background image

Page  4

P Scale

0 - Max

The default pressure scale is unidirectional 0 to full-scale (ex: 0 - 500 PSI). Use <UP> 

or <DOWN> to toggle the setting to a bi-directional scale (ex: ± 500 PSI). The setting 

changes from "0 - Max" to "+/- Max.

<MENU> 

Press to save and advance to next menu item

3. PRESSURE SCALE

USER MENU

The User Menu can be accessed by pressing the <MENU> key at any time after the start-up mode. Note 

that the <ZERO> key function changes to an <UP> key function when a menu is active.

The system suspends operation when in the menu and holds the last pressure value as the output value. 

If the User Menu is not active for 5 minutes (no key press), then the menu will exit and the device returns 

to normal operation.

The User Menu operation and parameters are explained below.

Output

0-5 Vdc

This item only appears if the PCB jumper is in the VOLT position. Use <UP> or 

<DOWN> to set the output signal type to 0-5 or 0-10 Vdc. The factory default is 0-5 

Vdc.

<MENU> 

Press to save and advance to next menu item

1. OUTPUT

P. Range

500 PSI

The pressure range defaults to the largest range (1) of the device. Use <UP> or

 <DOWN> to step through the four available ranges specific to the model. Available 

options are shown below in Figure 12:

2. PRESSURE RANGE

Model

1

2

3

4

01

50 PSI

25 PSI

10 PSI

5 PSI

02

100 PSI

50 PSI

20 PSI

10 PSI

03

250 PSI

125 PSI

50 PSI

25 PSI

04

500 PSI

250 PSI

100 PSI

50 PSI

05

5.0 Bar

2.5 Bar

1.0 Bar

0.5 Bar

06

7.0 Bar

3.5 Bar

1.4 Bar

0.7 Bar

07

10 Bar

5 Bar

2 Bar

1 Bar

08

35 Bar

17.5 Bar

7 Bar

3.5 Bar

09

500 kPa

250 kPa

100 kPa

50 kPa

10

700 kPa

350 kPa

140 kPa

70 kPa

11

1000 kPa

500 kPa

200 kPa

100 kPa

12

3500 kPa

1750 kPa

700 kPa

350 kPa

PRESSURE RANGE

<MENU> 

Press to save and advance to next menu item

Damping

4 sec

The pressure averaging time for surge damping defaults to 4 seconds. This can be 

changed from 1 to 60 seconds using <UP> or <DOWN>.

<MENU> 

Press to save and advance to next menu item

4. DAMPING

Figure 12

<MENU> 

Press and release the <MENU> key to enter the User Menu

IN-GE-DPXXX-02-02      11/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание DP Series

Страница 1: ...ace using the two integrated mounting holes The remote sensor cable connection should be located on the bottom of the enclosure The two mounting holes will facilitate a 10 size screw not supplied See Figure 1 Ensure there is enough space around the unit to make the electrical connections and that it is within an acceptable distance for the length of remote sensor cables Avoid locations with severe...

Страница 2: ...le boot and pushing firmly onto sensor See Figure 9 Repeat for the Low pressure sensor Low Pressure Sensor Shut Off Valve Direction of Water Flow Direction of Water Flow High Pressure Sensor Shut Off Valve Pump Supply Water Line Return Water Line Figure 6 Figure 7 Figure 8 Figure 9 CONFIGURATION Most configuration is done using User Menu setting with LCD and push buttons on PCB See User Menu secti...

Страница 3: ...erminal Check the controller Analog Input to determine the proper connection before applying power If using the Zero function connect the Remote Zero Switch between the ZERO and COM terminals Figure 11 Wiring for all output signals and 24 Vac Vdc power from controller Wiring if using the remote zero input WARNING Do NOT apply voltage to Zero terminal Wiring for all output signals and external 24 V...

Страница 4: ...nd advance to next menu item 1 OUTPUT P Range 500 PSI The pressure range defaults to the largest range 1 of the device Use UP or DOWN to step through the four available ranges specific to the model Available options are shown below in Figure 12 2 PRESSURE RANGE Model 1 2 3 4 01 50 PSI 25 PSI 10 PSI 5 PSI 02 100 PSI 50 PSI 20 PSI 10 PSI 03 250 PSI 125 PSI 50 PSI 25 PSI 04 500 PSI 250 PSI 100 PSI 50...

Страница 5: ...mal mode the device also monitors the ZERO UP DOWN and MENU keys and takes appropriate action The keys are used to access the User Menu The device also monitors the Volt mA jumper to determine the appropriate output scaling The voltage span may be set via the User Menu to either 0 5 Vdc or 0 10 Vdc A sensor auto zero can be initiated by pressing and holding the internal ZERO switch for at least 3 ...

Страница 6: ...Cycles 100 million Surge Damping 1 60 seconds averaging menu selectable Zero Adjust Push button and remote input Sensor Operating Range 40 to 105 C 40 to 221 F Operating Environment 0 to 50 C 32 to 122 F 10 to 90 RH non condensing Pressure Connection 1 4 NPT male Sensor Housing IP67 Remote Sensor Cable S FT 6 plenum rated A Armored Flexible S S Wiring Connection 14 22 AWG screw terminal block Encl...

Отзывы: