Parameter Menu Sub-Menu 1 Sub-Menu 2 Sub-Menu 3

Description

Factory Default

Page 0

, Temperature Control

Temperature Control Off

Temperature Control On

ON

Cooling Mode, moving cooling air to space

COOL

Heating Mode, moving heating air to space

Temperature Setpoint in Degrees Fahrenheit, 15° 

to 130°, by 1°, Units Controlled by P1

72°F

Temperature Setpoint in Degrees Celsius, -10° to 

55°, by 0.5°, Units Controlled by P1

Page 1

, Temperature Units

Fahrenheit Degrees

F

Celsius Degrees

Page 2

, Humidity Control

Humidity Control Off

OFF

Humidity Control On

Humidity Setpoint, 0 to 100 %RH by 1 %RH

50%

Page 3

, Restore Factory Default Menu Values

Entry Screen, Leave Current Values

OFF

Restore Factory Values

Page 4

, Display Format

Turn Minor and Major Display Off, Mode Icons On

Show % Fan Speed

Show Space Temperature and Humidity, Depends 

on control mode

run

Page 5

, Fan Cutout Timer

Fan Cutout Off

OFF

Fan Cutout On

Cutout Timer, 0 to 300 seconds

30

Page 6

, Override % Fan Speed

20% to 100% Fan Speed, by 1%

100

Page 7

, Manual Fan Speed Override

Manual Fan Speed Override Off

OFF

Manual Fan Speed Override On

Manually Set Fan Speed, 20% to 100% in 1% 

increments or 0%

50

Page 8

, Minimum % Fan Speed

20

Minimum % Fan Speed Value, 20% to 100% in 1% 

increments

Page 9

, Maximum % Fan Speed

Maximum % Fan Speed Value, 20% to 100% in 

1% increments

100

Page 10

, Analog Output Reference

0 to 100 %RH, for 0 to 10 VDC

15° to 130°F or -10° to 55°C, for 0 to 10 VDC, 

Units Controlled by P1

t

Parameter P7 continued....

Allows manual control of the fan speed for system 

setup and commissioning tests.  Exiting this 

parameter returns the controller to normal operation.
When entering this parameter, the value shall be 

OFF (normal operation). Press the UP button to set 

the parameter value to On and then press the ENT 

button. The unit is now in manual control.
The major display shall read 50 for 50% output (5 

VDC out). The minor display shall show %SPD.
Pressing the UP button shall increase the displayed 

value and proportionally change the fan speed. 

Pressing the DN button shall decrease the displayed 

value and proportionally change the fan speed.
Allowed values are 0% and 20 to 100%, for 0 VDC 

and 2 to 10 VDC fan motor control voltage.
The fan speed will remain at the displayed value 

until the ENT button is pressed placing the unit back 

to the parameter selection mode.

Minimum Fan Speed, Parameter P8

Factory Default = 20%

Parameter P8 continued... 

%MIN #

 = 20% to 100% in 1% increments

Sets the min fan speed that the controller may 

control to. Note: the controller will not allow the 

output min to be set higher than the output max.

Maximum Fan Speed, Parameter P9

Factory Default = 100%

%MAX #

 = 20% to 100% in 1% increments

Sets the max fan speed that the controller may 

control to. Note: the controller will not allow the 

output max to be set lower than the output min.

Analog Output Reference, Parameter P10

Factory Default = Temperature

REF H

 = Humidity, 0 to 10V for 0 to 100%RH

REF t

 = Temperature, 

     

  0 to 10V for 15° to 130°F (-10° to 55°C)

An analog output across J15 terminals “REF” and 

“GND” for the measured temp or humidity.

Содержание Vari-Green Control 475573

Страница 1: ...thms are satisfied the output voltage shall be set to its lowest value 2 VDC If the temperature is 1 F below the temperature DANGER Always disconnect lock and tag power source before installing or servicing Failure to disconnect power source can result in fire shock or serious injury CAUTION When servicing the fan motor may be hot enough to cause pain or injury Allow motor to cool before servicing...

Страница 2: ...rage of this product is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow...

Страница 3: ...two 3 16 inch holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 5 Drill one 1 2 inch hole in the middle of the marked wiring area 6 Pull the wire through the wall and out of the 1 2 Inch hole leaving about six inches free 7 Pull the wire through the hole in the base plate 8 Secure the base to the dryw...

Страница 4: ...Heat Control Icon Cool Control Icon Display Features The minor display is used to describe the units displayed and the main display shows the numeric value The fan icon is illuminated whenever the fan output voltage is at or above the minimum specified in parameter P8 Minimum Fan Speed The Cool and Heat Icons are illuminated in each control mode respectively The dot in the lower left is used to si...

Страница 5: ...Setpoint 0 to 100 RH in 1 increments Restore Factory Default Parameter Values Parameter P3 Factory Default OFF FAC OFF Entry screen leave current values FAC On Restore factory values Display Format Parameter P4 Factory Default run DIS OFF Turn minor and major displays off leave control mode and fan icons on DIS FAn Unit shows fan speed until scroll button pushed DIS run Unit shows temp or humidity...

Страница 6: ...button to set the parameter value to On and then press the ENT button The unit is now in manual control The major display shall read 50 for 50 output 5 VDC out The minor display shall show SPD Pressing the UP button shall increase the displayed value and proportionally change the fan speed Pressing the DN button shall decrease the displayed value and proportionally change the fan speed Allowed val...

Страница 7: ...seconds 30 Page 6 Override Fan Speed 20 to 100 Fan Speed by 1 100 Page 7 Manual Fan Speed Override Manual Fan Speed Override Off OFF Manual Fan Speed Override On Manually Set Fan Speed 20 to 100 in 1 increments or 0 50 Page 8 Minimum Fan Speed 20 Minimum Fan Speed Value 20 to 100 in 1 increments Page 9 Maximum Fan Speed Maximum Fan Speed Value 20 to 100 in 1 increments 100 Page 10 Analog Output Re...

Страница 8: ...ck will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Warranty 475573 Indoor Air Quality Temp Humidity Rev 1 June 2012 Copyright 2012 Greenheck Fan Corporation Problem Fan always at minimum speed Blow into the bottom of the unit Your breath should increase the hum...

Отзывы: