7 Operation and Commissioning
After the battery is installed and wired, operate and commission it to check if the battery works properly.
!
CAUTION
When operating or commissioning the battery, please strictly follow the safety instruction below:
⁎
Technicians must go through technical training and obtain certificates in compliance with local laws and
regulations.
⁎ Please stand on dry insulating objects and do not wear metal objects such as watches, rings and necklaces
during operation.
⁎
Use insulating tools and wear protective devices.
⁎ Do not contact with two charged positions with a potential difference.
⁎ Hang a prohibition sign that stops people from turning on the breakers on the power distribution equipment
if needed.
⁎
If any abnormality is detected, immediately power off the battery. Proceed again only after causes are
confirmed.
7.1 Power on Battery
Power on the battery in either of the following ways:
Keep the inverter on and turn on battery breaker(s). The battery(s) is activated after detecting a voltage
from the inverter.
Alternatively, hold the
Power
button on battery for over one second.
If LED1 to LED6 are lit on one by one and SOC indicators on all batteries indicate SOC correctly,
batteries are powered on successfully.
After the battery(s) is powered on, observe it for 15 minutes to confirm that it can charge and discharge
properly.
7.2
Power off Battery
Hold the
Power
button of the single battery or one battery in parallel connection for over two seconds.
LED1 to LED4 and LED6 flicker for 2 times, and the battery(s) turns off.
!
CAUTION
⁎ If a battery encounters undervoltage protection, it powers off five minutes later.
⁎ If a battery encounters a communication abnormality or permanent fault, it powers off 15 minutes later.