Microprocessor Controller for DOAS
45
®
Active_Temperature_
Setpoint
Active Temperature Set
point
132
AV
ReadCOV_
NoWrite
0.1
30179
Input
2
Chilled_Water_1_
Valve_Analog_Output
Chilled Water 1 Valve
Analog Output
201
AV
ReadCOV_
NoWrite
0.1
30473
Input
2
Condenser_1_Analog_
Output
Condenser 1 Analog Output
205
AV
ReadCOV_
NoWrite
0.1
30481
Input
2
Condenser_2_Analog_
Output
Condenser 2 Analog Output
206
AV
ReadCOV_
NoWrite
0.1
30483
Input
2
Electric_Heater_1_
Analog_Output
Electric Heater 1 Analog
Output
221
AV
ReadCOV_
NoWrite
0.1
30513
Input
2
Energy_Recovery_
Analog_Output
Energy Recovery Analog
Output
229
AV
ReadCOV_
NoWrite
0.1
30517
Input
2
Exhaust_Fan_Speed_
Analog_Output
Exhaust Fan Speed Analog
Output
231
AV
ReadCOV_
NoWrite
0.1
30521
Input
2
Hot_Gas_Reheat_
Analog_Output
Hot Gas Reheat Analog
Output
235
AV
ReadCOV_
NoWrite
0.1
30523
Input
2
Hot_Water_Valve_1_
Analog_Output
Hot Water Valve 1 Analog
Output
236
AV
ReadCOV_
NoWrite
0.1
30525
Input
2
Mod_Gas_Furnace_1_
Analog_Output
Mod Gas Furnace 1 Analog
Output
242
AV
ReadCOV_
NoWrite
0.1
30537
Input
2
Outside_Air_Damper_
Analog_Output
Outside Air Damper Analog
Output
250
AV
ReadCOV_
NoWrite
0.1
30541
Input
2
Supply_Fan_Speed_
Analog_Output
Supply Fan Speed Analog
Output
264
AV
ReadCOV_
NoWrite
0.1
30557
Input
2
Modulating_
Compressor_Analog_
Output_BMS
Modulating Compressor
Analog Output - Valent BMS
285
AV
ReadCOV_
NoWrite
0.1
30585
Input
2
Circuit_A_Sat_
Discharge_
Temperature
Circuit A Saturated
Discharge Temperature
286
AV
ReadCOV_
NoWrite
0.1
30587
Input
2
Circuit_B_Sat_
Discharge_
Temperature
Circuit B Saturated
Discharge Temperature
287
AV
ReadCOV_
NoWrite
0.1
30589
Input
2
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST
INDEX
REGISTER
TYPE
SIZE