6.3 DC side wiring

Ø

Ø

Ø

When  the  sun  shines  on  the  panel,  voltage  will  be  generated. 

The  high  voltage  after  the  connection  may  cause  life-threatening. 
Therefore, before connecting the DC input line, the panel should be 
shielded with  opaque  material  before  operation,  and  the  inverter  is 
ensured. The DC switch of the unit is in the "OFF" state, otherwise 
the high voltage of the inverter may be life-threatening.

To avoid electric shock, do not touch the live parts and carefully 

connect the terminals.

Make sure the AC switch is disconnected before wiring.

Please ensure that the following conditions are met, otherwise it may 
cause fire hazard or damage to the inverter. In this case, the company 
does not carry out warranty and assumes any responsibility.

Ø

The maximum open circuit voltage of each string of PV modules 

shall not exceed 1100Vdc under any conditions.

Ø

The  PV  modules  connected  in  series  in  the  PV  string  are  all  of 

the same specification type.

Ø

The  maximum  short-circuit  current  of  each  PV  string  shall  not 

exceed 25A under any conditions.

Ø

The  total  output  power  of  all  PV  strings  must  not  exceed  the 

maximum input power of the inverter.

Ø

In  order  to  optimize  the  system  configuration,  it  is 

recommended to connect the same number of PV modules with two 

inputs.

Ø

If  the  inverter  output  is  directly  connected  to  the  grid  (ie  the 

output  side  is  not  connected  to  the  low  frequency  isolation 
transformer), make sure that the PV string is not grounded.

Ø

If  the  inverter  is  for  a  specific  model  of  the  thin-film  battery 

pack  (PV-ground),  please  turn  on  the  low-frequency  isolation 
transformer after the output is connected, otherwise the inverter will 
be damaged.

Ø

   

If  it  is  measured  that  there  is  a  stable  non-zero  DC  voltage 

between  the  positive  pole  and  the  ground  of  the  PV  string,  it 

indicates that an insulation fault has occurred at a certain position in 

the PV string, and it is necessary to ensure that the fault is repaired 

before continuing the wiring.

Moisture and dust penetration can damage the inverter.

Make sure the cable connector is securely tightened.

If the cable connector is not installed correctly, the inverter may 

be damaged by moisture and dust. All warranty claims are invalid.

Ø

Ø

Danger

Warning

Note

The MID series inverter has two independent inputs, as shown below:

fig6

.

5

 

PV terminal

A

C

Note: MID 25KTL3-X model MPPt2 is 3 sets of PV input.

The selection of PV modules should pay attention to the following points:

The PV modules of each PV string are of the same specification.

The PV modules of each PV string are connected in series by the same number.

Ø

Ø

Ø

Ø

        Before  connecting  the  panel,  please  make  sure  that  the  DC  input 

polarity is correct, that is, the positive pole of the PV module is connected 

to the DC input terminal of the inverter marked “+”, and the negative pole 

is connected to the DC input terminal marked “-”.

The maximum DC input current and voltage of the inverter must not 

exceed the following limits:

Model

Single maximum input 

current

Maximum input voltage

MID 6-12KTL3-XL

25A

1100V

MID 10-22KTL3-X

25A

1100V

MID 25KTL3-X

25A/37.5A

1100V

Note

Connecting DC terminal:

Cables

Cables 

Positive

 

metal

 

terminal

Positive

 

connector

Negative

 

connector

Negative

 

metal

 

terminal

4~6mm²

4~6mm²

fig6

.

6 Quick installation instructions

Содержание MID 10KTL3-X

Страница 1: ...nzhen P R China No 28 Guangming Road Shiyan Street Bao an District Shenzhen P R China 86 755 2747 1942 www ginverter com www ginverter com T E W service ginverter com service ginverter com 86 755 2747...

Страница 2: ...2 1 Foreword 2 2 Applicable personnel 2 3 Product overview and features 2 4 Safety instructions 1 1 Validity 1 2 Target Group 1 3 Additional information 3 Product Description 4 Unpacking and Inspecti...

Страница 3: ...ubleshooting 7 Debugging 14 Specification 8 1 Normal mode 8 2 Failure mode 8 3 Shutdown mode 9 1 Boot display 9 2 OLED display wake up 9 3 Touch operation 11 1 Start the inverter 11 2 Shut down the in...

Страница 4: ...refully before using this product Any changes to this manual by Growatt New Energy will not be notified to the user 2 2 Applicable Personnel The inverter must be installed by a professional electricia...

Страница 5: ...V modules Otherwise in the sunlight the voltage at the component terminals is high which poses a personal danger Make sure that the input DC voltage does not exceed 550V under any circumstances Higher...

Страница 6: ...t operating state of the inverter red fault green normal operation Flashing red light warning Flashing green light Update program 3 2 Dimensions Size and weight Model Height H Width W Depth D Weight M...

Страница 7: ...nverter for a long time refer to the specifications in Chapter 12 for the weight of the inverter The installation location must match the size of the inverter Do not install the inverter on a building...

Страница 8: ...Installation Environment Make sure that the inverter is installed in a suitable place and is not allowed to be installed in a closed box fig5 4 Closed box In order to reduce the inverter load and ext...

Страница 9: ...h of the inverter is in the OFF state and that the AC side is open otherwise the high voltage of the inverter may be life threatening Each inverter must be independently installed with an AC circuit b...

Страница 10: ...er model Switch specification Inverter model Switch specification MID 6KTL3 XL 25A 127V MID 8KTL3 XL 32A 127V MID 10KTL3 XL 40A 127V MID 11KTL3 XL 40A 127V MID 12KTL3 XL 50A 127V MID 10KTL3 X 32A 230V...

Страница 11: ...PV ground please turn on the low frequency isolation transformer after the output is connected otherwise the inverter will be damaged If it is measured that there is a stable non zero DC voltage betw...

Страница 12: ...allation instructions 2 Push the threaded sleeve into the socket and tighten the waterproof gland fig6 9 Quick installation instructions Ka 3 Dock the client to the inverter plug until both are tightl...

Страница 13: ...real time When the inverter monitors any unexpected conditions such as system failure and inverter failure the fault information will be displayed on the display In the fault mode the inverter indica...

Страница 14: ...ic CT Off grid setting Enable Country Region VDE0126 Country Region VDE0126 Country Region G99 Country Region N4105 Country Region G98 Country Region Ireland Country Region EN50438 Country Region Belg...

Страница 15: ...er 2 Close the DC switch when the input PV voltage is higher than 250Vdc and the inverter will start automatically Start and Shut Down the Inverter 11 11 1 Start the inverter 11 2 Shut down the invert...

Страница 16: ...ew fan 5 Reinstall the fan mounting plate and inverter Troubleshooting 13 PV inverters sometimes do not work properly we recommend the following solutions to eliminate common faults The table below he...

Страница 17: ...anufacturer 13 2 Syetem error 13 2 1 Warning code Warning Code Fault Discription Suggestion Warning 300 No Utility 1 Please confirm grid is lost or not 2 If error message still exists contact manufact...

Страница 18: ...r 3 If error message still exists contact manufacturer Error Code Fault Discription Suggestion Error 300 AC V Outrange 1 Check grid voltage 2 If the error message still exists despite the grid voltage...

Страница 19: ...art inverter 2 If error message still exists contact manufacturer Error 414 EEPROM fault 1 Restart inverter 2 If error message still exists contact manufacturer Error 415 Internal power test fail PV P...

Страница 20: ...ctor 0 8Leading 0 8Lagging THDi 3 AC grid connection type 3W PE 3W N PE Efficiency Max efficiency 98 65 Euro eta 98 3 Specifications Model MID 6KTL3 XL MID 8KTL3 XL MID 10KTL3 XL MID 11KTL3 XL MID 12K...

Страница 21: ...0 8Leading 0 8Lagging THDi 3 AC grid connection type 3W N PE Efficiency Max efficiency 98 65 Euro eta 98 3 Specifications Model MID 10KTL3 X MID 12KTL3 X MID 15KTL3 X MID 17KTL3 X Protection devices D...

Страница 22: ...ng 0 8Lagging THDi 3 AC grid connection type 3W N PE Efficiency Max efficiency 98 65 Euro eta 98 3 Specifications Model MID 20KTL3 X MID 22KTL3 X MID 25KTL3 X Protection devices DC reverse polarity pr...

Страница 23: ...ing the defective equipment The cost of installing or reinstalling a faulty device should also be explicitly excluded from other related logistics and processing costs associated with warranty claims...

Отзывы: