background image

IOM ERH FS

Rev. 1 January 2002

Warranty

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a
period of five years from the purchase date. Any units or parts which prove defective during the warranty period will be
replaced at our option when returned to our factory, transportation prepaid.

Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove
defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not
be responsible for any removal or installation costs.

GREENHECK

P.O. BOX 410  SCHOFIELD, WISCONSIN 54476-0410

PH. 715-359-6171

www.greenheck.com

®

Due to continuing product development Greenheck has the right to change specifications without notice

* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.

Energy Wheel

Does NOT Turn

Blower fan motor overloads are
tripping and auto-resetting.

Decrease fan speed.

Possible Cause

Symptom

Corrective Action

Exhaust Only frost control
sensors are tripping.

Adjust frost temperature sensor set point as needed.

Air seals are too tight.

See Energy Recovery Wheel on page 12

“Economizer” sensors are
operating.

Adjust temperature or enthalpy set points as needed.

No power to wheel motor.

Make sure wheel drive is plugged in. Verify power is
available.

Wheel drive belt

Check for loose or broken belts. Replace belts (consult
factory).

One or Both

Blowers Turn Off

Intermittently and

Back on After

About 2 Minutes

Wheel motor overloads are
tripping, due to rubbing
between wheel and air seals.

Recheck air seals, make sure they are not too tight. See
Energy Recovery Wheel on page 12.

Fan wheel rubbing on inlet

Adjust wheel and/or inlet cone. Tighten wheel hub or bearing
collars on shaft.

Bearings.

Replace defective bearings (s). Lubricate bearings. Tighten
collars and fasteners.

Wheel out of balance.

Replace or rebalance.

Loose wheel on shaft.

Tighten wheel setscrew.

Energy Wheel

Runs Intermittently

Loose motor or blower sheave.

Tighten sheave setscrew.

Belts too loose.

Adjust belt tension after 24 hours of operation.

Belts too tight.

Loosen to maintain a 3/8 inch deflection per foot of span
between sheaves.

Worn belt.

Replace.

Motor base or blower loose.

Tighten mounting bolts.

Build up of material on wheel.

Clean wheel and housing.

Bearing and drive misaligned.

Realign.

Noise being transmitted by
duct.

Make sure duct work is supported properly. Make sure duct
work metal thickness is sized for proper stiffness. Check duct
size at discharge to ensure that air velocities are not too high.

Excessive Noise or

Vibration

Trouble Shooting

Copyright © 2002 Greenheck Fan Corp.

Содержание ERH-20

Страница 1: ...E TO COMPLY WITH THIS SAFETY PRECAUTION COULD RESULT IN PROPERTY DAMAGE SERIOUS INJURY OR DEATH PART 459657 READ AND SAVE THESE INSTRUCTIONS ENERGY RECOVERY UNIT with HEATING Models ERH 20 45 55 90 IN...

Страница 2: ...n wheel 11 Fan RPM 12 Energy Recovery Wheel 12 Coils 12 Routine Maintenance 13 14 Belts 13 Motors 13 Blower Wheel and Fasteners 13 Vibration 14 Filters 14 Coil Maintenance 15 Energy Recovery Wheel Mai...

Страница 3: ...nsure stability and balance Avoid twisting or uneven lifting of the unit Never lift units by weatherhoods The ERH brings in fresh outdoor air and removes stale exhaust air Prior to discharging the exh...

Страница 4: ...ervice clearances Keep the supply inlet of the unit away from any other exhaust fans 3 Install Curb Locate curb over roof opening and fasten in place Check that the diagonal dimensions are within 1 8...

Страница 5: ...nect separate from the unit disconnect Thus electric post heaters require a separate power connection IMPORTANT Use minimum 14 ga wire for 24 volt control power Control wire resistance should not exce...

Страница 6: ...ntenance that must be performed Blower and motor assemblies energy recovery wheel cassette coil and filter sections are always provided with a service door or panel for proper component access Clearan...

Страница 7: ...S HIGHLY RECOMMENDED 5 Pipe sizes for the system must be selected on the basis of the head pressure available from the circulation pump The velocity should not exceed 6 feet per second and the frictio...

Страница 8: ...irst stage of the preheater will turn on If the first stage does not satisfy the set point the second stage will also turn on Post heaters Post heaters are standard as 4 stage step control Post heater...

Страница 9: ...ches the thermostat setting the electric preheater will turn on and warm the air entering the energy wheel Testing Turn the thermostat as high as it will go The heater should turn on If it doesn t eit...

Страница 10: ...nsor up as high as it goes and keep the Override sensor as low as it will go The wheel should stop rotating Turn both sensors as high as they will go The wheel should start rotating Set the Temperatur...

Страница 11: ...ree phase units interchange any two power leads this can be done at the motor starter START UP CHECKS WARNING DO NOT OPERATE ENERGY RECOVERY VENTILATOR WITHOUT THE FILTERS AND BIRDSCREENS INSTALLED TH...

Страница 12: ...sen all eight seal retaining screws These screws are located on the bearing support that spans the length of the cassette through the wheel center Tighten the screws so the air seals tug slightly on t...

Страница 13: ...MOTORS Motor maintenance is generally limited to cleaning and lubrication where applicable Cleaning should be limited to exterior surfaces only Removing dust and grease build up on the motor housing a...

Страница 14: ...FIGURE 19 Internal Model Filter Size Quantity ERH 20 20 x 20 2 ERH 45 20 x 25 3 ERH 55 16 x 25 6 ERH 90 20 x 20 8 VIBRATION Excessive vibration maybe experienced during initial start up Left unchecke...

Страница 15: ...from the fan and create an environment for odor and bacteria to grow and spread through the conditioned zone High pressure water 700 Psi or less may be used to clean coils with fin thickness over 0 0...

Страница 16: ...by entering the unit through the Exhaust Blower access door WARNING Disconnect power to the unit before performing any type of service ACCESSING ENERGY RECOVERY WHEEL FIGURE 21 ROUTINE ENERGY RECOVERY...

Страница 17: ...eaning is complete shake the excess water from the wheel or segments Dry wheel or segments before placing them back into the cassette Place wheel or segments back into cassette by reversing removal pr...

Страница 18: ...minum mesh filter 6 Optional exhaust weatherhood with birdscreen 7 Optional supply and exhaust air filter racks with 2 in pleated 30 efficient filters 8 Electrical control box standard features Single...

Страница 19: ...higher or lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage incorrect Check mo...

Страница 20: ...eded Air seals are too tight See Energy Recovery Wheel on page 12 Economizer sensors are operating Adjust temperature or enthalpy set points as needed No power to wheel motor Make sure wheel drive is...