Page 8
14. TEMP Analog Output Direction
(direct or reverse)
(Default
=
dIr)
15. RH Analog Output Direction
(direct or reverse)
(Default
=
dIr)
16. DP Analog Output Direction
(direct or reverse)
(Default
=
dIr)
17. TEMP Analog Input Range
(input
scaling)
(Default
=
50C)
18. DP Analog Input Range
(input scaling, Pa)
(Default
=
250)
19. Buzzer
Assignment
(TEMP, RH, DP, disable or all)
(Default
=
dP)
20. Buzzer Reset Mode
(manual or auto-reset)
(Default
=
AUt)
21. Buzzer Auto Reset Time
(Resolution = 1 sec)
(Default
=
15
sec)
22. Digital Input Function
(disable, freeze or silence)
(Default
=
disable)
23. TEMP Alarm Operation
(low, high, both, disable)
(Default
=
disable)
24. RH Alarm Operation
(low, high, both, disable)
(Default
=
disable)
o u t
t e
d i r
o u t
r h
d i r
o u t
d p
d i r
a i n
t e
5 0
a i n
d p
2 5 0
b u z z
a s s
d p
b u z z
r s t
a u t
b u z z
1 5
s e c
d l l n
f u n
d i s
a l a r
t e
d i s
A L A r
r h
d i s
IN-CR3
CXXANA-01 04
/20
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com