Greenheck DS-M Скачать руководство пользователя страница 15

High Volume, Low Speed Ceiling Fans

15

®

Guy Wire Installation

IMPORTANT: 

Guy wires must be installed 45º to 60º 

from vertical to ensure proper functioning.

Standard Steel Cable Clamp

Components required from Bag # 916290:
  •  Guy Wire Clamp Assembly (4)
  •  Guy Wire Clamp Bolt (4)
  •  Quick Link (8)
  •  20 ft. Guy Wire (4)
  •  U-Bolt Steel Cable Clamp (8)
  •  Turnbuckle (4)
Hardware/Tools Needed (Not Included):
 • Level
  •  Torque Wrench
  •  7/16 in. Socket and Wrench
  •  5/16 in. Socket and Wrench
  •  Adjustable Wrench
  •  Cable Cutters (optional)

  1.  Secure guy wire clamps to the building structure 

using the guy wire clamp bolts and an adjustable 
wrench. Attach guy wires to the eyelets on the guy 
wire clamp assemblies using (4) supplied quick 
links.

DOWNTUBE & MOUNT ASSEMBLY

UG2 GRIPPLE

®

 TURNBUCKLE

GUY WIRE

GUY WIRE

GUY WIRE

GUY WIRE CLAMP ASSEMBLY

GUY WIRE CLAMP BOLT

45º to 60º

UG2 GRIPPLE

®

 TURNBUCKLE

GUY WIRE ATTACHMENT RING

QUICK LINK

  2.  Insert the loose end of each guy wire through the 

eyebolt on a turnbuckle. Turn the guy wire back 
onto itself and align the loose end of the guy wire 
(referred to as the dead-end) with the length of 
guy wire that is attached to the building structure 
(referred to as the live-end).

  3.  Attach the dead-end of each guy wire to the live-

end using (2) of the supplied 0.094 in. u-bolt steel 
cable clamps. Loosely tighten the nuts on the steel 
cable clamps, leaving enough room for the guy 
wire to slide through the steel cable clamps. 

IMPORTANT: 

The first steel cable clamp must be 

installed a minimum of 51/2 inches away from the dead-
end of the guy wire to ensure proper functioning.

IMPORTANT: 

Steel cable clamps consist of two parts: 

the u-bolt and the saddle. Steel cable clamps must be 
installed with the u-bolt over the dead-end of the guy 
wire and the saddle over the live-end of the guy wire. 
Failure to install steel cable clamps in this manner may 
result in unsafe operating conditions. Refer to drawing 
below for correct orientation.

DOWNTUBE & MOUNT

ASSEMBLY

GUY WIRE

45º to 60º

TURNBUCKLE

GUY WIRE 

ATTACHMENT RING

CABLE CLAMP

QUICK LINK

5-1/2 IN.

MIN.

TORQUE TO 54 IN∙LBF

(6.10 N∙m)

DEAD END

LIVE END

  4.  Attach all (4) turnbuckles to the guy wire 

attachment ring located on the downtube using 
(4) supplied quick links.

  5.  Pull the dead-end of each guy wire through the 

steel cable clamps until taut.

  6.  Tighten the nuts on the steel cable clamps using a 

7/16 in. socket and torque to 54 in∙lbf (6.10 N∙m), 
alternating between nuts until reaching proper 
torque.

  7.  Place a level against the downtube and tighten all 

(4) turnbuckles by hand in a crisscross pattern until 
the guy wires are tight and the fan is level. 

NOTE: 

When leveling the fan, place the level against 

the downtube in-between two neighboring guy wires 
to simplify the leveling process. The level should also 
be moved around the circumference of the downtube 
periodically to ensure that the fan is level in all 
directions.
  8.  Cut or organize excess guy wires to ensure that 

they do not interfere with fan performance. Make 
sure to leave at least 51/2 inches of wire between 
the dead-end of the guy wire and the first wire rope 
clip to ensure proper functioning.

Содержание DS-M

Страница 1: ...e servicing or cleaning unit switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot...

Страница 2: ...ailability of transportation and truck space Confirmation of shipment s must be limited to only items on the bill of lading Storage Fans are protected against damage during shipment If the unit cannot...

Страница 3: ...n 1 General Information 4 Minimum Spacing Requirements 4 Fan Components 5 Optional Fan Components 6 Required Tools 6 Mounting Installation 7 Motor Hub to Downtube Installation 10 Fan Networking 11 Saf...

Страница 4: ...fan will not interfere with correct sprinkler operation and that the fan installation complies with all national state and local codes For NFPA 13 compliance fan must be installed in the center of fou...

Страница 5: ...VFD Cover 1 DOWNTUBE MOU MOTOR HUB ASSEMBLY FRONT VFD COVER RE POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUN...

Страница 6: ...lt 4 Wood Beam Hardware Kit Optional Bag 915429 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT WOOD BEAM WOOD BEAM BRACKET 1 2 in 13 GRADE B Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1...

Страница 7: ...versal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknut I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSA...

Страница 8: ...Downtube Installation Wood Beam Mounting Kit For Beams 41 2 87 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut...

Страница 9: ...e to 80 ft lbf 108 5 N m STRUCTURAL STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m T...

Страница 10: ...OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL SAFETY RETENTION CABLE 4 Using a Phillips screwdriver remove the front VFD cover and set aside 5...

Страница 11: ...be adjusted using the following instructions DIPSWITCH 3 DIPSWITCH 2 First Fan FIRST FAN IN SERIES ALL OTHER FANS IN SERIES 1 Determine the first fan in the network daisy chain by identifying the fan...

Страница 12: ...Positions 6 8 are used to set parameters needed for fan operation and should not be adjusted NOTE It is good practice to use successive Modbus addresses for networked fans but this is not necessary f...

Страница 13: ...ve end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be installed a minimum of 5 inches away from...

Страница 14: ...ome in contact with any sharp edges 5 Insert the loose end of the safety cable into the open hole of the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one...

Страница 15: ...y from the dead end of the guy wire to ensure proper functioning IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over t...

Страница 16: ...ll 4 turnbuckles to the guy wire attachment ring located on the downtube using 4 supplied quick links Pull the loose end of each guy wire through the No 4 Gripple connector until each guy wire is taut...

Страница 17: ...e installed bolts to 25 ft lbf 34 N m 5 16 in 18 x 2 GRADE 8 BOLT 2 PER BLADE TORQUE TO 25 FT LBF 34 N m IMPORTANT If airfoils must be removed and reinstalled for any reason do not re use the supplied...

Страница 18: ...ncy stop landing point and the building s fire suppression system using the wiring diagram shown Communication Wiring Fan Control Installation IMPORTANT DS M fans must be installed with the supplied C...

Страница 19: ...ns on page 11 to complete network setup for the fans With Optional 1 000 ft Bulk Spool of CAT 5e Cable Included Component 1 000 ft Bulk Spool of CAT 5e Control Cable 1 Shielded Pass Through RJ45 Conne...

Страница 20: ...1 Refer to the wiring diagrams below to complete power wiring 2 Secure any loose power cable to the building structure to ensure it does not interfere with fan performance POWER CABLE FROM FAN POWER...

Страница 21: ...personnel who are familiar with local codes and regulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to...

Страница 22: ...ension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switches turned off or disconnected Check for cor...

Страница 23: ...Volts 1 units 15 Voltage Output RMS R xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 M...

Страница 24: ...___________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ ______________________________...

Отзывы: