The energy recovery wheel may be de-energized for the purpose of providing economizer (free cooling)
operation. This can be achieved with a signal from a Temperature or Enthalpy sensor mounted in the supply air
inlet compartment (see FIGURE 13). This Primary sensor will de-energize the energy wheel when the outdoor air
temperature (factory default is 65°F) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable
set point. An additional Override temperature sensor is also furnished in the supply air inlet compartment to
deactivate economizer mode (see FIGURE 13). The Override (with field adjustable set point) is set at some
temperature lower than the Primary sensor (factory default is 50°F). Effectively, the two sensors create a
deadband where the energy recovery wheel will not operate and free cooling from outside can be brought into
the building unconditioned.

Testing 

(terminals referenced below are in the unit control center — see FIGURE 5, Item #7)

Temperature sensor with Override

• Turn both Temperature and Override

thermostats down as low as they go.
The wheel should be rotating.

• Turn the Temperature sensor up as

high as it goes, and keep the Override
sensor as low as it will go. The wheel
should stop rotating.

• Turn both sensors as high as they will

go. The wheel should start rotating. 

• Set the Temperature sensor to the

desired temperature for economizer
operation to begin. Set the Override
sensor to the desired temperature for
economizer operation to end (factory
default is 65°F and 50°F, respectively).

Enthalpy sensor with Override

• A factory-installed 620 ohm resistor is

connected across terminals SR and +.
The Override sensor should be turned
down below current temperature in unit. Turn the unit on; LED on the sensor should be off. Check
continuity across terminals 2 and 3, there should not be continuity. There should be continuity
between terminals 1 and 2.

• Disconnect the 620 ohm resistor from terminals SR and +. LED should turn on. There should be

continuity between terminals 2 and 3. There should not be continuity between terminals 1 and 2.

• Turn the Override sensor above current temperature in unit. There should be continuity between

terminals 3 and 6. Set the Override sensor to the desired temperature for economizer operation to end
(factory default is 50°F).

• Reconnect the factory-installed jumper.

10

ECONOMIZER APPLICATION/OPERATION

Enthalpy Sensor
(Primary Sensor)

Timed Exhaust

Frost Control

Override

Probes

FIGURE 13

Содержание ERH-20

Страница 1: ...E TO COMPLY WITH THIS SAFETY PRECAUTION COULD RESULT IN PROPERTY DAMAGE SERIOUS INJURY OR DEATH PART 459657 READ AND SAVE THESE INSTRUCTIONS ENERGY RECOVERY UNIT with HEATING Models ERH 20 45 55 90 IN...

Страница 2: ...n wheel 11 Fan RPM 12 Energy Recovery Wheel 12 Coils 12 Routine Maintenance 13 14 Belts 13 Motors 13 Blower Wheel and Fasteners 13 Vibration 14 Filters 14 Coil Maintenance 15 Energy Recovery Wheel Mai...

Страница 3: ...nsure stability and balance Avoid twisting or uneven lifting of the unit Never lift units by weatherhoods The ERH brings in fresh outdoor air and removes stale exhaust air Prior to discharging the exh...

Страница 4: ...ervice clearances Keep the supply inlet of the unit away from any other exhaust fans 3 Install Curb Locate curb over roof opening and fasten in place Check that the diagonal dimensions are within 1 8...

Страница 5: ...nect separate from the unit disconnect Thus electric post heaters require a separate power connection IMPORTANT Use minimum 14 ga wire for 24 volt control power Control wire resistance should not exce...

Страница 6: ...ntenance that must be performed Blower and motor assemblies energy recovery wheel cassette coil and filter sections are always provided with a service door or panel for proper component access Clearan...

Страница 7: ...S HIGHLY RECOMMENDED 5 Pipe sizes for the system must be selected on the basis of the head pressure available from the circulation pump The velocity should not exceed 6 feet per second and the frictio...

Страница 8: ...irst stage of the preheater will turn on If the first stage does not satisfy the set point the second stage will also turn on Post heaters Post heaters are standard as 4 stage step control Post heater...

Страница 9: ...ches the thermostat setting the electric preheater will turn on and warm the air entering the energy wheel Testing Turn the thermostat as high as it will go The heater should turn on If it doesn t eit...

Страница 10: ...nsor up as high as it goes and keep the Override sensor as low as it will go The wheel should stop rotating Turn both sensors as high as they will go The wheel should start rotating Set the Temperatur...

Страница 11: ...ree phase units interchange any two power leads this can be done at the motor starter START UP CHECKS WARNING DO NOT OPERATE ENERGY RECOVERY VENTILATOR WITHOUT THE FILTERS AND BIRDSCREENS INSTALLED TH...

Страница 12: ...sen all eight seal retaining screws These screws are located on the bearing support that spans the length of the cassette through the wheel center Tighten the screws so the air seals tug slightly on t...

Страница 13: ...MOTORS Motor maintenance is generally limited to cleaning and lubrication where applicable Cleaning should be limited to exterior surfaces only Removing dust and grease build up on the motor housing a...

Страница 14: ...FIGURE 19 Internal Model Filter Size Quantity ERH 20 20 x 20 2 ERH 45 20 x 25 3 ERH 55 16 x 25 6 ERH 90 20 x 20 8 VIBRATION Excessive vibration maybe experienced during initial start up Left unchecke...

Страница 15: ...from the fan and create an environment for odor and bacteria to grow and spread through the conditioned zone High pressure water 700 Psi or less may be used to clean coils with fin thickness over 0 0...

Страница 16: ...by entering the unit through the Exhaust Blower access door WARNING Disconnect power to the unit before performing any type of service ACCESSING ENERGY RECOVERY WHEEL FIGURE 21 ROUTINE ENERGY RECOVERY...

Страница 17: ...eaning is complete shake the excess water from the wheel or segments Dry wheel or segments before placing them back into the cassette Place wheel or segments back into cassette by reversing removal pr...

Страница 18: ...minum mesh filter 6 Optional exhaust weatherhood with birdscreen 7 Optional supply and exhaust air filter racks with 2 in pleated 30 efficient filters 8 Electrical control box standard features Single...

Страница 19: ...higher or lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage incorrect Check mo...

Страница 20: ...eded Air seals are too tight See Energy Recovery Wheel on page 12 Economizer sensors are operating Adjust temperature or enthalpy set points as needed No power to wheel motor Make sure wheel drive is...

Отзывы: