Page  3

WIRING

•  Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical 

shock or equipment damage.

•  Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit 

with wiring used to supply inductive loads such as motors. Make all connections in accordance with 

national and local codes.

•  Pull at least six inches of wire into the enclosure, then complete the wiring connection according to the 

wiring diagram for the applicable power supply and output signal type.

•  Connect the plus DC or the AC voltage hot side to the PWR terminal. For voltage output or AC power, the 

supply Common is connected to the COM terminal. 

DO NOT connect power to the OUT terminals as 

the device will be damaged.

 It has half-wave power supply so the supply Common is the same as the 

signal Common. See Figure 11.

•  The analog output is available on the OUT terminal. Check the controller Analog Input to determine the 

proper connection before applying power.

•  If using the Zero function, connect the Remote Zero Switch between the ZERO and COM terminals.

Figure 11

Wiring for all output signals and 24 Vac/Vdc 

power from controller

Wiring if using the remote zero input

WARNING: Do NOT apply voltage to Zero terminal

Wiring for all output signals and external 24 Vac 

power transformer or 24 Vdc power supply

START-UP

Upon applying power to the device, it will enter the start-up mode. The LCD will display the current 

operating settings for 2 seconds each.

Version

1.00

1. SOFTWARE VERSION NUMBER

2. MODEL PRESSURE RANGE

P Range

50PSI

3. THE OUTPUT TYPE

Output

4-20mA

At the end of start-up mode the device will enter normal mode displaying pressure read from sensors.

0.0

PSI

Remote Zero 

Switch

COM

PWR

OUT

ZERO

External Power Supply

Controller

COM

PWR

OUT

Controller

COM

PWR

OUT

ZERO

External Power Supply

COM

PWR

OUT

ZERO

ZERO/UP

DOWN

MENU

mA

VOL

T

IN-GE-DPXXX-02-02      11/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание DP Series

Страница 1: ...ace using the two integrated mounting holes The remote sensor cable connection should be located on the bottom of the enclosure The two mounting holes will facilitate a 10 size screw not supplied See Figure 1 Ensure there is enough space around the unit to make the electrical connections and that it is within an acceptable distance for the length of remote sensor cables Avoid locations with severe...

Страница 2: ...le boot and pushing firmly onto sensor See Figure 9 Repeat for the Low pressure sensor Low Pressure Sensor Shut Off Valve Direction of Water Flow Direction of Water Flow High Pressure Sensor Shut Off Valve Pump Supply Water Line Return Water Line Figure 6 Figure 7 Figure 8 Figure 9 CONFIGURATION Most configuration is done using User Menu setting with LCD and push buttons on PCB See User Menu secti...

Страница 3: ...erminal Check the controller Analog Input to determine the proper connection before applying power If using the Zero function connect the Remote Zero Switch between the ZERO and COM terminals Figure 11 Wiring for all output signals and 24 Vac Vdc power from controller Wiring if using the remote zero input WARNING Do NOT apply voltage to Zero terminal Wiring for all output signals and external 24 V...

Страница 4: ...nd advance to next menu item 1 OUTPUT P Range 500 PSI The pressure range defaults to the largest range 1 of the device Use UP or DOWN to step through the four available ranges specific to the model Available options are shown below in Figure 12 2 PRESSURE RANGE Model 1 2 3 4 01 50 PSI 25 PSI 10 PSI 5 PSI 02 100 PSI 50 PSI 20 PSI 10 PSI 03 250 PSI 125 PSI 50 PSI 25 PSI 04 500 PSI 250 PSI 100 PSI 50...

Страница 5: ...mal mode the device also monitors the ZERO UP DOWN and MENU keys and takes appropriate action The keys are used to access the User Menu The device also monitors the Volt mA jumper to determine the appropriate output scaling The voltage span may be set via the User Menu to either 0 5 Vdc or 0 10 Vdc A sensor auto zero can be initiated by pressing and holding the internal ZERO switch for at least 3 ...

Страница 6: ...Cycles 100 million Surge Damping 1 60 seconds averaging menu selectable Zero Adjust Push button and remote input Sensor Operating Range 40 to 105 C 40 to 221 F Operating Environment 0 to 50 C 32 to 122 F 10 to 90 RH non condensing Pressure Connection 1 4 NPT male Sensor Housing IP67 Remote Sensor Cable S FT 6 plenum rated A Armored Flexible S S Wiring Connection 14 22 AWG screw terminal block Encl...

Отзывы: