SPECIFICATIONS

Power Supply ....................................24 Vac/dc ± 10% (non-isolated half-wave rectified)

Consumption ....................................75 mA max @ 24 Vdc

Output Signal ....................................4-20 mA sourcing, 0-5/0-10 Vdc (switch selectable)

Output Drive .....................................

Current:

 500 ohms max

 

Voltage:

 10K ohms min

Protection Circuitry .........................Reverse voltage protected, transient protected

LCD .......................................................35 x 15 mm (1.4 x 0.6"), 2-line x 8-character

Accuracy .............................................± 1% F.S. of selected range (range 4 is ±2% F.S.) @ 22°C (72°F) 

 

including hysteresis, non-linearity and repeatability

Stability ...............................................± 0.25% FS typical (1 year)

Pressure Ranges ...............................4 per model (menu selectable)

Media Compatibility .......................17-4 PH stainless steel

Proof Pressure ...................................2X highest range per model

Burst Pressure ...................................20X highest range per model

Maximum Line Pressure ................= highest model range

Pressure Cycles .................................> 100 million

Surge Damping ................................1-60 seconds averaging (menu selectable)

Zero Adjust ........................................Push-button and remote input

Sensor Operating Range ...............-40 to 105°C (-40 to 221°F)

Operating Environment ................0 to 50°C (32 to 122°F), 10 to 90 %RH non-condensing

Pressure Connection ......................1/4" NPT male

Sensor Housing ................................IP67

Remote Sensor Cable .....................

S:

 FT-6 plenum rated

 

A:

 Armored Flexible S/S

Wiring Connection ..........................14-22 AWG screw terminal block

Enclosure ............................................Polycarbonate, UL94-V0, IP65 (NEMA 4X)

 

F style includes thread adapter (1/2" NPT to M16) and cable gland fitting

Dimensions ........................................112.5 W x 116.5 H x 53.7 D mm

 

(4.43" x 4.59" x 2.11")

Weight .................................................650g (22.9 oz) - Including remote cables and sensors

Country of Origin .............................Canada

DIMENSIONS

 

116.5 mm

4.585"

53.7 mm

2.115"

0.5" NPT

 

82.55 mm

3.25"

68 mm

2.67"

Various lengths available

See ordering grid

  

  

  

112.5 mm

4.43"

99.7 mm

3.925"

IN-GE-DPXXX-02-02      11/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание DP Series

Страница 1: ...ace using the two integrated mounting holes The remote sensor cable connection should be located on the bottom of the enclosure The two mounting holes will facilitate a 10 size screw not supplied See Figure 1 Ensure there is enough space around the unit to make the electrical connections and that it is within an acceptable distance for the length of remote sensor cables Avoid locations with severe...

Страница 2: ...le boot and pushing firmly onto sensor See Figure 9 Repeat for the Low pressure sensor Low Pressure Sensor Shut Off Valve Direction of Water Flow Direction of Water Flow High Pressure Sensor Shut Off Valve Pump Supply Water Line Return Water Line Figure 6 Figure 7 Figure 8 Figure 9 CONFIGURATION Most configuration is done using User Menu setting with LCD and push buttons on PCB See User Menu secti...

Страница 3: ...erminal Check the controller Analog Input to determine the proper connection before applying power If using the Zero function connect the Remote Zero Switch between the ZERO and COM terminals Figure 11 Wiring for all output signals and 24 Vac Vdc power from controller Wiring if using the remote zero input WARNING Do NOT apply voltage to Zero terminal Wiring for all output signals and external 24 V...

Страница 4: ...nd advance to next menu item 1 OUTPUT P Range 500 PSI The pressure range defaults to the largest range 1 of the device Use UP or DOWN to step through the four available ranges specific to the model Available options are shown below in Figure 12 2 PRESSURE RANGE Model 1 2 3 4 01 50 PSI 25 PSI 10 PSI 5 PSI 02 100 PSI 50 PSI 20 PSI 10 PSI 03 250 PSI 125 PSI 50 PSI 25 PSI 04 500 PSI 250 PSI 100 PSI 50...

Страница 5: ...mal mode the device also monitors the ZERO UP DOWN and MENU keys and takes appropriate action The keys are used to access the User Menu The device also monitors the Volt mA jumper to determine the appropriate output scaling The voltage span may be set via the User Menu to either 0 5 Vdc or 0 10 Vdc A sensor auto zero can be initiated by pressing and holding the internal ZERO switch for at least 3 ...

Страница 6: ...Cycles 100 million Surge Damping 1 60 seconds averaging menu selectable Zero Adjust Push button and remote input Sensor Operating Range 40 to 105 C 40 to 221 F Operating Environment 0 to 50 C 32 to 122 F 10 to 90 RH non condensing Pressure Connection 1 4 NPT male Sensor Housing IP67 Remote Sensor Cable S FT 6 plenum rated A Armored Flexible S S Wiring Connection 14 22 AWG screw terminal block Encl...

Отзывы: