background image

D100-68-00

7

I56-1525-000

Figure 11. Testing detector alarm:

A78-2325-00

[6.2.2.2] RTS451A/RTS451KEYA Remote Test Station
The RTS451A/RTS451KEYA Remote Test Station facilitates
test of the alarm capability of the duct smoke detector as in-
dicated in the RTS451A/RTS451KEYA manual. The
DH100ACDCA duct smoke detector can be reset by the
RTS451A/RTS451KEYA. If a system control panel is used,
the panel itself may also require testing.

To install the RTS451A/RTS451KEYA, connect the device as
shown in Figure 9; wire runs must be limited to 25 ohms or
less per interconnecting wire.

[6.2.3] Sensitivity Tests
[6.2.3.1] MOD400 or MOD400R Test
After verification of alarm capability, use the MOD400R test
module with a voltmeter to check detector sensitivity as indi-
cated in the test module’s manual. The housing cover must
be removed to perform this test.

If test module readings indicate that the detector head is out-
side of the acceptable range that is printed on the label of the

detector, the detector chamber requires cleaning per Section
[7] of this manual.

[7] Detector Cleaning Procedures
Notify the proper authorities that the smoke detector system is
undergoing maintenance, and that the system will temporarily
be out of service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms and possible dis-
patch of the fire department.

[7.1] Air Filters
1. 
Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with new

filters. If they are not heavily coated, use a vacuum cleaner
or compressed air nozzle to remove dust, then reinstall the
filters.

[7.2] Photo Detector Boards
1. 
Remove the screen by gently grasping on each side and

pulling straight off.

2. Lift the photo chamber in the same fashion. Vacuum the

screen and cover. Use clean, compressed air to loosen
and blow out any remaining debris. Replacement screens
(S08-39-01) are available.

3. Vacuum photo chamber, then use clean compressed air to

blow area clean.

4. Replace the chamber by pressing it onto the base.    Press

the screen into place. It should fit tightly on the chamber.

[7.3] Ion Detector Boards
1. 
Brush or vacuum inside area of cover. Chamber may then

be blown out using clean, compressed air.

2. Vacuum sensing chamber before using clean, com-

pressed air to loosen and blow out any remaining debris.

[8.0] Board Replacement

[8.1] Detector Board Replacement
1.

Remove the two detector board mounting screws.

2.

Pull gently on the board to remove it.

ALARM SIGNAL (+)

AUX POWER (Ð)

15

20

(+)

(Ð)

DUCT DETECTOR
DH100ACDCA

PA400 (OPTIONAL)
AUDIBLE ALERT

ALARM SIGNAL (+)

AUX POWER (Ð)

15

20

(+)

(Ð)

DUCT DETECTOR
DH100ACDCA

RA400ZA (OPTIONAL)
REMOTE (LED)
ANNUNCIATOR

RED

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

APA451

PA400

RA400ZA

RTS451/RTS451KEY

STANDBY

12.5mA Max.

0mA

0mA

12mA Max.

ALARM

30mA Max.

15mA Max.

10mA Max.

7.5mA Max.

When a unit is powered at the 120VAC or 220/240VAC input, 
any combination of accessories may be used such that the given 
accessory loads are:

60mA or less in the standby state,
110mA or less in the alarm state.

Figure 10. Wiring diagrams for optional accessories (see page 6 for APA451 wiring diagram):

A78-2354-05

Содержание DH100ACDCPA

Страница 1: ...el interface alarm initiation HVAC control and other auxiliary functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detec For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm oc curs A ...

Страница 2: ...s of 500 to 4000 feet per minute Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these pa rameters If necessary use a velocity meter to check the air velocity in the duct 5 2 Drill The Mounting Holes Remove the paper backing from the mounting template sup plied Affix the template to the duct at the desired mounting location Make sure the templat...

Страница 3: ...dth All other lengths must be purchased sepa rately Order the correct length as specified in Table 1 for width of the duct where it will be installed The exhaust tube is molded onto the base of the duct housing and the A2440 00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not ex tend at least 2 inches into the duct The inlet tube is always i...

Страница 4: ...mation Replacement filters can be ordered from Sys tem Sensor 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 Exhaust tube intake tube filter P N F36 09 00 5 6 Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used to connect smoke detec...

Страница 5: ...filters should be replaced because only a high percentage of con tamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the fil ters In no case should the pressure differential fall below 0 03 inches of water 6 2 Standby Alarm And Sensitivity Tests 6 2 1 Standby And Trouble Sta...

Страница 6: ...FORMATION FOR WIRING OF AUXILIARY DEVICES REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER NOTE THE SUPERVISORY RELAY NOW PROVIDES A FORM C CONTACT FOR CUSTOMIZED APPLICATIONS FOR STANDARD APPLICATIONS ONLY THE NO CONTACT IS USED POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTO...

Страница 7: ...ed with dirt replace them with new filters If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 7 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining ...

Страница 8: ...cement 1 Disconnect wiring from the terminal block 2 Remove the two power board mounting screws 3 Pull gently on the board to remove it 4 To replace the board align the board mounting features holes and the interconnect terminals Push the board into place 5 Secure board with the two mounting screws 6 Re connect wiring to terminal block Power Supply Voltage 20 29 VDC 24 VAC 50 60 Hz 120 VAC 50 60 H...

Отзывы: