DP Alarm Operation
(low, high, both, disable)
(Default
=
both)
25. Setpoint Lock
(lock or unlock)
(Default
=
Un
LOC)
26. User Menu
(lock or unlock)
(Default = Un LOC)
USER MENU
The User Menu is accessed by pressing the <MENU> key. This menu is used in the field to configure
parameters such as alarm setpoints. The User Menu may be locked so it cannot be accessed in the field,
but can be unlocked via BACnet®, Modbus or the Installer menu if necessary using USER MENU LOCK.
If the User Menu is unlocked, then the following parameters are available to be changed.
If SETPOINT LOCK is set, then the setpoints can be viewed but not changed.
1. Temperature
Units
C F (Default = C)
2. Pressure
Units
(Pascal
or
mmWc)
PA,
StA
(Default
=
PA)
3. TEMP Alarm Low Setpoint
(Resolution = 1°)
(Default = 15C or 59F)
4. TEMP Alarm High Setpoint
(Resolution = 1°)
(Default
=
25C
or
77F)
5. TEMP Alarm Hysteresis
(Resolution = 0.1°)
(Default = 0.2 °C or 0.4 °F)
6. TEMP Alarm On Delay
(Resolution = 1 sec)
(Default
=
5
sec)