6
Parameter Menu Sub-Menu 1 Sub-Menu 2 Sub-Menu 3
Description
Factory Default
Page 0
, Temperature Control
Temperature Control Off
Temperature Control On
ON
Cooling Mode, moving cooling air to space
COOL
Heating Mode, moving heating air to space
Temperature Setpoint in Degrees Fahrenheit, 15°
to 130°, by 1°, Units Controlled by P1
72°F
Temperature Setpoint in Degrees Celsius, -10° to
55°, by 0.5°, Units Controlled by P1
Page 1
, Temperature Units
Fahrenheit Degrees
F
Celsius Degrees
Page 2
, Humidity Control
Humidity Control Off
OFF
Humidity Control On
Humidity Setpoint, 0 to 100 %RH by 1 %RH
50%
Page 3
, Restore Factory Default Menu Values
Entry Screen, Leave Current Values
OFF
Restore Factory Values
Page 4
, Display Format
Turn Minor and Major Display Off, Mode Icons On
Show % Fan Speed
Show Space Temperature and Humidity, Depends
on control mode
run
Page 5
, Fan Cutout Timer
Fan Cutout Off
OFF
Fan Cutout On
Cutout Timer, 0 to 300 seconds
30
Page 6
, Override % Fan Speed
20% to 100% Fan Speed, by 1%
100
Page 7
, Manual Fan Speed Override
Manual Fan Speed Override Off
OFF
Manual Fan Speed Override On
Manually Set Fan Speed, 20% to 100% in 1%
increments or 0%
50
Page 8
, Minimum % Fan Speed
20
Minimum % Fan Speed Value, 20% to 100% in 1%
increments
Page 9
, Maximum % Fan Speed
Maximum % Fan Speed Value, 20% to 100% in
1% increments
100
Page 10
, Analog Output Reference
0 to 100 %RH, for 0 to 10 VDC
15° to 130°F or -10° to 55°C, for 0 to 10 VDC,
Units Controlled by P1
t
Parameter P7 continued....
Allows manual control of the fan speed for system
setup and commissioning tests. Exiting this
parameter returns the controller to normal operation.
When entering this parameter, the value shall be
OFF (normal operation). Press the UP button to set
the parameter value to On and then press the ENT
button. The unit is now in manual control.
The major display shall read 50 for 50% output (5
VDC out). The minor display shall show %SPD.
Pressing the UP button shall increase the displayed
value and proportionally change the fan speed.
Pressing the DN button shall decrease the displayed
value and proportionally change the fan speed.
Allowed values are 0% and 20 to 100%, for 0 VDC
and 2 to 10 VDC fan motor control voltage.
The fan speed will remain at the displayed value
until the ENT button is pressed placing the unit back
to the parameter selection mode.
Minimum Fan Speed, Parameter P8
Factory Default = 20%
Parameter P8 continued...
%MIN #
= 20% to 100% in 1% increments
Sets the min fan speed that the controller may
control to. Note: the controller will not allow the
output min to be set higher than the output max.
Maximum Fan Speed, Parameter P9
Factory Default = 100%
%MAX #
= 20% to 100% in 1% increments
Sets the max fan speed that the controller may
control to. Note: the controller will not allow the
output max to be set lower than the output min.
Analog Output Reference, Parameter P10
Factory Default = Temperature
REF H
= Humidity, 0 to 10V for 0 to 100%RH
REF t
= Temperature,
0 to 10V for 15° to 130°F (-10° to 55°C)
An analog output across J15 terminals “REF” and
“GND” for the measured temp or humidity.