background image

5

An evaporative cooling section includes a galvanized 
steel housing with a louvered intake, two inch aluminum 
mesh filters and a stainless steel evaporative cooling 
media housing. The evaporative cooling media is 
Munters CELdek or GLASdek and has a depth of 
12 inches for 90% cooling effectiveness. 

Drain and overflow lines are conveniently stubbed 
through the side of the cooling section. The supply line 
connection is field located where convenient. 

IGX-HV airflow capacity for evaporative cooling is up 
to 14,000 cfm. Below 9,000 cfm, evaporative cooling 
modules ship attached and factory wired. Field 
attachment is required for airflow above 9,000 cfm.

Mixing Box controls:

Mixing box control option EC1 is recommended for use 

with evaporative 
cooling. On a call 
for cooling when 
the outdoor air 
temperature is below 
the economizer 
setpoint, the 
dampers modulate 
to provide cool 
mixed temperatures 
down to 55° F. When 
the outdoor air is 
above the economizer setpoint, the evaporative cooling 
section is energized and the dampers travel to the 100% 
outdoor air position.

The MB mixing box options are 

NOT

 recommended in 

conjunction with evaporative cooling.

cooLInG oPtIons

evaporative cooling

Model IGX-HV boasts the flexibility of Chilled Water or 
Direct Expansion (DX) cooling with capacity to 11,000 
CFM. The cooling section includes the cooling coil, 
stainless steel drain pan and insulated double wall 
construction. Drain and coil connections are stubbed 
through the wall for convenience. 

For proper coil sizing, use Greenheck’s Computer Aided 
Product Selection (CAPS) program or contact your local 
representative. Four and six row coils are available.

Cooling coil sections are installed downstream of the 
mixing box section for a draw through arrangement.  
This provides a streamlined transition to adjacent 
IGX-HV sections. DX coils require remote condensing 
units.

Mixing Box controls:

All MB and EC mixing box control options are available 
with chilled water or DX cooling coils. 

For economizer 
climates, the 
EC1 option is 
recommended. 
Mixing box options 
operate as described 
on page 4.

thermostats:

The cooling coil 
and MB mixing box 
control options may 
use a 1-stage (chilled 
water or single stage DX) or 2-stage (dual stage DX) 
cooling thermostat.

The cooling coil and EC mixing box control options 
require a 2-stage cooling thermostat. Economizer 
represents the first stage of cooling and a single DX 
stage or chilled water coil represents the second stage 
of cooling.

cooling coils

Mixing Box selection Guide

*Two-stage cooling thermostat required. Boldface type indicates factory recommended options.

ec options

MB options

ec1

ec2

ec3

ec4

MB1

MB2

MB3

MB4

no cooling

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

evaporative 

cooling

Yes

Yes

Not 

Recommended

Not 

Recommended

No

No

No

No

chilled Water or 

dX cooling

Yes*

Yes*

Yes*

Yes*

Yes

Yes

Yes

Yes

Содержание IGX-HV

Страница 1: ...Modular Heating Ventilating Unit Model IGX HV Indirect Gas Fired Heating Evaporative Chilled Water DX Cooling October 2008...

Страница 2: ...s steel heat exchanger Direct spark ignition system Easy access burner controls ETL listed to ANSI Standard Z83 8 Solid state automatic ignition module Vibration Isolators The entire fan and motor ass...

Страница 3: ...cooling The Intelligent Fan feature energizes the fan continuously during occupied mode and intermittently with a call for heating or cooling in unoccupied mode TC3 2 Stage Heating 2 Stage Cooling TC...

Страница 4: ...Like the MB2 option this option is appropriate for applications that call for a building automation system that will control the mixing box dampers MB4 Manual Quadrant The MB4 option consists of a man...

Страница 5: ...ng section includes the cooling coil stainless steel drain pan and insulated double wall construction Drain and coil connections are stubbed through the wall for convenience For proper coil sizing use...

Страница 6: ...1 3 000 RPM 1014 1097 1172 1244 1315 1386 250 BHP 1 22 1 39 1 55 1 72 1 88 2 05 MODEL CFM TOTAL STATIC PRESSURE in inches of WG Maximum Furnace Size Input MBH 0 50 0 75 1 00 1 25 1 50 1 75 IGX HV 112...

Страница 7: ...mist eliminating intake hood is standard on outdoor IGX HV models The mist eliminating intake hood provides a double layer of protection against moisture entering the mixing box section Propane Gas C...

Страница 8: ...d for a minimum of 150 of driven horsepower Pulleys shall be cast and have machined surfaces 10 horsepower and less shall be supplied with an adjustable drive pulley Electrical All internal electrical...

Отзывы: