General:

  Heating and Ventilating unit shall be as 

manufactured by Greenheck or approved equal provided 
all specifications are met. Greenheck Model IGX-HV is 
used as the basis of design. Performance shall be as 
scheduled on plans.

Furnace:

  Indirect gas fired furnace shall be 80% efficient, 

ETL Listed and have a blow through fan design. Furnace 
shall be capable of operation with Natural or LP gas and 
have a power venting system with post purge cycle. The 
heat exchanger shall be constructed of aluminized steel 
or stainless steel. Standard furnace features shall include 
main gas pressure regulator, main gas valve, electronic 
staged controls, direct spark ignition system, high limit and 
a 24 volt control transformer. Furnace shall be insulated 
and have double wall construction.

Temperature Control:

  Heating and cooling output shall 

be controlled by a room thermostat to maintain desired 
room temperature. Economizer control shall provide the 
first stage of cooling, where specified. Furnaces shall 
provide one or two stages of heat output control.

Unit Casing and Frames:

  All frames and panels shall 

be G90 galvanized steel. Where top panels are joined 
there shall be a standing seam to insure positive weather 
protection. All metal-to-metal surfaces exposed to the 
weather shall be sealed, requiring no caulking at job 
site. All components shall be easily accessible through 
removable doors.

Insulation:

  Models provided with a mixing box shall be 

insulated from the return section through to the supply 
discharge. Insulation shall be in accordance with NFPA 
90A and tested to meet UL 181 erosion requirements. 
Double wall shall be provided if specified.

Fan Section:

  Centrifugal fans shall be double width, 

double inlet. Fan and motor shall be mounted on a 
common base and shall be internally isolated. All blower 
wheels shall be statically and dynamically balanced. 
Ground and polished steel fan shafts shall be mounted in 
permanently lubricated ball bearings (up to size 118) or 
ball bearing pillow blocks (size 120 and larger). Bearings 
shall be selected for a minimum (L10) life in excess of 
100,000 hours at maximum cataloged speeds.

Motors and Drives:

  Motors shall be energy efficient, 

complying with EPACT standards, for single speed 
ODP and TE enclosures. Motors shall be permanently 
lubricated, heavy duty type, matched to the fan load and 
furnished at the specified voltage, phase and enclosure. 
Drives shall be sized for a minimum of 150% of driven 
horsepower.  Pulleys shall be cast and have machined 
surfaces, 10 horsepower and less shall be supplied with 
an adjustable drive pulley.

Electrical:

 

 All internal electrical 

components shall be prewired for 
single point power connection. All 
electrical components shall be UL 
listed, recognized or classified where 
applicable and wired in compliance 
with the National Electrical Code. 
Control center shall include motor 
starter, control circuit fusing, control 
transformer for 24 VAC circuit, 
integral disconnect switch with 
separate motor fusing and terminal 
strip. Contactors, Class 20 adjustable 
overload protection and single phase 
protection shall be standard.

Filter Section:

  Filters shall be 

mounted in a V-bank arrangement 
such that velocities across the filters 
do not exceed 550 feet per minute. Filters shall be easily 
accessible through a removable access panel.

Weatherhood:

  Weatherhood shall be mist eliminating 

type, constructed of G90 galvanized steel. The 
weatherhood shall contain drainable blade louvers, backed 
by mist eliminating filters to prevent moisture intake.

Mixing Box:

  Mixing box shall contain outside air and 

return air dampers with low leak, pressure activated, 
extruded vinyl blade seals, aluminum jamb seals, Belimo 
actuator and 30% efficient pleated filters in a V-bank 
arrangement. The mixing box shall modulate the amount 
of outdoor and return air by use of dampers. Input signal 
for return damper shall be from potentiometer, 2-10 volt 
signal, 4-20 mA signal or manual quadrant controller.

Evaporative Cooling Section:

  Evaporative cooling 

section shall include a galvanized steel housing with 
louvered intake, two inch aluminum mesh filters and a 
stainless steel evaporative cooling module all provided 
by the make-up air unit manufacturer. The louver shall 
be stationary type with drainable blades, designed to 
withstand wind loads of 25 PSF and bear the AMCA seal. 
Evaporative cooling media shall be Munters CELdek with 
a depth of 12 inches for a cooling effectiveness of 90%. 
Drain and overflow connections shall be piped through the 
side of the evaporative cooling section.

Cooling Coil:

 

 Direct expansion (DX) or chilled water 

coil shall be factory tested and rated in accordance with 
ARI 410. Coils shall have copper tubes with permanently 
expanded aluminum fins, 12 fpi or less. DX coils shall be 
equipped with distributors to receive expansion valves at 
the liquid connections. Drain pans shall extend at least 
12 inches downstream of coil and be sloped to drain 
connection.

Copyright © 2008 Greenheck Fan Corp. • IGX-HV Rev. 2 October 2008 SN

Specifications

Содержание IGX-HV

Страница 1: ...Modular Heating Ventilating Unit Model IGX HV Indirect Gas Fired Heating Evaporative Chilled Water DX Cooling October 2008...

Страница 2: ...s steel heat exchanger Direct spark ignition system Easy access burner controls ETL listed to ANSI Standard Z83 8 Solid state automatic ignition module Vibration Isolators The entire fan and motor ass...

Страница 3: ...cooling The Intelligent Fan feature energizes the fan continuously during occupied mode and intermittently with a call for heating or cooling in unoccupied mode TC3 2 Stage Heating 2 Stage Cooling TC...

Страница 4: ...Like the MB2 option this option is appropriate for applications that call for a building automation system that will control the mixing box dampers MB4 Manual Quadrant The MB4 option consists of a man...

Страница 5: ...ng section includes the cooling coil stainless steel drain pan and insulated double wall construction Drain and coil connections are stubbed through the wall for convenience For proper coil sizing use...

Страница 6: ...1 3 000 RPM 1014 1097 1172 1244 1315 1386 250 BHP 1 22 1 39 1 55 1 72 1 88 2 05 MODEL CFM TOTAL STATIC PRESSURE in inches of WG Maximum Furnace Size Input MBH 0 50 0 75 1 00 1 25 1 50 1 75 IGX HV 112...

Страница 7: ...mist eliminating intake hood is standard on outdoor IGX HV models The mist eliminating intake hood provides a double layer of protection against moisture entering the mixing box section Propane Gas C...

Страница 8: ...d for a minimum of 150 of driven horsepower Pulleys shall be cast and have machined surfaces 10 horsepower and less shall be supplied with an adjustable drive pulley Electrical All internal electrical...

Отзывы: