Page 12
GENERAL
Operating Conditions 0 - 50 °C (32 - 122 °F),
0 - 90 %RH non-condensing
Storage Temperature -20 - 60 °C (-4 - 140 °F)
Power Supply 24-30 Vdc / 20-26 Vac
Power Consumption 200 mA max
Wiring Connections Pluggable screw terminal block
(14 to 22 AWG)
Pressure Connections Port for 1/8” ID tubing
Enclosure - Wall Mount:
SS304, suitable for wipe-down.
225mm wide x 182.5mm high x 36mm deep.
(8.86” x 7.19” x 1.46”)
Enclosure - Remote Sensor Plate:
70mm wide x 115mm high45mm deep
(2.76” x 4.53” x 1.77”)
Weight
1.3 kg
Certification
CE, RoHS
ANALOG INPUTS FOR REMOTE SENSORS
Signal Type
4-20 mA / 0-5 Vdc / 0-10 Vdc selectable
Number
of
Inputs 3 (Temp, RH, DP)
Input Impedance 250 Ω for 4-20 mA, 10KΩ for voltage
Input Ranges 0-35/0-50 °C, 0-100 %RH, ± 250 Pa/± 500 Pa
Transmitter Power Output 20 Vdc nominal, 100 mA max
INDICATION
Temperature Display 3 digit LED as 0.0-50.0 °C or 32.0-122 °F
(°C / °F is indicated by an LED)
Relative Humidity Display 3 digit LED as 0.0-99.9 %RH
Differential Pressure Display
3 1/2 digit LED display as -500-500 Pa
or -50.0-50.0 mmWc (Pa / mmWc is indicated by an LED)
Digit Type 7 segment red LED, 0.80” (20.32 mm) high
Alarm Indication Low/High alarm red LED for each
USER INPUT
Programming Menu / Up / Down front panel tactile buttons
Alarm Silence
Silence front panel tactile buttons
ANALOG OUTPUTS
Signal Type
4-20 mA (sourcing)
and 0-5 Vdc / 0-10 Vdc selectable
Number of Outputs 3 (Temp, RH, DP)
Output Drive 500 Ω max for 4-20 mA,
10 KΩ min for voltage
Output Scales 0-50 °C, 0-100 %RH, ± 500 Pa
ALARM OUTPUTS
Number of Outputs
3 (Temp, RH, DP) can assign
condition as low/high/both
Output Type NO optically isolated solid state FET switch
Contact Rating 100 mA at 28 Vac / 40 Vdc maximum
Trip Point Upper and Lower alarms
adjustable over a range
Alarm Delay
0 to 255 seconds (programmable)
Operation
Self-resetting, non-latching
Alarm Buzzer Internal, operates on any alarm condition
Buzzer Delay 0-255 seconds (programmable)
Buzzer
DB
70db
at
30cm
Operation
Self-resetting, can be silenced
via button or disabled remotely
COMMUNICATION
Hardware Isolated 2-wire RS-485 MS/TP
Software
Modbus RTU or BACnet®
Baud Rate 9600, 19200, 38400, 57600, 76800 or 115200
Address Range 1-255 for Modbus, 0-127 for BACnet®
DIMENSIONS
225 mm
8.86“
182.5 mm
7.19“
36mm
1.46“
SPECIFICATIONS
IN-CR3
CXXANA-01 04
/20