background image

Page  1

INTRODUCTION

The continental series is an attractive, low profile 

enclosure that incorporates a precision temperature 

sensor used to monitor room temperatures. Additional 

options are available that include set-point adjustment, 

manual override, fan speed, handset communication 

port, and an LCD.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the device. Failure to follow these 

instructions may result in product damage. Do not use in an explosive or hazardous environment, with 

combustible for flammable gases, as a safety or emergency stop device or in any other application where 

failure of the product could result in personal injury. Take electrostatic discharge precautions during 

installation. 

Do not exceed the device ratings.

MOUNTING

The temperature sensor mounts directly on a wall or onto an electrical wall box. For the most accurate 

results, the unit should be mounted on an inside wall to a wall box five feet from the floor. Do not mount 

the sensor near doors, opening windows, supply air diffusers, or other known air disturbances. Avoid areas 

where the sensor is exposed to vibrations or rapid temperature changes.

The cover is hooked to the base at the top edge and must be removed from the bottom edge first. Use 

a small Phillips screwdriver to loosen the security screw as shown in Figure 1. (Complete removal is not 

required). Use a screw driver to carefully pry each bottom corner if necessary. Tip the cover away from the 

base and sit it aside as shown in Figure 2.

SENSOR ONLY

Feed at least 6 inches of wire through the wall and out of the junction box and feed connection wires 

through the center hole on the backplate. Secure the backplate to the wall or electrical box with suitable 

screws (not supplied) as shown in Figure 3. The mounting holes in the backplate allow for up, down, and 

side to side movement to compensate for unlevel electrical box installation.

Retrieve the sensor with clip. Turn the clip over and remove the 

backing from the clip to expose the adhesive back. Stick the 

clip on a smooth surface of the backplate. See Figure 4.

Make wire connections as per the Wiring Illustrations on Page 2. 

Re-install the decorative cover by placing the top of the cover 

into the cover holder on the top of the backplate and snapping 

the bottom into place as shown in Figure 7. Tighten security 

screw with a screwdriver.

Figure 1

Figure 3

Figure 2

Figure 4

IN-GE-TSRCXXX-01 04/20

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Room Temperature Sensor

TSRC Series - Installation Instructions

Содержание TSRC Series

Страница 1: ... at the top edge and must be removed from the bottom edge first Use a small Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal is not required Use a screw driver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figure 2 SENSOR ONLY Feed at least 6 inches of wire through the wall and out of the juncti...

Страница 2: ...s mounted on the wall For added protection place the PCB in the supplied anti static bag Mount the base by screwing it to an electrical box or directly to the wall as shown in Figure 5 After the base is screwed to an electrical box or the wall using the appropriate holes remove the PCB from the anti static bag feed connection wires through center hole and place the top of the PCB into the PCB hold...

Страница 3: ... LED The LED is typically used as indication as when manual override has been selected It is available on the LED and LED terminals and requires 5 Vdc to power The LED option is not available when LCD installed FAN SPEED SWITCH The 5 position speed fan speed has a resistance output signal on the FAN and FAN terminals and has different resistances for each position 5 positions Auto Off Low Mid High...

Страница 4: ...ot as resistive output 20 to 20K Ω Custom Spans Available 1K 2K 5K 10K or 20K Ω OCCUPIED INPUT Signal Type Digital input 0 5 Vdc active low Action Causes OCC segment to light on LCD LED INPUT Signal Type Active high low or 2 wire 5 V current limit standard LED Colors Red Green or Yellow Power Supply 5 Vdc standard 10 Vdc or 24 Vdc optional LCD DISPLAY Power Supply 12 24 Vdc 24 Vac 10 Consumption 2...