Mobile reverse osmosis system
AVRO-flex 400
Order no.
095 752 946-inter Edited by: phar-mrie G:\BA-752946-INTER_095_AVRO-FLEX_400.DOCX
23
D Installation
1 | General installation instructions
The installation site must provide adequate space. A foundation of a
sufficient size and adequate load carrying capacity has to be pro-
vided. The required connections must be provided prior to the installa-
tion of the system. For dimensions and connection data, please refer
to table C-1.
Note:
For the installation of systems with optional accessories (refer
to Chapter C, item 6.3), also observe the operation manuals supplied
with these components.
1.1 Water connection
Certain binding rules must always be observed when installing a mo-
bile reverse osmosis system AVRO-flex 400. Additional recommenda-
tions are given in order to facilitate the handling of the system. The in-
stallation instructions described below are also illustrated in fig. E-2.
Binding rules
The installation of a mobile reverse osmosis system AVRO-flex 400
represents a major interference with the drinking water system.
Therefore, only authorised experts may install such systems.
Observe local installation guidelines and general regulations.
Install a drinking water filter (e. g. BOXER KD) upstream of the sys-
tem.
Install a system separator upstream – not required when using a
GENO-therm filling device.
Install an activated carbon filter upstream, if required.
Provide a drain connection (minimum DN 50) to discharge the con-
centrate.
Note:
If the concentrate is directed to a lifting system, the delivery
rate of the lifting system should at least be 800 l/h.
Warning!
The installation site must have a floor drain. If no floor drain
is available, an adequate safety device needs to be installed (refer to
Chapter C, item 6.3 “Optional accessories”).
Warning!
Floor drains that discharge to a lifting system do not work in
case of a power failure.
Recommendation
If the mobile reverse osmosis system AVRO-flex 400 is not connected
to the optional filling device GENO-therm, a sampling valve should be
installed directly upstream and downstream of the mobile reverse os-
mosis system AVRO-flex 400. This simplifies the sampling for the reg-
ular quality control (functional check).