User Interface

A scroll button protrudes through the case.  The 

programming switches and programming jumper are 
inside the case. 

Minor Display 

0.34 inch 3-digit 

Alpha-Numeric

Main Display 0.76 

inch 4-digit Numeric 

Dot

Controller 

Terminal

Transformer 

Control Terminal

J15-FAN

0 to 10V

J15-GND

COM

J15-24V

24V

Wiring

All wiring for the Greenheck Temperature and 

Humidity Controller is Class II low-voltage control 

wiring. See the Wiring Diagram on Page 7 for the 

wiring overview.

Optional Remote Override

Connect a normally-open switch between terminals 

J17-OVR and J15-GND on the controller.  Closing 

this switch will activate the remote override feature.  

Opening the switch will de-activate the override.

Optional Output Reference

A 0 to 10VDC signal is available from J15-REF to 

J15-GND.  The signal is 15° to 130° F (-10° to 55°C) 

or 0 to 100% Relative Humidity depending on the 

value of parameter P10 (see pg 6).

Control box to factory mounted 

transformer control input.

Scroll

Button

Programming

Jumper in 

RUN Mode

Fan ON Icon 

Programming 

Switches

Heat Control 

Icon 
Cool Control 

Icon 

Display Features

The minor display is used to describe the units 

displayed and the main display shows the numeric 

value.  The fan icon is illuminated whenever the fan 

output voltage is at or above the minimum specified 

in parameter P8, Minimum % Fan Speed.  The Cool 

and Heat Icons are illuminated in each control mode 

respectively.  The dot in the lower left is used to 

signal fan cut-out mode.

Normal Operation (J19 = RUN)

The Greenheck Indoor Air Quality – Temperature/

Humidity Controller ships with the following factory 

setting: Cooling Control, Temperature Setpoint 72°F, 

Fan Control output at 2 to 10 Volts and Cut-Out 

Disabled.  Pressing the scroll button at any time 

shows the Temperature setpoint, a second push 

shows the fan speed in percent.

The scroll button will change the display momentarily 

to view other information such as setpoints and fan 

speed.  These are for reference only, and cannot 

be adjusted.  The exact sequence will depend on 

the settings of parameters P0, P1, P2 and P4.  For 

examples, see the two figures below. 

Scroll Button Sequence, 

Temperature & Humidity Control 

Cooling Mode, °F Temperature 

and Display in run.

Scroll Button 

Sequence, 

Temperature 

Control 

Cooling Mode, 

°F Temperature 

and Display in 

run.

Содержание Vari-Green Control 475573

Страница 1: ...thms are satisfied the output voltage shall be set to its lowest value 2 VDC If the temperature is 1 F below the temperature DANGER Always disconnect lock and tag power source before installing or servicing Failure to disconnect power source can result in fire shock or serious injury CAUTION When servicing the fan motor may be hot enough to cause pain or injury Allow motor to cool before servicing...

Страница 2: ...rage of this product is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow...

Страница 3: ...two 3 16 inch holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 5 Drill one 1 2 inch hole in the middle of the marked wiring area 6 Pull the wire through the wall and out of the 1 2 Inch hole leaving about six inches free 7 Pull the wire through the hole in the base plate 8 Secure the base to the dryw...

Страница 4: ...Heat Control Icon Cool Control Icon Display Features The minor display is used to describe the units displayed and the main display shows the numeric value The fan icon is illuminated whenever the fan output voltage is at or above the minimum specified in parameter P8 Minimum Fan Speed The Cool and Heat Icons are illuminated in each control mode respectively The dot in the lower left is used to si...

Страница 5: ...Setpoint 0 to 100 RH in 1 increments Restore Factory Default Parameter Values Parameter P3 Factory Default OFF FAC OFF Entry screen leave current values FAC On Restore factory values Display Format Parameter P4 Factory Default run DIS OFF Turn minor and major displays off leave control mode and fan icons on DIS FAn Unit shows fan speed until scroll button pushed DIS run Unit shows temp or humidity...

Страница 6: ...button to set the parameter value to On and then press the ENT button The unit is now in manual control The major display shall read 50 for 50 output 5 VDC out The minor display shall show SPD Pressing the UP button shall increase the displayed value and proportionally change the fan speed Pressing the DN button shall decrease the displayed value and proportionally change the fan speed Allowed val...

Страница 7: ...seconds 30 Page 6 Override Fan Speed 20 to 100 Fan Speed by 1 100 Page 7 Manual Fan Speed Override Manual Fan Speed Override Off OFF Manual Fan Speed Override On Manually Set Fan Speed 20 to 100 in 1 increments or 0 50 Page 8 Minimum Fan Speed 20 Minimum Fan Speed Value 20 to 100 in 1 increments Page 9 Maximum Fan Speed Maximum Fan Speed Value 20 to 100 in 1 increments 100 Page 10 Analog Output Re...

Страница 8: ...ck will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Warranty 475573 Indoor Air Quality Temp Humidity Rev 1 June 2012 Copyright 2012 Greenheck Fan Corporation Problem Fan always at minimum speed Blow into the bottom of the unit Your breath should increase the hum...

Отзывы: