background image

POWER BOARD

EXHAUST TUBE

METAL SAMPLING TUBE

(sold separately)

POWER BOARD

MODULE COVER

SENSOR HEAD

SENSOR MODULE

COVER

MAGNET TEST

SMOKE TEST PORT

[3] GENERAL DESCRIPTION

Smoke introduced into an air duct system will be distributed throughout the 
entire building. Smoke detectors designed for use in air duct systems are used to 
sense the presence of smoke in the duct. 

Model DSD240 Duct Smoke Detector utilizes 4-wire photoelectric technology 
for the detection of smoke. This detection method, when combined with an 
efficient housing, samples air passing through the duct allowing detection of 
a developing hazardous condition. When sufficient smoke is sensed, an alarm 
signal is initiated and appropriate action can be taken to shut off fans, blowers, 
change over air handling systems, etc. These actions can facilitate the manage-
ment of toxic smoke and fire gases throughout the areas served by the duct 
system.

The DSD240 detector is designed to operate on 24 VDC/VAC or 240 VAC. Alarm 
and supervisory relay contacts are available for control panel interface (alarm 
initiation), HVAC control, and other auxiliary functions. The fire alarm control 
panel is NOT notified when sensor maintenance its required. Auxiliary relays 
are provided for fan shut down. Detector interconnection provides signaling of 
up to 30 other detectors in the loop for multiple fan shut down. These detectors 
are not designed for 2-wire applications.

[3.1] DETECTOR FEATURE SET

-Utilizes 2D51 plug-in head

-Cover missing signal

-Sampling tubes install from front or rear of detector

-Compatible with existing accessories

[4] CONTENTS OF THE DUCT SMOKE DETECTOR KIT

1.  Sensor/power board assembly and cover(s)
2.  Three #10 sheet metal screws for mounting
3.  Drilling template
4.  One sampling tube end cap
5.  One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must be 
the correct length for the width of the duct where it will be installed. See Table 1 
on page 3 to determine the inlet tube required for different duct widths. 

[5] DETECTOR INSTALLATION

[5.1] VERIFY AIR FLOW DIRECTION AND VELOCITY

Model DSD240 detectors are designed to be used in air handling systems with 
air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12 feet 
can be accommodated. Be sure to check engineering specifications to ensure 
that the air velocity in the duct falls within these parameters. If necessary, use a 
velocity meter (anemometer) to check the air velocity in the duct.

[5.2] DETERMINE MOUNTING LOCATION AND CONFIGURATION

On ducts wider than 18 inches it is recommended that the detector be mounted 
downstream of a bend, obstruction in the duct, or the supply or return air inlet.

Exception:

 Installation of duct detectors can be on or within a commercial 

packaged rooftop heating and air-conditioning system, fire/smoke dampers and 
economizers. They may be mounted in either the supply and/or return air sec-
tion as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted 
in a side-by-side “rectangular” configuration or a top-over-bottom “square” 
configuration as shown in 

Figure 2. I

f mounting in the square configuration, 

remove the rear attachment pin, rotate the unit at the hinge, and replace the 
pin into the new attachment hole as shown in 

Figure 2

. Do NOT remove the 

hinge screw during this process. Final installation approval shall be based upon 
passing section 7.2.

FIGURE 2:

REMOVE PIN AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE PIN TO

SECURE DETECTOR

IN PLACE.

H0638-00

[5.3] DRILL THE MOUNTING HOLES

Remove the paper backing from the mounting template supplied. Affix the tem-
plate to the duct at the desired mounting location. Make sure the template lies 
flat and smooth on the duct. 

[5.3.1] FOR RECTANGULAR SIDE-BY-SIDE MOUNTING CONFIGURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for the 
rectangular configuration mounting tabs as shown on mounting template. Drill 
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using a 
1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 inch drill 

at target “B” centers.

[5.3.2] FOR SQUARE TOP-OVER-BOTTOM MOUNTING CONFIGURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for 
the square configuration mounting tabs as shown on mounting template. Drill 
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using a 
1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 inch drill 

at target “C” centers. If desired, drill an additional .156 inch hole at the location 
of one of the mounting tabs on the lower housing.

[5.4] SECURE THE DUCT DETECTOR TO THE DUCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION:

 Do not overtighten the screws.

[2] FIGURE 1. EXPLODED VIEW OF DUCT SMOKE DETECTOR COMPONENTS:

H0637-00

IN-GE-DSD240-01-01 2 

I56-9200-001 

 

 5/6/2019

Содержание DSD240

Страница 1: ...l Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC resistive 10A 250 VAC resistive 1 2 HP 240 VAC 1 4 HP 120 VAC NOTE Alarm auxiliary contac...

Страница 2: ...hese parameters If necessary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop heat...

Страница 3: ...y holes in the protruding sec tion of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct...

Страница 4: ...ODEL 607 01 15 TO 36 VDC SUPPLY 1000 OHM 5 1 WATT RESISTOR VOLT METER FLUKE MODEL 87 OR EQUIVALENT FIGURE 5 PROCEDURE FOR VERIFYING AIR FLOW LESS THAN 500 FPM H0163 01 FIGURE 6 SYSTEM WIRING DIAGRAM FOR 4 WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUT...

Страница 5: ...y 5 seconds as depicted in Table 3 on page 7 The maintenance condition indicates that the sensor is operating outside its original factory preset sensitivity and shall be cleaned or replaced Replacement 2D51 sensors are available as a separate item See Sec tion 9 for reference This is a valid UL test 11 4 DETECTOR TESTING AND MAINTENANCE PROCEDURES Notify the proper authorities that the smoke dete...

Страница 6: ...and then gently pushing it until it locks into place 8 Reinstall the detector FIGURE 9 DETECTOR SENSOR EXPLODED VIEW SENSOR COVER SENSING CHAMBER COVER AND SCREEN SENSOR CHAMBER COVER REMOVAL TABS C1009 00 12 2 REINSTALLATION 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check Section 11 2 4 Notify the proper authorities testing has been completed and the smoke ...

Страница 7: ...ern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Terminals 4 and 5 ar...

Страница 8: ...send defective units post age prepaid to 150 English Drive Moncton N B Canada E1E 4G7 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreason able use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for an...

Отзывы: