High Volume, Low Speed Ceiling Fans

12

®

All Remaining Fans

FIRST FAN IN SERIES

ALL OTHER FANS IN SERIES

  1.  Remove the front VFD cover using a phillips 

screwdriver.

  2.  On the communication wiring terminal strip, 

remove the 24V (brown-white) wire and cap with 
a wire nut or heat shrink. Additionally, remove the 
stranded silver drain wire that is attached to the 
circuit board mounting screw and isolate from all 
circuit board components using heat shrink.

  3.  Set dipswitch 2 as shown below. Dipswitch 2 is 

used to set parameters that improve network 
function and will need to be adjusted for all fans in 
the network except for the first fan.

      Position 1 – Off 
      Position 2 – Off
      Position 3 – Off 
  4.  Adjust positions 1 – 5 on dipswitch 3 so that each 

successive fan has a unique Modbus address. A 
table with all possible Modbus addresses is shown 
below. 

IMPORTANT:

 Positions 6 – 8 are used to set parameters 

needed for fan operation and should not be adjusted.

NOTE: 

It is good practice to use successive Modbus 

addresses for networked fans, but this is not necessary 
for proper functioning of the network. 
  4.  Reinstall the front VFD cover.

Modbus Address Settings - Dipswitch 3

Modbus 

Address

Position 

1

Position 

Position 

3

Position 

4

Position 

5

Position 

6, 7, 8

1

Off

Off

Off

Off

Off

Do Not 

Modify

2

On

Off

Off

Off

Off

3

Off

On

Off

Off

Off

4

On

On

Off

Off

Off

5

Off

Off

On

Off

Off

6

On

Off

On

Off

Off

7

Off

On

On

Off

Off

8

On

On

On

Off

Off

9

Off

Off

Off

On

Off

10

On

Off

Off

On

Off

11

Off

On

Off

On

Off

12

On

On

Off

On

Off

13

Off

Off

On

On

Off

14

On

Off

On

On

Off

15

Off

On

On

On

Off

16

On

On

On

On

Off

17

Off

Off

Off

Off

On

18

On

Off

Off

Off

On

19

Off

On

Off

Off

On

20

On

On

Off

Off

On

21

Off

Off

On

Off

On

22

On

Off

On

Off

On

23

Off

On

On

Off

On

24

On

On

On

Off

On

25

Off

Off

Off

On

On

26

On

Off

Off

On

On

27

Off

On

Off

On

On

28

On

On

Off

On

On

29

Off

Off

On

On

On

30

On

Off

On

On

On

31

Off

On

On

On

On

Содержание DS-M

Страница 1: ...e servicing or cleaning unit switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot...

Страница 2: ...ailability of transportation and truck space Confirmation of shipment s must be limited to only items on the bill of lading Storage Fans are protected against damage during shipment If the unit cannot...

Страница 3: ...n 1 General Information 4 Minimum Spacing Requirements 4 Fan Components 5 Optional Fan Components 6 Required Tools 6 Mounting Installation 7 Motor Hub to Downtube Installation 10 Fan Networking 11 Saf...

Страница 4: ...fan will not interfere with correct sprinkler operation and that the fan installation complies with all national state and local codes For NFPA 13 compliance fan must be installed in the center of fou...

Страница 5: ...VFD Cover 1 DOWNTUBE MOU MOTOR HUB ASSEMBLY FRONT VFD COVER RE POWER CABLE PLUG OPTIONAL LIGHT POWER CABLE OPTIONAL SAFETY CABLE WITH NO 4 GRIPPLE FACTORY INSTALLED VFD FIRE ALARM LANDING POINT COMMUN...

Страница 6: ...lt 4 Wood Beam Hardware Kit Optional Bag 915429 1 2 in WASHER 1 2 in 13 GRADE 8 NYLON LOCKNUT WOOD BEAM WOOD BEAM BRACKET 1 2 in 13 GRADE B Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1...

Страница 7: ...versal mounting plate is snug against the beam but can still be moved approximately 1 4 in of the bolt threads exposed below the nylon locknut I BEAM CLAMPING PLATE I BEAM CLAMPING PLATE SHIM UNIVERSA...

Страница 8: ...Downtube Installation Wood Beam Mounting Kit For Beams 41 2 87 8 in Wide Components required from Bag 915429 Wood Beam Bracket 2 1 2 in 13 x 11 2 in Grade 8 Hex Bolt 4 1 2 in 13 Grade 8 Nylon Locknut...

Страница 9: ...e to 80 ft lbf 108 5 N m STRUCTURAL STEEL ANGLES BY OTHERS 1 2 in 13 x 1 3 4 in GRADE 8 HEX BOLT Z PURLIN 1 2 in WASHER Z PURLIN BRACKET 1 2 in 13 GRADE 8 NYLON LOCKNUT TORQUE TO 80 FT LBF 108 5 N m T...

Страница 10: ...OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL LIGHT POWER PLUG OPTIONAL LIGHT COMMUNICATION PLUG OPTIONAL SAFETY RETENTION CABLE 4 Using a Phillips screwdriver remove the front VFD cover and set aside 5...

Страница 11: ...be adjusted using the following instructions DIPSWITCH 3 DIPSWITCH 2 First Fan FIRST FAN IN SERIES ALL OTHER FANS IN SERIES 1 Determine the first fan in the network daisy chain by identifying the fan...

Страница 12: ...Positions 6 8 are used to set parameters needed for fan operation and should not be adjusted NOTE It is good practice to use successive Modbus addresses for networked fans but this is not necessary f...

Страница 13: ...ve end 4 Attach the dead end of the safety cable to the live end using the supplied 0 188 in u bolt steel cable IMPORTANT The first steel cable clamp must be installed a minimum of 5 inches away from...

Страница 14: ...ome in contact with any sharp edges 5 Insert the loose end of the safety cable into the open hole of the No 4 Gripple connector Note that the cable will only feed through the Gripple connector in one...

Страница 15: ...y from the dead end of the guy wire to ensure proper functioning IMPORTANT Steel cable clamps consist of two parts the u bolt and the saddle Steel cable clamps must be installed with the u bolt over t...

Страница 16: ...ll 4 turnbuckles to the guy wire attachment ring located on the downtube using 4 supplied quick links Pull the loose end of each guy wire through the No 4 Gripple connector until each guy wire is taut...

Страница 17: ...e installed bolts to 25 ft lbf 34 N m 5 16 in 18 x 2 GRADE 8 BOLT 2 PER BLADE TORQUE TO 25 FT LBF 34 N m IMPORTANT If airfoils must be removed and reinstalled for any reason do not re use the supplied...

Страница 18: ...ncy stop landing point and the building s fire suppression system using the wiring diagram shown Communication Wiring Fan Control Installation IMPORTANT DS M fans must be installed with the supplied C...

Страница 19: ...ns on page 11 to complete network setup for the fans With Optional 1 000 ft Bulk Spool of CAT 5e Cable Included Component 1 000 ft Bulk Spool of CAT 5e Control Cable 1 Shielded Pass Through RJ45 Conne...

Страница 20: ...1 Refer to the wiring diagrams below to complete power wiring 2 Secure any loose power cable to the building structure to ensure it does not interfere with fan performance POWER CABLE FROM FAN POWER...

Страница 21: ...personnel who are familiar with local codes and regulations and have experience with this type of equipment Once the fan has been put into operation a periodic maintenance program should be set up to...

Страница 22: ...ension if applicable Defective motor Replace motor Defective variable frequency drive VFD Replace VFD Fan does not operate Electrical supply Check for switches turned off or disconnected Check for cor...

Страница 23: ...Volts 1 units 15 Voltage Output RMS R xxx 0 1000 RMS Modulated Output Voltage Volts 1 units 16 Current Motor RMS R xx x 0 150 RMS Motor current Amps 0 1 units 17 Temperature Motor R S xxx x 300 1100 M...

Страница 24: ...___________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ ______________________________...

Отзывы: