Cleaning, inspection, maintenance
24 | 44
B
A
_
T
D3
-A
K
0
0
0
en
_035
6.2 Intervals
Operation
Interval
Execution
Inspection
2 months
Owner/user
Maintenance
6 months
Owner/user or
specialist installer
Change of the
filter element
In case of soiling
and during
maintenance
Owner/user or
specialist installer
6.3 Inspection
According to DIN EN 806-5, the owner/user has to inspect the
filters every 2 months.
► Check the installation for leaks (refer to chapter 5).
6.4 Maintenance
6.4.1 Preparation for hygienic change of filter the element
1.
Place a bucket under the filter.
2.
Close shut-off valve 1.
3.
Depressurise the line.
4.
Close shut-off valve 2.
5.
Tilt the filter cover forwards (1) and pull it downwards (2).