Indoor Air Quality–Temp/Humidity

1

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble, 

install, operate or maintain the product described. Protect yourself and others by observing all safety 

information. Failure to comply with instructions could result in personal injury and/or property damage!

The Temperature and Humidity Controller is 

specifically designed to control a Vari-Green fan 

motor.  The Temperature and Humidity Controller 

will sense the temperature and humidity in the 

space and will automatically adjust the speed of 

a supply or exhaust fan to adjust the ventilation 

rate accordingly.  The temperature measurement 

will be compared to a field adjustable temperature 

setpoint, processed through a Proportional/Integral/

Derivative (PID) control algorithm to produce a 2 

to 10 VDC fan motor control output.  The humidity 

measurement will be compared to a field adjustable 

humidity setpoint, processed through a PID control 

algorithm to produce a 2 to 10 VDC fan motor 

control output.  If the unit is in temperature only 

mode the temperature algorithm’s output shall be 

used to provide the fan motor control output.  When 

the unit is in humidity-only mode the humidity 

algorithm’s output shall be used to provide the 

fan motor control output.  When the unit is in 

temperature and humidity mode the algorithm with 

the greatest output shall be used to provide the fan 

motor control output.

When all active algorithms are satisfied, the output 

voltage shall be set to its lowest value, 2 VDC.  If 

the temperature is 1°F below the temperature 

DANGER

Always disconnect, lock and tag power source before 

installing or servicing. Failure to disconnect power 

source can result in fire, shock or serious injury.

CAUTION

When servicing the fan, motor may be hot enough 

to cause pain or injury. Allow motor to cool before 

servicing.

CAUTION

Precaution should be taken in explosive 

atmospheres.

Only qualified personnel should install this product. 

Personnel should have a clear understanding of 

these instructions and should be aware of general 

safety precautions. Improper installation can result 

in electric shock, possible injury due to coming in 

contact with moving parts, as well as other potential 

hazards. Other considerations may be required 

if high winds or seismic activity are present. If 

more information is needed, contact a licensed 

professional engineer before moving forward.

Temperature and Humidity Controller

General Safety Information

setpoint in 

temperature control 

and the humidity 

is 3% below the 

humidity setpoint in 

humidity control or 

both in temperature 

and humidity control, 

the voltage output 

may be set to zero 

(optional cutout 

mode).  The unit 

will resume normal 

fan operation if 

the temperature 

changes by 1°F or 

the humidity changes by 5%.

Ventilating based on the temperature and humidity 

measurements assures that the space will not be 

over or under ventilated while using the Vari-Green 

motor technology to operate quietly and efficiently.  

The Temperature and Humidity Controller has 

adjustments for setpoint, minimum and maximum 

fan speed.  The fan speed and temperature or 

humidity level are available as an analog output to 

be read by a building 

Содержание Vari-Green Control 475573

Страница 1: ...thms are satisfied the output voltage shall be set to its lowest value 2 VDC If the temperature is 1 F below the temperature DANGER Always disconnect lock and tag power source before installing or servicing Failure to disconnect power source can result in fire shock or serious injury CAUTION When servicing the fan motor may be hot enough to cause pain or injury Allow motor to cool before servicing...

Страница 2: ...rage of this product is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow...

Страница 3: ...two 3 16 inch holes in the center of each marked mounting hole DO NOT punch the holes or the drywall anchors will not hold Insert a drywall anchor into each hole 5 Drill one 1 2 inch hole in the middle of the marked wiring area 6 Pull the wire through the wall and out of the 1 2 Inch hole leaving about six inches free 7 Pull the wire through the hole in the base plate 8 Secure the base to the dryw...

Страница 4: ...Heat Control Icon Cool Control Icon Display Features The minor display is used to describe the units displayed and the main display shows the numeric value The fan icon is illuminated whenever the fan output voltage is at or above the minimum specified in parameter P8 Minimum Fan Speed The Cool and Heat Icons are illuminated in each control mode respectively The dot in the lower left is used to si...

Страница 5: ...Setpoint 0 to 100 RH in 1 increments Restore Factory Default Parameter Values Parameter P3 Factory Default OFF FAC OFF Entry screen leave current values FAC On Restore factory values Display Format Parameter P4 Factory Default run DIS OFF Turn minor and major displays off leave control mode and fan icons on DIS FAn Unit shows fan speed until scroll button pushed DIS run Unit shows temp or humidity...

Страница 6: ...button to set the parameter value to On and then press the ENT button The unit is now in manual control The major display shall read 50 for 50 output 5 VDC out The minor display shall show SPD Pressing the UP button shall increase the displayed value and proportionally change the fan speed Pressing the DN button shall decrease the displayed value and proportionally change the fan speed Allowed val...

Страница 7: ...seconds 30 Page 6 Override Fan Speed 20 to 100 Fan Speed by 1 100 Page 7 Manual Fan Speed Override Manual Fan Speed Override Off OFF Manual Fan Speed Override On Manually Set Fan Speed 20 to 100 in 1 increments or 0 50 Page 8 Minimum Fan Speed 20 Minimum Fan Speed Value 20 to 100 in 1 increments Page 9 Maximum Fan Speed Maximum Fan Speed Value 20 to 100 in 1 increments 100 Page 10 Analog Output Re...

Страница 8: ...ck will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Warranty 475573 Indoor Air Quality Temp Humidity Rev 1 June 2012 Copyright 2012 Greenheck Fan Corporation Problem Fan always at minimum speed Blow into the bottom of the unit Your breath should increase the hum...

Отзывы: