA3 Installation and operating instructions GRUNDFOS INSTRUCTIONS ...

Страница 2: ...ass valve 17 8 Operating the product 17 8 1 Using automatic night setback 17 8 2 Function of automatic night setback 18 8 3 Setting manual summer mode 18 8 4 Dry running protection 18 8 5 ALPHA Reader 18 8 6 High torque start 18 9 Fault finding 19 10 Technical data and installation dimensions 20 10 1 Technical data 20 10 2 Dimensions ALPHAx XX 40 XX 50 XX 60 XX 80 21 10 3 Dimensions ALPHAx 25 40 A...

Страница 3: ...g shells but with a plug designed for ALPHA SOLAR DANGER Indicates a hazardous situation which if not avoided will result in death or serious personal injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious personal injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate personal injury SIGNAL WORD Descripti...

Страница 4: ...fig 1 pos C See also section 3 2 Control box positions 3 Tighten the fittings 3 2 Control box positions Fig 2 Control box positions Always install the pump with a horizontal motor shaft Pump installed correctly in a vertical pipe See fig 2 pos A Pump installed correctly in a horizontal pipe See fig 2 pos B Do not install the pump with a vertical motor shaft See fig 2 pos C and D 3 2 1 Positioning ...

Страница 5: ...s install the pump with horizontal motor shaft Position the control box in position 9 o clock See fig 7 Fig 7 Position of the ALPHA SOLAR control box You can turn the control box in steps of 90 TM05 3151 1212 TM05 3147 1212 CAUTION Hot surface Minor or moderate personal injury Position the pump so that persons cannot accidentally come into contact with hot surfaces CAUTION Pressurised system Minor...

Страница 6: ...ry out the electrical connection and protection in accordance with local regulations The motor requires no external motor protection Check that the supply voltage and frequency correspond to the values stated on the nameplate See section 6 4 1 Nameplate Connect the pump to the power supply with the plug supplied with the pump See steps 1 to 7 TM05 3058 0912 Do not insulate the control box or cover...

Страница 7: ...9 3812 3 Bend the cable with the cable conductors pointing upwards TM05 5540 3812 4 Pull out the conductor guide plate and throw it away TM05 5541 3812 5 Click the plug cover onto the power supply plug TM05 5542 3812 Max 1 5 mm2 12 mm 5 5 10 mm 7 mm 17 mm 6 Screw the cable gland onto the power supply plug TM05 5543 3812 7 Insert the power supply plug into the male plug in the pump control box TM05...

Страница 8: ...nnect the cable to the control box with a TE Mini Superseal plug The signal cable can be supplied with the pump as an accessory Step Action Illustration 1 Loosen the cable gland and remove it from the plug TM05 5545 3812 2 Pull off the plug cover while pressing on both sides TM05 5546 3812 3 Add the conductor guide plate to loosen all three cable conductors at the same time If the guide plate is m...

Страница 9: ...Venting the heating system Fig 13 Venting of the heating system Vent the heating system as follows via an air vent valve installed above the pump 1 via a pump housing with air separator 2 In heating systems that often contain much air we recommend that you install pumps with pump housing with air separator i e ALPHAx XX XX A When the heating system has been filled with liquid do as follows 1 Open ...

Страница 10: ...n heating systems domestic hot water systems as well as air conditioning and cold water systems Cold water systems are defined as systems where the ambient temperature is higher than the temperature of the pumped liquid ALPHAx is the best choice for the following systems underfloor heating systems one pipe systems two pipe systems ALPHAx is suitable for the following Systems with constant or varia...

Страница 11: ...lammable material Minor or moderate personal injury Do not use the pump for flammable liquids such as diesel oil and petrol WARNING Biological hazard Death or serious personal injury In domestic hot water systems the temperature of the pumped liquid must always be above 50 C due to the risk of legionella WARNING Biological hazard Death or serious personal injury In domestic hot water systems the p...

Страница 12: ...Constant curve Automatic night setback Manual summer mode Dry running protection ALPHA Reader High torque start ALPHAx XX 40 ALPHAx XX 50 ALPHAx XX 60 ALPHAx XX 80 Example ALPHAx 25 40 N 180 Pump type Blank Standard version L Limited version Nominal diameter DN of inlet and outlet ports mm Maximum head dm Blank Cast iron pump housing A Pump housing with air separator N Stainless steel pump housing...

Страница 13: ...n for enabling or disabling of automatic night setback The button enables and disables automatic night setback See fig 18 pos 4 Automatic night setback is only relevant for heating systems prepared for this function See section 9 Fault finding The light field is on when automatic night setback is active See fig 18 pos 3 Factory setting automatic night setback is not active If you have set the pump...

Страница 14: ...21 Three proportional pressure curves settings The selection of the proportional pressure setting depends on the characteristics of the heating system and the actual heat demand 7 7 2 Pump setting for one pipe heating systems Fig 22 Selection of pump setting for system type Factory setting AUTOADAPT Recommended and alternative pump settings according to fig 22 AUTOADAPT See section 7 7 1 Pump sett...

Страница 15: ...p runs at a constant speed independent of the actual flow demand in the system The pump performance follows the selected performance curve I II or III See fig 27 where II has been selected For further information see section 11 1 Guide to performance curves Fig 27 Three constant curve constant speed settings The selection of the constant curve constant speed setting depends on the characteristics ...

Страница 16: ...p will move out or in on the lowest constant pressure curve depending on the heat demand in the system See fig 28 The head is kept constant irrespective of the heat demand CP2 Intermediate constant pressure curve The duty point of the pump will move out or in on the intermediate constant pressure curve depending on the heat demand in the system See fig 28 The head is kept constant irrespective of ...

Страница 17: ...ault finding 8 Operating the product 8 1 Using automatic night setback Fig 30 Automatic night setback activated If you select speed I II or III automatic night setback is disabled You do not have to re enable automatic night setback if the power supply has been switched off If the power supply is switched off when the pump is running on the curve for automatic night setback the pump starts in norm...

Страница 18: ...c night setback button 3 to 10 seconds See fig 30 The green light field flashes quickly After a short while the display turns off and the green light field flashes slowly Fig 31 Automatic night setback button 8 3 2 Deactivating manual summer mode Deactivate the manual summer mode by pressing any of the buttons Then the pump returns to the previous mode and setting 8 4 Dry running protection The dr...

Страница 19: ...n and E 1 a The rotor is blocked Remove the impurities Changes between and E 2 a Insufficient supply voltage Check that the supply voltage falls within the specified range Changes between and E 3 a Electrical fault Replace the pump Changes between and E 4 a Dry running protection Make sure that there is sufficient liquid in the pipe system Reset the error by pressing any button or switch off the p...

Страница 20: ...n 43 dB A Ambient temperature 0 40 C Temperature class TF110 to CEN 335 2 51 Surface temperature The maximum surface temperature will not exceed 125 C Liquid temperature 2 110 C Power consumption in manual summer mode 0 8 watt Specific EEI values ALPHAx XX 40 EEI 0 15 ALPHAx XX 50 EEI 0 16 ALPHAx XX 60 EEI 0 17 ALPHAx XX 80 EEI 0 18 ALPHAx XX 40 A EEI 0 18 ALPHAx XX 60 A EEI 0 20 Ambient temperatu...

Страница 21: ...44 5 44 5 36 8 103 5 52 1 1 2 ALPHAx 25 80 N 130 130 60 5 60 5 44 5 44 5 36 8 103 5 52 1 1 2 ALPHAx 25 40 180 180 60 5 60 5 44 5 44 5 35 9 103 5 52 1 1 2 ALPHAx 25 40 N 180 180 60 5 60 5 44 5 44 5 36 9 103 5 52 1 1 2 ALPHAx 25 50 180 180 60 5 60 5 44 5 44 5 35 9 103 5 52 1 1 2 ALPHAx 25 50 N 180 180 60 5 60 5 44 5 44 5 36 9 103 5 52 1 1 2 ALPHAx 25 60 180 180 60 5 60 5 44 5 44 5 35 9 103 5 52 1 1 ...

Страница 22: ... 60 A Dimensional sketches and table of dimensions Fig 34 ALPHAx 25 40 A 25 60 A TM05 2574 0212 Pump type Dimensions L1 B1 B2 B3 B4 H1 H2 H3 G ALPHAx 25 40 A 180 180 63 5 98 32 63 50 124 81 1 1 2 ALPHAx 25 60 A 180 180 63 5 98 32 63 50 124 81 1 1 2 ...

Страница 23: ...e curves If a specific minimum performance is required individual measurements must be made The curves for speeds I II and III are marked The curves apply to a kinematic viscosity of 0 474 mm2 s 0 474 cSt The conversion between head H m and pressure p kPa has been made for water with a density of 1000 kg m3 For liquids with other densities for example hot water the outlet pressure is proportional ...

Страница 24: ... TM05 1672 4111 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 Q m h 0 1 2 3 4 m H III II I 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 Q m h 0 5 10 15 20 W P1 III II I PP1 CP1 PP2 CP2 PP3 CP3 Setting P1 W I1 1 A AUTOADAPT 3 18 0 04 0 18 Min 3 0 04 Max 18 0 18 ...

Страница 25: ... 4111 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 Q m h 0 1 2 3 4 5 m H III II I 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 Q m h 0 5 10 15 20 25 W P1 III II I PP1 CP1 PP3 CP3 CP2 PP2 Setting P1 W I1 1 A AUTOADAPT 3 26 0 04 0 24 Min 3 0 04 Max 26 0 24 ...

Страница 26: ...0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 Q m h 0 1 2 3 4 5 6 III II I 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 Q m h 0 5 10 15 20 25 30 35 W P1 III II I H m PP1 CP1 CP3 CP2 PP2 PP3 Setting P1 W I1 1 A AUTOADAPT 3 34 0 04 0 32 Min 3 0 04 Max 34 0 32 ...

Страница 27: ...x 25 40 A TM05 2016 4211 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 Q m h 0 1 2 3 4 m H III II I 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 Q m h 0 5 10 15 20 W P1 III II I PP1 CP1 CP3 CP2 PP2 PP3 Setting P1 W I1 1 A AUTOADAPT 3 18 0 04 0 18 Min 3 0 04 Max 18 0 18 ...

Страница 28: ...11 1 0 0 8 0 6 0 4 0 2 0 0 Q m h 2 8 2 6 2 4 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 Q m h 0 1 2 3 4 5 6 m H III II I 1 2 1 4 1 6 1 8 2 0 2 2 0 5 10 15 20 25 30 35 W P1 III II I PP1 CP1 CP3 CP2 PP2 PP3 Setting P1 W I1 1 A AUTOADAPT 3 34 0 04 0 32 Min 3 0 04 Max 34 0 32 ...

Страница 29: ...English GB 29 11 8 Performance curves ALPHAx XX 80 N Fig 41 ALPHAx 25 60 A TM061285 2114 PP1 CP1 PP2 CP2 PP3 CP3 Setting P1 W I1 1 A AUTOADAPT 3 50 0 04 0 44 Min 3 0 04 Max 50 0 44 ...

Страница 30: ...t supplied with insulating shells However you can order insulating shells as an accessory See table below The insulation thickness of the insulating shells corresponds to the nominal diameter of the pump The insulating shells which are tailored to the individual pump type enclose the entire pump housing The insulating shells are easy to fit around the pump See fig 43 Fig 43 Insulating shells Produ...

Страница 31: ...th a single push button one red green LED and four yellow LEDs Fig 46 User interface with one push button and five LEDs The user interface shows the following operating status alarm status settings view after pressing the button 13 6 Operating status During operation the display shows the actual operating status or the alarm status 13 7 Alarm status If the circulator has detected one or more alarm...

Страница 32: ...SOLAR CONSTANT CURVE 1 CONSTANT CURVE 2 CONSTANT CURVE 3 CONSTANT CURVE 4 PWM C PROFILE SOLAR 8 5 m 6 5 m 5 5 m 4 5 m 10 5 m 6 5 m Fault Description The rotor is blocked Deblock the rotor The supply voltage is low Make sure that there is sufficient voltage supply to the pump Electrical error Replace the pump and send the pump to the nearest Grundfos service centre ON 230 V No 2 5 mm 160 V ON 230 V...

Страница 33: ...trol to a PWM signal When you use SIKON HE you can replace the conventional 230 V UPS solar pumps by Grundfos ALPHA SOLAR pumps without having to change the controller to a high efficiency pump controller The function of the performance control of the pump is maintained Fig 49 Digital solar circuit controller For further information about the controller see www prozeda de 16 Technical data TM04 99...

Страница 34: ...Curve 4 7 5 m Setting Max P1 nom Curve 1 19 W Curve 2 28 W Curve 3 35 W Curve 4 45 W Electrical data 1 x 230 V 50 Hz Settings Speed P1 W I 1 1 A PWM C PP CP CC Min 2 0 04 1 4 Max 45 0 48 TM06 6493 1516 TM06 5636 5115 B1 B2 H3 H2 H1 L1 L3 Pump type Dimensions mm Connections Weight kg L1 L3 B1 B2 H1 H2 H3 ALPHA SOLAR 15 75 130 130 90 72 45 36 92 128 G 1 1 8 ALPHA SOLAR 25 75 130 130 90 72 45 36 92 1...

Страница 35: ... information see the end of life information at www grundfos com Subject to alterations TM06 3652 0815 Note PWM speed curves on request 4 Pñ K P N3D S 4 O V 4 Pñ K 3 EEI 0 20 Part 3 PL avg 25 W Setting Max head nom Curve 1 6 5 m Curve 2 8 5 m Curve 3 10 5 m Curve 4 14 5 m Setting Max P1 nom Curve 1 39 W Curve 2 45 W Curve 3 52 W Curve 4 60 W Electrical data 1 x 230 V 50 Hz Settings Speed P1 W I 1 ...

Страница 36: ...ács alábbi előírásainak IT Dichiarazione di conformità CE Grundfos dichiara sotto la sua esclusiva responsabilità che il prodotto Grundfos ALPHA2 ALPHA3 al quale si riferisce questa dichiarazione è conforme alle seguenti direttive del Consiglio riguardanti il riavvicinamento delle legislazioni degli Stati membri CE LT EB atitikties deklaracija Mes Grundfos su visa atsakomybe pareiškiame kad gaminy...

Страница 37: ...7 A1 2001 A2 2008 Ecodesign Directive 2009 125 EC Circulator pumps Commission Regulation No 641 2009 and 622 2012 Standards used EN 16297 1 2012 EN 16297 2 2012 EN 16297 3 2012 Bjerringbro 20st of April 2016 Svend Aage Kaae Technical Director Grundfos Holding A S Poul Due Jensens Vej 7 8850 Bjerringbro Denmark Person authorised to compile the technical file and empowered to sign the EC declaration...

Страница 38: ...38 ...

Страница 39: ... 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd 7 Jalan Peguam U1 25 Glenmarie Industrial Park 40150 Shah Alam Sela...

Страница 40: ...88108 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S www grundfos com ...

Отзывы: