Js/gp/bbq/bbqbench/milobenchelectricalwiringrequirements.doc Updated 08.09.14
1
Myles Single Bench Base Slab Information and Electrical Wiring Requirements
Suggested slab size 2866 mm x 2866 x 100 mm thick
Base size of Milo barbecue bench 872 mm x 872 mm OD
130 mm turn in for fixing of bench to the concrete slab
4 x M10 Dyna bolts 50 mm deep (supplied)
ELECTRICAL WIRING REQUIRMENTS:
Electrical wiring to waterproof GPO 10 amp to AS3000:2007 standard requires a minimum of 2.5 mm² cabling for each Greenplate Inbench
barbecue unit, larger for long runs, with each barbecue unit having it’s own 20 amp RCBO C-Curve type A in the mains sub-board.
“Under No circumstance should more than one barbecue unit be on one power line. Failure to install correctly will VOID
the warranty as damage to the electrical equipment will occur.”
872 MM
872 MM
Single GPO power point with
separate 10 amp circuit for each GP
300 Inbench Unit to be installed on
timber or steel post 200 mm from
back wall, of Milo bench
[BASE VIEW]
200 MM
130 MM
DOOR
2866 MM
250 MM
2866 MM