Troubleshooting Guide cont....

 

10.  Order the heater with the factory installed 

linear temperature limit control if the heater 
width is greater than 72 inches.

 

11.  Never use aluminum conductors. Use copper 

conductors only for all incoming wiring.

 

12.  Never install a standard heater outdoors with-

out making special provisions to protect the 
heater and control box from the elements. 

 

13.  Never bundle, tie or wrap power wiring. The 

wire could overheat or the insulation could 
breakdown. 

 

14.  Never use a different voltage and/or phase 

than what is listed on the heater nameplate 
label. The duct heater is to be used only at the 
voltage and phase that is listed on the name-
plate label. 

Note:

  An airflow switch only proves that airflow exists 

(a differential in static pressure), not that the 
minimum air velocities and proper air distribution 
for the duct heater exist.

FIG. 7

Air Handler

FIG. 8

Humidifier

FIG. 9

Air Filter

AIR HANDLER

HEATER

HEATER

HUMIDIFIER

AIR FILTER

HEATER

48" MIN.

48" MIN.

DUCT

DUCT

DUCT

48" MIN.

DUCT W/ INTERNAL INSULATION

DUCT W/ EXTERNAL INSULATION

CORRECT

INCORRECT

CORRECT

INCORRECT

FIG. 10

FIG. 11

FIG. 12

INCORRECT

7

Electric Duct Heaters

Содержание IDHB

Страница 1: ...both obvious and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Check to be sure that all parts of the shipment including accessories are accounted for Dampers must be kept dry and clean Indoor storage and protection from dirt dust and the weather is highly recommended Do not store at temperatures in excess of 100 F 3...

Страница 2: ...g as required in the side of the duct Slide heater in the duct using the control box as template to mark the mounting screw holes Remove unit and drill mounting holes Mount unit to duct with sheet metal screws Connect high and low voltage supplies along with fan interlock circuit if no airflow switch is furnished Larger heaters may require hangers To install a flange type heater FIG 2 insert heate...

Страница 3: ...atts per sq ft of duct area divide the total watts required by the duct area EXAMPLE Duct Size 2ft x 3ft Total watts 20 000 W Sq Ft 20 000 3333 6 2 If the air handler equipment is expressed in fpm then a direct cross reference can be made by comparing the temperature of the air as it enters the Duct Heater to the KW rating on the chart of rated velocity a Draw a line horizontally from the Watts Sq...

Страница 4: ...insulation left in place or duct constructed from insulation board Recess Insulation Thickness Note Size of heater is based on the following Heater H Duct H Insulation Thickness x 2 Heater W Duct W Insulation Thickness recess required Internal insulation cut away The internal insulation is to be removed from the area where the heater is mounted Recess Insulation Thickness Note Size of heater is ba...

Страница 5: ...ct heater with electronic step controller or SSR control Without Remote Sensor With Remote Sensor Note Do not adjust dip switches on thermostat Viconics C1025 11 Room Thermostat Viconics C1025 11 Room Thermostat Viconics S61 Remote Sensor Duct Heater Signal Interface Module Duct Heater Signal Interface Module Note This heater will not operate with a standard 24 VAC control signal Do not adjust any...

Страница 6: ...e in duct size downstream from an air handler upstream from a humidifier downstream from an air filter fan 7 Never install a standard heater into a duct with an internal obstruction An obstruction can block airflow at the temperature limit controls and element terminations If this situation exists it can be corrected by using a heater with recessed control box and reduced wrapper size This situati...

Страница 7: ...insulation could breakdown 14 Never use a different voltage and or phase than what is listed on the heater nameplate label The duct heater is to be used only at the voltage and phase that is listed on the name plate label Note An airflow switch only proves that airflow exists a differential in static pressure not that the minimum air velocities and proper air distribution for the duct heater exist...

Страница 8: ...eck Fan Corporation As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Specific Greenheck product warranties are located on greenheck com within the product area tabs and in the Library under Warranties Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo greenheck com Website www greenheck com Our Commitment ...

Отзывы: