Page 23
SFM 6.1 Slurry Flow Meter
Possible Causes:
Corrective Action:
METER READING ERRATIC
Sensor mounted too close to valve, pump or elbow
Change sensor placement. Recommended 6-10
diameters from elbows, and 30 diameters from
pumps, controlling valves, orifice plates,
nozzles or open pipe discharge
NO FLOW INDICATION
Not enough suspended particles or gases in the fluid
Relocate sensor in more turbulent pipe section.
Mount sensor at 12 o'clock position on
horizontal pipe
Coupling compound washed out, or sensor loose on
pipe
Remount sensor
Use Dow Corning Silicone #4
Power interruption. No flow.
Check fuse/breaker. Confirm flow
METER READING TOO HIGH
Calibration error
Review
UNITS/MODE
menu and
Pipe ID
Vibration or noise on the pipeline
Install in another location.
Pipe is not full
Remount Sensor on vertical pipe
Nearby velocity increasing device (pump, valve, orifice
plate)
Relocate sensor >30 pipe diameters from
velocity increasing device
Local electrical noise
Ensure all Flowmeter wiring is in METAL
conduit and sensor cable shield is connected to
Ground stud
Variable Speed Drive interference
Follow Drive manufacturers wiring and
Grounding instructions
Relocate Flowmeter electronics, Sensor and
wiring away from VSD
Содержание SFM 6.1
Страница 2: ...Note This page has been left blank intentionally ...
Страница 5: ...Page 5 SFM 6 1 Slurry Flow Meter CONNECTIONS ...
Страница 7: ...Page 7 SFM 6 1 Slurry Flow Meter CALIBRATION MENU ...
Страница 8: ...Page 8 SFM 6 1 Slurry Flow Meter ICONS ...
Страница 19: ...Page 19 SFM 6 1 Slurry Flow Meter SENSOR MOUNTING COUPLING RECOMMENDATIONS ...
Страница 28: ...Page 28 SFM 6 1 Slurry Flow Meter FLOW METER DATA SHEET ...
Страница 41: ......