background image

Power Up Instruction

Before turning on the power, verify all wiring to ensure that it complies 

with one of the included wiring diagrams and verify that the output 

signal type is correctly selected on the jumpers. Also, review the 

specifications to ensure the power supply is correct and that the 

pressure is within the correct range. The product should be allowed to 

warm-up for several minutes before attempting to verify accuracy. 

Allow the device to operate for 20 minutes before any calibration is 

performed.

Normal Operation

If the unit is set to a unipolar range such as 0-1 "wc, then the pressure applied to the High port must be higher than the 

pressure applied to the Low port. In this case, if the Low port is left open to ambient pressure and the High port is used to 

measure a positive pressure, then the output pressure can be calculated as follows:

 

4-20 mA  

Pressure  =  [(Output current – 4 mA) / 16 mA]  x  Range

 

0-5 Vdc   

Pressure  =  (Output voltage / 5 V)  x  Range

 

0-10 Vdc  

Pressure  =  (Output voltage / 10 V)  x  Range

In the case of 0-1 "wc, 4 mA or 0 V = 0 "wc and 20 mA or 5 V or 10 V = 1 "wc. Since the transmitter is linear, 0.5 "wc would be 12 

mA or 2.5 V or 5 V. If the positive pressure connection is reversed then the transmitter will always output 4 mA or 0 V.

For a bipolar range such as

 

±

 

1 "wc, the pressure applied to the High port should be higher than pressure applied to the Low 

port for a positive output response. In this case, differential pressure can be measured using both ports. If the High port has a 

positive pressure with respect to the Low port, then the output indicates a positive pressure. Negative pressure is indicated if 

the High pressure is less than the Low pressure. For bipolar ranges, the output pressure can be calculated as follows:

 

4-20 mA  

Pressure  =  [(Output current – 4 mA) / 16 mA]  x  2  x  Range – Offset

 

0-5 Vdc   

Pressure  =  (Output voltage / 5 V)  x  2  x  Range – Offset

 

0-10 Vdc  

Pressure  =  (Output voltage / 10 V)  x  2  x  Range – Offset

Wiring Instruction (con’t)

Figure 7

Wiring all output signals and 

24 Vdc power from controller

Wiring for all output signals and 

external 24 Vac power transformer

Wiring for all output signals and 

external 24 Vdc power supply

24 Vdc Power Supply

Pneumatic Connections

The two pressure ports on the enclosure are labeled High and Low. The 

output signal reads a positive value when the port pressure is higher 

on the High port than the Low port so ensure these ports are connect-

ed correctly. Use 1/8" to 3/16" ID flexible tubing for the pressure 

connections. A flexible silicone tube is recommended. Arrange the 

tubing to minimize stress on the connections and ensure there are no 

kinks in the tubing. For most accurate measurements, do not leave the 

Low port open to the atmosphere, run a return line from the Low port 

to the vicinity of the point being measured. See figure 10.

Figure 10

High Port

Low Port

Operation can be verified by measuring the output signal. For voltage output configuration, measure the voltage between 

the PRESS OUT and COMMON terminals. The voltmeter should read between 0-5 or 0-10 Vdc depending on the output range 

selected on the DIP switch. For current output configuration, insert a mA meter in series with the PRESS OUT terminal and it 

should read between 4 and 20 mA.

1/8” to 3/16” ID 

flexible tubing

Figure 8

Relay Output

Remote Zero 

Figure 9

Greystone Energy Systems, Inc.  150 English Drive,   Moncton, NB  E1E 4G7  Canada  Tel: +1-506-853-3057  Tollfree (North America): +1-800-561-5611  Fax: +1-506-853-6014

Email: [email protected]    Web: www.greystoneenergy.com

Содержание ULP1

Страница 1: ...it Leave enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations excessive moisture or rapid temperature changes It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the right The enclosure has a standard conduit opening and may be installed with either conduit and a conduit coupler or a cable glan...

Страница 2: ...dings may result See figure 7 The RELAY output is a normally open dry contact This signal can be used to directly control an alarm ventilation fan or may be connected to a digital input of the BAS for status monitoring Ensure any loads connected to the relay is within the relay rating in the Specification section See figure 8 The remote zero feature may be used by wiring a dry contact relay only d...

Страница 3: ...less than the Low pressure For bipolar ranges the output pressure can be calculated as follows 4 20 mA Pressure Output current 4 mA 16 mA x 2 x Range Offset 0 5 Vdc Pressure Output voltage 5 V x 2 x Range Offset 0 10 Vdc Pressure Output voltage 10 V x 2 x Range Offset Wiring Instruction con t Figure 7 Wiring all output signals and 24 Vdc power from controller Wiring for all output signals and exte...

Страница 4: ...e then the relay contacts will close When the input pressure decreases below the setpoint for the delay time then the relay contacts will open again The alarm on off delay time can be set to either LO Delay 10 seconds or HI Delay 60 seconds via a DIP switch The operation described above is for the default Normal Alarm A DIP switch can be set to Reverse Alarm which will cause the alarm operation to...

Отзывы: