High Volume, Low Speed Ceiling Fans

4

®

B

A

3 FT. CLEARANCE AROUND BLADES

2X FAN DIAMETER 

FROM HVAC

MINIMUM 10 FT. ABOVE

FINISHED FLOOR

HVAC

DIFFUSER

WHEN FULL DIFFUSER OUTLET 

IS BELOW HVLS FAN,

 HVLS FAN MUST BE 1X FAN DIAMETER AWAY

3 FT. CLEARANCE AROUND BLADES

Minimum Spacing Requirements

Minimum Spacing From Center of Fan (ft.)

Fan Size (ft.)

A

B

16

24

48

20

30

60

24

36

72

Pre-Installation Checks

IMPORTANT: 

Consult all applicable national, state 

and local codes to ensure that all necessary code 
requirements are met. It is the sole responsibility of the 
installer to ensure compliance with applicable codes.
Prior to installing the fan, perform each of the following 
checks:
  1.  Verify that fan components are undamaged. Do not 

install or operate any damaged fan components, 
fans, or fan accessories. Failure to comply with 
this instruction may result in property damage, 
personal injury and/or death.

  2.  Verify that the fan is to be installed in a location 

where the airfoils will be a minimum of 10 ft. 
above the finished floor with a minimum of 
3 ft. of horizontal and vertical clearance to any 
obstructions. 

  3.  Verify that the fan is to be installed in a location 

where the center of the fan is a minimum of 1.5 fan 
diameters away from building walls and corners.

  4.  For best performance, the fan must be installed 

with a two fan diameter minimum clearance to 
radiant heaters and HVAC system discharges or 
intakes.

  5.  Check that the fan will not be mounted in a 

location near overhead doors or other building 
openings where gusts of wind may occur. Fan 
should not be installed or operated in locations 
where wind is present.

  6.  If the building is equipped with a fire sprinkler 

system, verify that the placement of the fan will 
not interfere with correct sprinkler operation and 
that the fan installation complies with all national, 
state and local codes. For NFPA 13 compliance, 
fan must be installed in the center of four adjacent 
sprinklers with at least 3 ft. of vertical clearance 
between the fan and sprinkler deflectors. Fan must 
also be interlocked to shut down upon receiving a 
waterflow signal from the building’s alarm system. 

  7.  Check to see if the intended placement of the fan 

is directly below any building lights or skylights. If 
possible, avoid installing fan directly below a light 
source to prevent a strobing effect that can be 
caused by fan rotation. 

  8.  If the building has a mezzanine or other elevated 

spaces that may be occupied by people, verify 
that no component of the fan can be reached 
from the highest level or deck. The fan must be 
positioned so that the tips of the airfoils are a 
minimum of 3 ft. away from the furthest point 
that a person could reach or otherwise come in 
contact, to prevent injury. 

  9.  If the fan is to be mounted in an area where 

materials or equipment may be elevated into its 
path, ensure that the floor is marked or painted 

to alert personnel of the overhead location of the 
fan(s).

 10.  Before installation, it is important to verify that the 

mounting surface will bear the operating weight 
and maximum torque (twisting force) of the unit. 
The Structural Engineer of Record (SEOR) must 
perform a thorough evaluation of the mounting 
structure and determine all final mounting 
requirements before the fan is installed. It is the 
sole responsibility of the installer to ensure that the 
mounting structure and fan installation method are 
adequate for safe operation of the fan.

Fan Size 

(ft.)

DS-M3

*Max. Fan 

Weight (lbs)

Max Torque 

(ft∙lbf)

16

192

36.7

20

201

50.6

24

210

54.0

*Maximum weight is shown in pounds and includes all available 
options, actual fan weight may be less. 

General Information

Содержание DS-M

Страница 1: ...e servicing or cleaning unit switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot...

Страница 2: ...ailability of transportation and truck space Confirmation of shipment s must be limited to only items on the bill of lading Storage Fans are protected against damage during shipment If the unit cannot...

Страница 3: ...n 1 General Information 4 Minimum Spacing Requirements 4 Fan Components 5 Optional Fan Components 6 Required Tools 6 Mounting Installation 7 Motor Hub to Downtube Installation 10 Fan Networking 11 Saf...

Страница 4: ...fan will not interfere with correct sprinkler operation and that the fan installation complies with all national state and local codes For NFPA 13 compliance fan must be installed in the center of fou...

Страница 5: ...VFD Cover 1 DOWNTUBE MOU MOTOR HUB ASSEMBLY FRONT VFD COVER RE POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUN...

Страница 6: ...lt 4 Wood Beam Hardware Kit Optional Bag 915429 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT WOOD BEAM WOOD BEAM BRACKET 1 2 in 13 GRADE B Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1...

Страница 7: ...versal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknut I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSA...

Страница 8: ...Downtube Installation Wood Beam Mounting Kit For Beams 41 2 87 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut...

Страница 9: ...e to 80 ft lbf 108 5 N m STRUCTURAL STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m T...

Страница 10: ...OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL SAFETY RETENTION CABLE 4 Using a Phillips screwdriver remove the front VFD cover and set aside 5...

Страница 11: ...be adjusted using the following instructions DIPSWITCH 3 DIPSWITCH 2 First Fan FIRST FAN IN SERIES ALL OTHER FANS IN SERIES 1 Determine the first fan in the network daisy chain by identifying the fan...

Страница 12: ...Positions 6 8 are used to set parameters needed for fan operation and should not be adjusted NOTE It is good practice to use successive Modbus addresses for networked fans but this is not necessary f...

Страница 13: ...ve end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be installed a minimum of 5 inches away from...

Страница 14: ...ome in contact with any sharp edges 5 Insert the loose end of the safety cable into the open hole of the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one...

Страница 15: ...y from the dead end of the guy wire to ensure proper functioning IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over t...

Страница 16: ...ll 4 turnbuckles to the guy wire attachment ring located on the downtube using 4 supplied quick links Pull the loose end of each guy wire through the No 4 Gripple connector until each guy wire is taut...

Страница 17: ...e installed bolts to 25 ft lbf 34 N m 5 16 in 18 x 2 GRADE 8 BOLT 2 PER BLADE TORQUE TO 25 FT LBF 34 N m IMPORTANT If airfoils must be removed and reinstalled for any reason do not re use the supplied...

Страница 18: ...ncy stop landing point and the building s fire suppression system using the wiring diagram shown Communication Wiring Fan Control Installation IMPORTANT DS M fans must be installed with the supplied C...

Страница 19: ...ns on page 11 to complete network setup for the fans With Optional 1 000 ft Bulk Spool of CAT 5e Cable Included Component 1 000 ft Bulk Spool of CAT 5e Control Cable 1 Shielded Pass Through RJ45 Conne...

Страница 20: ...1 Refer to the wiring diagrams below to complete power wiring 2 Secure any loose power cable to the building structure to ensure it does not interfere with fan performance POWER CABLE FROM FAN POWER...

Страница 21: ...personnel who are familiar with local codes and regulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to...

Страница 22: ...ension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switches turned off or disconnected Check for cor...

Страница 23: ...Volts 1 units 15 Voltage Output RMS R xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 M...

Страница 24: ...___________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ ______________________________...

Отзывы: