Troubleshooting Guide

A duct heater must be installed according to the 
installations instructions, wiring diagram and labeling 
supplied with the heater.
Listed below are some important items when installing 
an electric duct heater:
 

1.  Never operate a duct heater without airflow. 

The heater must always be interlocked with the 
fan. This may be accomplished by either an 
airflow switch or fan interlock relay.

 

2.  Never operate heater without achieving at least 

the minimum airflow required. Always refer to 
the installation instructions and the nameplate 
label to determine minimum air velocities based 
on inlet air temperature. If the minimum airflow 
requirements are not present the heater will not 
function properly and safely 
(see 

Figure 3

).

 

3.  Never operate the heater with uneven airflow. 

The minimum airflow requirements must be 
present at all points over the heater face (see 

Figure 3

).

 

4.  The air must be filtered. The incoming air must 

be free from all debris, combustible particles, 
and hazardous vapors.

 

5.  Locate the heater at least 24 in. from an elbow 

or turn (see 

Figure 4

).

 

6.  Locate the heater at least 48 in. from the 

following (see 

Figures 5-9

):

 

  • heat pump or central air 

 

  • canvas duct connector or transition 

 

     section for change in duct size. 

 

  • downstream from an air handler. 

 

  • upstream from a humidifier 

 

  • downstream from an air filter 

 

  • fan

 

7.  Never install a standard heater into a duct with 

an internal obstruction. An obstruction can 
block airflow at the temperature limit controls 
and element terminations. If this situation 
exists, it can be corrected by using a heater 
with recessed control box and reduced wrapper 
size. This situation is common with internally 
insulated ducts (see

 Figure 10

).

 

8.  Never insulate the exterior of the control box. 

The control must be completely accessible and 
located where ventilation can be provided at all 
times (see 

Figure 11

).

 

9.  Never install a heater near a double blower 

outlet. A heater must be installed far enough 
away from a double blower outlet so that even 
and proper airflow is present or separate duct 
heaters placed in the duct runouts of each 
blower (see 

Figure 12

).

500 fpm

470 fpm

780 fpm

EXAMPLE: IF 780 fpm IS REQUIRED

EXAMPLE: IF 780 fpm IS REQUIRED

EXAMPLE: IF 780 fpm IS REQUIRED

CORRECT

MIN. AIRFLOW AND EVEN AIR 

DISTRIBUTION ARE PRESENT

INCORRECT

MIN. AIRFLOW AND EVEN AIR 

DISTRIBUTION ARE NOT PRESENT

INCORRECT

MIN. AIRFLOW IS NOT PRESENT

FIG. 3

470 fpm
470 fpm

780 fpm
780 fpm

780 fpm
780 fpm

FIG. 4

FIG. 5

Heat Pump or Air Conditioner

24" MIN.

48" MIN.

HEAT PUMP OR

AIR CONDITIONER

HEATER

HEATER

DUCT

DUCT

INCORRECT

CORRECT

FIG. 5

Transition Change

HEATER

48" MIN.

48" MIN.

HEATER

DUCT

DUCT

6

Electric Duct Heaters

Содержание IDHB

Страница 1: ...both obvious and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Check to be sure that all parts of the shipment including accessories are accounted for Dampers must be kept dry and clean Indoor storage and protection from dirt dust and the weather is highly recommended Do not store at temperatures in excess of 100 F 3...

Страница 2: ...g as required in the side of the duct Slide heater in the duct using the control box as template to mark the mounting screw holes Remove unit and drill mounting holes Mount unit to duct with sheet metal screws Connect high and low voltage supplies along with fan interlock circuit if no airflow switch is furnished Larger heaters may require hangers To install a flange type heater FIG 2 insert heate...

Страница 3: ...atts per sq ft of duct area divide the total watts required by the duct area EXAMPLE Duct Size 2ft x 3ft Total watts 20 000 W Sq Ft 20 000 3333 6 2 If the air handler equipment is expressed in fpm then a direct cross reference can be made by comparing the temperature of the air as it enters the Duct Heater to the KW rating on the chart of rated velocity a Draw a line horizontally from the Watts Sq...

Страница 4: ...insulation left in place or duct constructed from insulation board Recess Insulation Thickness Note Size of heater is based on the following Heater H Duct H Insulation Thickness x 2 Heater W Duct W Insulation Thickness recess required Internal insulation cut away The internal insulation is to be removed from the area where the heater is mounted Recess Insulation Thickness Note Size of heater is ba...

Страница 5: ...ct heater with electronic step controller or SSR control Without Remote Sensor With Remote Sensor Note Do not adjust dip switches on thermostat Viconics C1025 11 Room Thermostat Viconics C1025 11 Room Thermostat Viconics S61 Remote Sensor Duct Heater Signal Interface Module Duct Heater Signal Interface Module Note This heater will not operate with a standard 24 VAC control signal Do not adjust any...

Страница 6: ...e in duct size downstream from an air handler upstream from a humidifier downstream from an air filter fan 7 Never install a standard heater into a duct with an internal obstruction An obstruction can block airflow at the temperature limit controls and element terminations If this situation exists it can be corrected by using a heater with recessed control box and reduced wrapper size This situati...

Страница 7: ...insulation could breakdown 14 Never use a different voltage and or phase than what is listed on the heater nameplate label The duct heater is to be used only at the voltage and phase that is listed on the name plate label Note An airflow switch only proves that airflow exists a differential in static pressure not that the minimum air velocities and proper air distribution for the duct heater exist...

Страница 8: ...eck Fan Corporation As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Specific Greenheck product warranties are located on greenheck com within the product area tabs and in the Library under Warranties Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo greenheck com Website www greenheck com Our Commitment ...

Отзывы: