   Installation Instructions 

Introduction

The Ultra Low Pressure Transmitter is used to measure differential 

pressure in the range of 0.125 to 1"wc (30 to 250 Pa). It combines 

precision high sensitivity silicon sensing capabilities and the latest ASIC 

technology to substantially reduce offset errors due to changes in 

temperature, stability to warmup, long term instability and position 

sensitivity. It is ideal for monitoring pressure for air or other clean inert 

gas. It features several field selectable uni- or bi-directional pressure 

ranges and output signal types for the most flexible application. The 

device has an on-board auto-zero function as well as a connection for 

remote zeroing. Options include an LCD to display the pressure value 

and an alarm relay with a variable trip point.

Before Installation

Read these instructions carefully before installing and commission-

ing the Pressure Transmitter. Failure to follow these instructions 

may result in product damage. 

Do not use in an explosive or hazard-

ous environment, with combustible or flammable gases, as a safety or 

emergency stop device or in any other application where failure of the 

product could result in personal injury. Take electrostatic discharge 

precautions during installation and do not exceed the device ratings.

Figure 1

Mounting

Mount the device using the four holes on the base of the unit. Leave 

enough space around the unit to connect the pressure tubing and 

avoid locations with severe vibrations, excessive moisture or rapid 

temperature changes. It should be mounted on a vertical surface with 

the pressure ports on the bottom and the cable entrance on the right. 

The enclosure has a standard ½” conduit opening and may be installed 

with either conduit and a conduit coupler or a cable gland type fitting.  

Open the hinged cover by releasing the latch and connect the device 

according to the wiring instructions. After wiring and setup are 

complete, close and latch the cover. The cover may be secured with 

two self-tapping screws in the holes provided.

 as shown in figure 1.  

The enclosure has a hinged cover with latch.  Open cover by pulling 

slightly on the latch on the right side of the enclosure. At the same 

time pulling on the cover, as illustrated in figure 2.

Feed conduit/cable gland fitting through the provided hole in side of 

enclosure and secure with a lock nut as show in figure 3. It is recom-

mended that weatherproof conduit or cable gland fittings be used.

Make wiring connections as per the “Wiring” illustrations on Page 3.

Swing door closed until securely latched.  For added security, 2 screws 

are provided that may be installed in the integrated screw tabs.  See 

figure 4.

Figure 2

Figure 4

Figure 3

Conduit

Ultra Low Pressure Transmitter

ULP

Greystone Energy Systems, Inc.  150 English Drive,   Moncton, NB E1E 4G7  Canada  Tel: +1-506-853-3057  Tollfree (North America): +1-800-561-5611 Fax: +1-506-853-6014

Email: [email protected]    Web: www.greystoneenergy.com

Содержание ULP1

Страница 1: ...it Leave enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations excessive moisture or rapid temperature changes It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the right The enclosure has a standard conduit opening and may be installed with either conduit and a conduit coupler or a cable glan...

Страница 2: ...dings may result See figure 7 The RELAY output is a normally open dry contact This signal can be used to directly control an alarm ventilation fan or may be connected to a digital input of the BAS for status monitoring Ensure any loads connected to the relay is within the relay rating in the Specification section See figure 8 The remote zero feature may be used by wiring a dry contact relay only d...

Страница 3: ...less than the Low pressure For bipolar ranges the output pressure can be calculated as follows 4 20 mA Pressure Output current 4 mA 16 mA x 2 x Range Offset 0 5 Vdc Pressure Output voltage 5 V x 2 x Range Offset 0 10 Vdc Pressure Output voltage 10 V x 2 x Range Offset Wiring Instruction con t Figure 7 Wiring all output signals and 24 Vdc power from controller Wiring for all output signals and exte...

Страница 4: ...e then the relay contacts will close When the input pressure decreases below the setpoint for the delay time then the relay contacts will open again The alarm on off delay time can be set to either LO Delay 10 seconds or HI Delay 60 seconds via a DIP switch The operation described above is for the default Normal Alarm A DIP switch can be set to Reverse Alarm which will cause the alarm operation to...

Отзывы: